MODEL: R3-AV4  
Remote I/O R3 Series  
CAUTION  
UNUSED INPUT CHANNELS  
Set the unused channels to the ranges other than 1 - 5 V.  
Otherwise, set them as "Unused" with PC Configurator  
software: R3CON. Unused channels left open with 1 – 5 V  
setting are equal to the input lower than -15 %, which sets a  
data abnormality at the PLC or the host device.  
Open circuit with the input range set to ±10 V means 50 %  
of the full-scale. An alarm setpoint must be set to a value  
that does not trip an unwanted alarm.  
DC VOLTAGE INPUT ALARM MODULE  
(4 points, isolated)  
27.5 [1.08]  
130  
[5.12]  
GENERAL SPECIFICATIONS  
Connection  
109  
[4.29]  
mm [inch]  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
MODEL: R3–AV4[1][2]  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
ORDERING INFORMATION  
• Code number: R3-AV4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-AV4W/CE/Q)  
Input range: Selectable with the side DIP SW  
Conversion rate: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with input circuit abnormality (AD converter response  
failure);  
• Specify the specification for option code /Q  
(e.g. /C01)  
NO. OF CHANNELS  
4: 4  
Green in normal operating conditions.  
[1] COMMUNICATION MODE  
S: Single  
INPUT SPECIFICATIONS  
Narrow Span: -1 – +1 V, 0 – 1 V DC  
Input resistance: 100 kΩ min.  
Wide Span: -10 – +10 V, -5 – +5 V,  
0 – 10 V, 0 – 5 V, 1 – 5 V DC  
W: Dual  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Input resistance: 1 MΩ min.  
/CE: CE marking  
Other Options  
INSTALLATION  
blank: none  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
R3-AV4 SPECIFICATIONS  
ES-8435 Rev.7 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3-AV4  
ALARM ON DELAY TIME  
PERFORMANCE  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is set when the preset time elapses after  
the input has entered in the alarm range.  
This setting is common to all four points.  
POWER ON DELAY TIME  
Conversion accuracy: Refer to the table at the end of this  
section.  
Conversion rate: 80 / 40 / 20 / 10 msec. selectable  
Data allocation: 1  
Current consumption: 60 mA  
(0.0 to 99.0 sec.; factory set to 5.0)  
Temp. coefficient: ±0.015 % /°C (±0.008 %/°F)  
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to input 3 to input 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
The alarm output start functioning in the preset time after  
the power has been turned on.  
This setting is common to all four points.  
ALARM HOLD TIME  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is held for the preset time even if it is  
reset in shorter time.  
Conversion accuracy  
This setting is common to all four points.  
RATE  
80 msec. 40 msec. 20 msec. 10 msec.  
RANGE  
0ꢀ05ꢁ  
0ꢀ05ꢁ  
0ꢀ05ꢁ  
0ꢀ05ꢁ  
0ꢀ1ꢁ  
0ꢀ1ꢁ  
0ꢀ1ꢁ  
0ꢀ1ꢁ  
0ꢀ1ꢁ  
0ꢀ.ꢁ  
0ꢀ.ꢁ  
0ꢀ1ꢁ  
0ꢀ.ꢁ  
0ꢀꢂꢁ  
-10 – +10 V  
-5 – +5 V  
0ꢀꢂꢁ  
0ꢀꢂꢁ  
0ꢀꢂꢁ  
0ꢀ.ꢁ  
0ꢀ.ꢁ  
0ꢀ.ꢁ  
-1 – +1 V  
0 – 10 V  
0 – 5 V  
1 – 5 V  
0 – 1 V  
0ꢀꢂꢁ  
0ꢀꢂꢁ  
0ꢀ.ꢁ  
0ꢀꢃꢁ  
0ꢀꢃꢁ  
0ꢀꢂꢁ  
0ꢀ1ꢁ  
0ꢀ05ꢁ  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
ALARM SETTING  
The following parameters are programmable using the PC  
Configurator Software (model: R3CON).  
ALARM TRIP POINT (-15.00 to +115.00 %;  
factory set to A1: 80.00, A2: 60.00, A3: 40.00, A4: 20.00)  
Four alarm setpoints are selectable per each input.  
ALARM TYPE  
(High or Low; factory set to A1: High, A2: High, A3: Low,  
A4: Low)  
High or Low alarm is selectable for each alarm trip point.  
High alarm: An alarm is set when the input signal goes  
above the setpoint.  
Low alarm: An alarm is set when the input signal goes below  
the setpoint.  
DEADBAND (HYSTERESIS)  
(0.00 to 100.00 %; factory set to 5.00)  
Deadband (deviation between the points where the alarm is  
set and reset) is selectable for each alarm trip point.  
R3-AV4 SPECIFICATIONS  
ES-8435 Rev.7 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3-AV4  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
Functions  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SW3  
ON  
SW2  
SW1  
Range  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)  
or  
Input 4 (SW2)  
Conv.  
Rate  
Input 1 (SW1)  
or  
Input 3 (SW2)  
ON  
ON  
OUTPUT DATA DESCRIPTIONS  
Four alarm setpoints are selectable per each input. One (1) word (16 bit) data is transmitterd to the PLC or the host device via  
the R3 network module.  
15  
0
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Input 1  
Input 2  
Input 3  
Input 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
R3-AV4 SPECIFICATIONS  
ES-8435 Rev.7 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3-AV4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
INTERNAL BUS A  
Communication  
Circuit  
+
+
+
+
+
+
+
+
1
2
INTERNAL BUS B*  
WIDE SPAN  
NARROW SPAN  
WIDE SPAN  
INPUT 1  
INPUT 2  
INPUT 3  
INPUT 4  
Control  
Circuit  
11  
12  
3
INTERNAL POWER  
Input Circuit  
Input Circuit  
Input Circuit  
5
4
10  
15  
20  
13  
14  
6
NARROW SPAN  
WIDE SPAN  
7
16  
17  
8
NARROW SPAN  
WIDE SPAN  
9
18  
19  
NARROW SPAN  
* For dual redundant communication.  
Note: Connect either wide or narrow span terminals for each channel.  
Specifications are subject to change without notice.  
R3-AV4 SPECIFICATIONS  
ES-8435 Rev.7 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3-AV4S/CE

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV4S/Q

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV4W

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV4W/CE

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV4W/Q

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8S

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8S/CE

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8S/Q

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8W

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8W/CE

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM

R3-AV8W/Q

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM