MDP-FT [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MDP-FT
型号: MDP-FT
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总4页 (文件大小:122K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MDP-FT  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
RELATED PRODUCTS  
• Telemetering module (model: TMS)  
• 300 bps modem (model: MOD2)  
• 1200 bps modem (model: MOD3x)  
• Voice/data modem (model: MOD4)  
• 1200 bps modem (model: MOD5)  
LIGHTNING SURGE PROTECTOR FOR TELEMETERING USE  
(3.4 kHz)  
Functions & Features  
• Designed specifically to protect telemetering systems  
utilizing leased circuit  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
• Applied to modems for computer using audio band signals  
and to telemetering systems  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
• Absorbs surges only without affecting instrumentation  
signal  
• No interruption of signal by unplugging the protector  
element  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
23.5 (.93)  
Weight:  
120 g (0.26 lb), standard  
Lot.NO  
N1430B  
100  
(3.94)  
JPAN  
145 g (0.32 lb), with DIN rail mounting adapter  
MADEIN  
M•STER  
MODEL  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
Line to line: ±1.2 V  
80 (3.15)  
mm (inch)  
Line to earth: ±140 V  
Voltage protection level (Up):  
• @ 1 kV (100 A)  
MODEL: MDP–FT[1]  
Line to line: ±15 V  
Line to earth: ±650 V  
• @ 2 kV (1 kA)  
ORDERING INFORMATION  
• Code number: MDP-FT[1]  
Specify a code from below for [1].  
(e.g. MDP-FT/A33/Q)  
Line to line: ±45 V  
Line to earth: ±800 V  
Response time:  
• Specify the specification for option code /Q  
(e.g. /C01)  
Line to line: ≤ 4 nsec.  
Line to earth: ≤ 20 nsec.  
Leakage current @Uc:  
Line to line: ≤ 20 μA  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Line to earth: ≤ 10 μA  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
/A33: With adapter (model A-33)  
Other Options  
Nominal current (I ): 100 mA  
N
Internal series resistance: ≤ 8 Ω ±20 % (including return)  
Capacitance @ 1 MHz:  
blank: none  
/Q: Option other than the above (specify the specification)  
Line to line: ≤ 500 pF  
Line to earth: ≤ 100 pF  
Surge protection: IEC 61643-21 Categories C1, C2, D1  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
MDP-FT SPECIFICATIONS  
ES-8118 Rev.18 Page 1/4  
http://www.m-system.co.jp/  
MODEL: MDP-FT  
CONNECTION EXAMPLES  
4-WIRE CONNECTION  
MODEM A  
MODEM B  
MDP-FT  
MDP-FT  
P1  
S1  
S2  
S1  
P1  
P2  
S
R
P2  
S2  
G
G
G
G
DTE  
FG  
R
FG  
DTE  
P1  
P2  
S1  
S2  
S1  
S2  
P1  
P2  
S
(PROTECTED EQUIPMENT)  
(PROTECTED EQUIPMENT)  
MDP-FT  
MDP-FT  
2-WIRE CONNECTION  
MODEM A  
MODEM B  
MDP-FT  
MDP-FT  
P1  
P2  
S1  
S2  
S1  
S2  
P1  
P2  
S
R
G
G
DTE  
DTE  
FG  
FG  
(PROTECTED EQUIPMENT)  
(PROTECTED EQUIPMENT)  
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
MDP-FT SPECIFICATIONS  
ES-8118 Rev.18 Page 2/4  
http://www.m-system.co.jp/  
MODEL: MDP-FT  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
STANDARD  
80 (3.15)  
53 (2.09)  
2–5 (.20) dia.  
MTG HOLE  
23.5 (.93)  
27 (1.06)  
HEAD ELEMENT  
P1  
P2  
BASE  
4–M4 TERMINAL SCREW  
S1  
S2  
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
(.33)  
[3.3 (.13)]  
80 (3.15)  
53 (2.09)  
27 (1.06)  
23.5 (.93)  
DIN RAIL  
35mm wide  
P1 P2  
4–M4 TERMINAL SCREW  
S1 S2  
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MOUNTING REQUIREMENTS unit: mm (inch)  
2–M4 SCREW  
25 (.97) min.  
MDP-FT SPECIFICATIONS  
ES-8118 Rev.18 Page 3/4  
http://www.m-system.co.jp/  
MODEL: MDP-FT  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
4Ω  
S1  
P1  
ELEMENT  
ZD  
Discharge  
Elements  
TO CABLE  
TO EQUIPMENT  
ZD  
S2  
P2  
4Ω  
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
Specifications are subject to change without notice.  
MDP-FT SPECIFICATIONS  
ES-8118 Rev.18 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

MDP-FT/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-FT/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LC

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LC/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LC/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LWA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LWA/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LWA/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-MFA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM