MDP-LWA/Q [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MDP-LWA/Q
型号: MDP-LWA/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总4页 (文件大小:124K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MDP-LWA  
Screw terminal: Nickel-plated steel  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
Housing material: Flame-resistant resin (black)  
INSTALLATION  
LIGHTNING SURGE PROTECTOR FOR  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
LonWorks  
(FTT-10A)  
Functions & Features  
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN  
rail mounting adapter  
• Designed specifically for the network  
• No interruption of transmission signal by unplugging the  
head element module  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
Line to line: ±1.5 V  
Line to earth: ±100 V  
Lot.NO  
SHLD to earth: ±160 V  
MDEIJPAN1430B  
Voltage protection level (Up):  
• @ 2 kV (1 kA)  
M•STER  
MODEL  
Line to line: ±40 V  
Line to earth: ±350 V  
SHLD to earth: ±650 V  
MODEL: MDP–LWA[1]  
Response time:  
Line to line: ≤ 4 nsec.  
ORDERING INFORMATION  
• Code number: MDP-LWA[1]  
Specify a code from below for [1].  
(e.g. MDP-LWA/A33/Q)  
Line or SHLD to earth: ≤ 20 nsec.  
Leakage current:  
Line to line: ≤ 0.15 mA @ ±1.5 V  
Line to earth: ≤ 20 μA @ ±100 V  
SHLD to earth: ≤ ±20 μA @ ±160 V  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Nominal current (I ): 100 mA  
N
Internal series resistance: ≤ 3.3 Ω including return  
Capacitance @ 1 MHz:  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Line to line: ≤ 200 pF  
Line to earth: ≤ 200 pF  
/A33: With adapter (model A-33)  
Other Options  
SHLD to earth: ≤ 30 pF  
Input attenuation: -1 dB or less @ DC to 100 kHz, Z  
0
= 50 Ω  
blank: none  
Surge protection: IEC 61643-21 Categories C1, C2  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
APPLICABLE NETWORK  
LonWorks FTT-10A network  
This unit is not applicable to LonWorks Link Power network.  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
MDP-LWA SPECIFICATIONS  
ES-8234 Rev.6 Page 1/4  
http://www.m-system.co.jp/  
MODEL: MDP-LWA  
CONNECTION EXAMPLES  
CONNECTION DIAGRAM  
M-RESTER  
Protected Device  
*1  
A
C
B
1
3
2
NET  
A, B  
*2  
*3  
SHLD  
G
G
Cross wiring  
Grounding  
*1. Be sure to use twisted-pair cables.  
*2. No polarity.  
*3. With shielded twisted-pair cables, connect the shield to the surge protector’s 'B' terminal.  
Follow instructions provided with the protected device whether '2' terminal should be  
connected or not. However, if the shield terminal of the protected device is not isolated  
from NET A / B, DO NOT connect '2' terminal to the protected device.  
NETWORK CONFIGURATION  
Panel / Cabinet  
M-RESTER  
Surge Side  
Protected Side  
Networꢀ Cable  
Networꢀ Cable  
Crossover Wire  
G
G
G
Protected  
Devices  
(Nodes)  
Grounding  
Panel / Cabinet  
M-RESTER  
Surge Side  
Protected Side  
Networꢀ Cable  
Crossover Wire  
G
G
G
Protected  
Devices  
(Nodes)  
•The M-RESTER is applicable to networꢀs which consist only of FTT-1ꢁA.  
Not applicable to the ones connected to Linꢀ Power networꢀ.  
• The maximum number of nodes connectable to the networꢀ segment is reduced by one  
when one unit of M-RESTER is added.  
• When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),  
install the M-RESTER by each group of devices. Insert the M-RESTER at the surge side of the networꢀ.  
• For detailed information on the networꢀ, refer to LONWORKS FTT-1ꢁA Free Topology Transceiver  
User’s Guide provided by Echelon.  
MDP-LWA SPECIFICATIONS  
ES-8234 Rev.6 Page 2/4  
http://www.m-system.co.jp/  
MODEL: MDP-LWA  
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
STANDARD  
80 (3.15)  
2–5 (.20) dia.  
31.5 (1.24)  
MTG HOLE  
53 (2.09)  
27 (1.06)  
HEAD ELEMENT  
3
2
1
BASE  
6–M4 TERMINAL SCREW  
C
B
A
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
(.33)  
[3.3 (.13)]  
80 (3.15)  
53 (2.09)  
27 (1.06)  
31.5 (1.24)  
DIN RAIL  
35mm wide  
3
2
1
6–M4 TERMINAL SCREW  
C
B
A
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MDP-LWA SPECIFICATIONS  
ES-8234 Rev.6 Page 3/4  
http://www.m-system.co.jp/  
MODEL: MDP-LWA  
MOUNTING REQUIREMENTS unit: mm (inch)  
2–M4 SCREW  
33 (1.30) min.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
1.5W  
A
C
1
3
NET A, B  
(line)  
NET A, B  
1.5W  
HEAD  
ELEMENT  
Surge  
Side  
Protected  
Device Side  
Discharge  
Element  
Voltage  
Limiter  
SHIELD  
B
2
SHIELD  
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
Specifications are subject to change without notice.  
MDP-LWA SPECIFICATIONS  
ES-8234 Rev.6 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

MDP-MFA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-MFA/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-MFA/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PA/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PA/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM