MDP-LWA/Q [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDP-LWA/Q |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总4页 (文件大小:124K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDP-LWA
Screw terminal: Nickel-plated steel
Lightning Surge Protectors for
Electronics Equipment M-RESTER
Housing material: Flame-resistant resin (black)
INSTALLATION
LIGHTNING SURGE PROTECTOR FOR
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
LonWorks
(FTT-10A)
Functions & Features
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN
rail mounting adapter
• Designed specifically for the network
• No interruption of transmission signal by unplugging the
head element module
PERFORMANCE
Max. continuous operating voltage (Uc):
Line to line: ±1.5 V
Line to earth: ±100 V
Lot.NO
SHLD to earth: ±160 V
MDEIJPAN1430B
Voltage protection level (Up):
• @ 2 kV (1 kA)
M•STER
MODEL
Line to line: ±40 V
Line to earth: ±350 V
SHLD to earth: ±650 V
MODEL: MDP–LWA[1]
Response time:
Line to line: ≤ 4 nsec.
ORDERING INFORMATION
• Code number: MDP-LWA[1]
Specify a code from below for [1].
(e.g. MDP-LWA/A33/Q)
Line or SHLD to earth: ≤ 20 nsec.
Leakage current:
Line to line: ≤ 0.15 mA @ ±1.5 V
Line to earth: ≤ 20 μA @ ±100 V
SHLD to earth: ≤ ±20 μA @ ±160 V
Max. discharge current (Imax): 5000 A (8 / 20 μs)
• Specify the specification for option code /Q
(e.g. /C01)
Nominal current (I ): 100 mA
N
Internal series resistance: ≤ 3.3 Ω including return
Capacitance @ 1 MHz:
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
Line to line: ≤ 200 pF
Line to earth: ≤ 200 pF
/A33: With adapter (model A-33)
Other Options
SHLD to earth: ≤ 30 pF
Input attenuation: -1 dB or less @ DC to 100 kHz, Z
0
= 50 Ω
blank: none
Surge protection: IEC 61643-21 Categories C1, C2
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
APPLICABLE NETWORK
LonWorks FTT-10A network
This unit is not applicable to LonWorks Link Power network.
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
MDP-LWA SPECIFICATIONS
ES-8234 Rev.6 Page 1/4
http://www.m-system.co.jp/
MODEL: MDP-LWA
CONNECTION EXAMPLES
CONNECTION DIAGRAM
M-RESTER
Protected Device
*1
A
C
B
1
3
2
NET
A, B
*2
*3
SHLD
G
G
Cross wiring
Grounding
*1. Be sure to use twisted-pair cables.
*2. No polarity.
*3. With shielded twisted-pair cables, connect the shield to the surge protector’s 'B' terminal.
Follow instructions provided with the protected device whether '2' terminal should be
connected or not. However, if the shield terminal of the protected device is not isolated
from NET A / B, DO NOT connect '2' terminal to the protected device.
NETWORK CONFIGURATION
Panel / Cabinet
M-RESTER
Surge Side
Protected Side
Networꢀ Cable
Networꢀ Cable
Crossover Wire
G
G
G
Protected
Devices
(Nodes)
Grounding
Panel / Cabinet
M-RESTER
Surge Side
Protected Side
Networꢀ Cable
Crossover Wire
G
G
G
Protected
Devices
(Nodes)
•The M-RESTER is applicable to networꢀs which consist only of FTT-1ꢁA.
Not applicable to the ones connected to Linꢀ Power networꢀ.
• The maximum number of nodes connectable to the networꢀ segment is reduced by one
when one unit of M-RESTER is added.
• When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),
install the M-RESTER by each group of devices. Insert the M-RESTER at the surge side of the networꢀ.
• For detailed information on the networꢀ, refer to LONWORKS FTT-1ꢁA Free Topology Transceiver
User’s Guide provided by Echelon.
MDP-LWA SPECIFICATIONS
ES-8234 Rev.6 Page 2/4
http://www.m-system.co.jp/
MODEL: MDP-LWA
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ STANDARD
80 (3.15)
2–5 (.20) dia.
31.5 (1.24)
MTG HOLE
53 (2.09)
27 (1.06)
HEAD ELEMENT
3
2
1
BASE
6–M4 TERMINAL SCREW
C
B
A
GROUND TERMINAL (G)
(used as mounting bracket)
■ WITH DIN RAIL MOUNTING ADAPTER
8.5
(.33)
[3.3 (.13)]
80 (3.15)
53 (2.09)
27 (1.06)
31.5 (1.24)
DIN RAIL
35mm wide
3
2
1
6–M4 TERMINAL SCREW
C
B
A
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MDP-LWA SPECIFICATIONS
ES-8234 Rev.6 Page 3/4
http://www.m-system.co.jp/
MODEL: MDP-LWA
MOUNTING REQUIREMENTS unit: mm (inch)
2–M4 SCREW
33 (1.30) min.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
1.5W
A
C
1
3
NET A, B
(line)
NET A, B
1.5W
HEAD
ELEMENT
Surge
Side
Protected
Device Side
Discharge
Element
Voltage
Limiter
SHIELD
B
2
SHIELD
BASE
G
GROUND TERMINAL
(used as mounting attachment)
Specifications are subject to change without notice.
MDP-LWA SPECIFICATIONS
ES-8234 Rev.6 Page 4/4
http://www.m-system.co.jp/