MODEL: R3-NF1
Remote I/O R3 Series
GENERAL SPECIFICATIONS
Connection
T-Link: Euro type connector terminal (applicable wire size:
T-Link INTERFACE MODULE
(Fuji Electric T-Link use)
0.2 to 2.5 mm , stripped length 7 mm)
2
Internal bus: Via the Installation Base
27.5 (1.08)
(model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
130
(5.12)
Screw terminal: Nickel-plated steel
Isolation: T-Link to internal bus or internal power to power
input to RUN contact output to FG
119
(4.69)
mm (inch)
Input error data setting: Input value setting at input module
error with side DIP SW
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
Status data setting: WITHOUT / WITH (side DIP SW)
(Not available with firmware version earlier than 1.02)
I/O points setting: 4, 8, 16, 64 (front DIP SW)
I/O type setting: Input only, output only, input/output mixed
(front DIP SW)
MODEL: R3–NF1–[1][2]
ORDERING INFORMATION
• Code number: R3-NF1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NF1-R/Q)
RUN indicator: Bi-color (green/red) LED; Green ON in normal
communication; Red ON when receiving data (Function
selected with DIP SW)
• Specify the specification for option code /Q
(e.g. /C01/SET)
ERR indicator: Bi-color (green/red) LED;
Green ON or blinking at communication error (Blinking with
setting errors); Red ON at transmitting data (Function
selected with DIP SW)
[1] POWER INPUT
N: No power supply
■ RUN CONTACT OUTPUT
AC Power
RUN contact: Turns ON while the green RUN LED is ON (T-
Link in normal communication).
K3: 100 – 120 V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
L3: 200 – 240 V AC
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
DC Power
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When
7
driving an inductive load, external contact protection and
noise quenching recommended.
[2] OPTIONS
blank: none
T-Link SPECIFICATIONS
Node address: Rotary switch; 00 – 99
Configuration: Multi-drop
/Q: With options (specify the specification)
Communication: Half-duplex
Baud rate: 500 kbps
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Transmission media/distance:
KPEV-SB, 0.75 mm
2
× 1 pair, 700 m
× 1 pair, 1000 m
/C02: Polyurethane coating
T-KPEV-SB, 1.25 mm
2
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8429)
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 1/7
http://www.m-system.co.jp/
MODEL: R3-NF1
INSTALLATION
Power consumption
•AC: Approx. 25 VA
•DC: Approx. 14 W
Current consumption (no power supply): 130 mA
Output current (power supply): 250 mA continuous at 20 V
DC; 400 mA for 10 minutes
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (T-Link to
internal bus or internal power to power input to RUN contact
output to FG)
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Node Address Setting
Rotary SW (MSB)
SA1
SA2
RUN LED
ERR LED
Node Address Setting
Rotary SW (LSB)
DIP SW
SW3
ON
SW2
SW1
RT+
RT–
SD
T2
Network
SW6
Configuration Jack
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
8:N.U
7:N.U.
6:KS5
5:KS4
4:KS3
3:KS2
2:KS1
1:KS0
T1
Euro Type
Connector Terminal
1
2
3
4
ON
ON
5
6
ON
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 2/7
http://www.m-system.co.jp/
MODEL: R3-NF1
TRANSMISSION DATA DESCRIPTIONS
The DIP switches on the front of the module specify each I/O module’s I/O points and I/O type. The DIP switches on the side of the module specify status data.
The allocation area, which is set in order from the slot No. 1, is assigned to the I/O data. I/O module s data exceeding the configured area is unable.
’
With input status data ON, the last 2 words of the input data area are used as status data. The status data settng is avaliable for firmware version
1.02 or later. For other versions SW3-3 setting is ignored and the device works as if SW3-3 is off. When I/O data and the status area are duplicated,
status data takes priority.
For example, when the total number of I/O points is of 16, the data areas are assigned as shown below:
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
Module 7
4
4
4
1
1
1
1
Then the I/O data are assigned as in the figures below:
■ WITHOUT STATUS DATA (SW3-3: OFF)
• INPUT-ONLY or OUTPUT-ONLY DATA
• I/O MIXED DATA
Half of the words specified with the KS0 through KS3 are as-
signed to the inputs, the other half to the outputs.
Module 1 is always assigned to the input. Insert the input
modules to the slots 1 and 2, and the output modules to the
slots 3 through 7.
Data areas specified with the side DIP switches are assigned
to each module from Module 1 through Module 7 in turn.
If the total number of I/O points is of 4 or 8, non-existing
data are not sent/received.
15
0
15
0
Begin
Begin
Address +0
Address +0
Module 1
Module 2
Module 3
Module 1
Module 2
Module 3
+2
+4
+2
+4
Input
(8 points)
+6
+6
+8
+8
+10
+12
+14
+10
+12
+14
Output
(8 points)
Module 4
Module 5
Module 6
Module 7
Module 4
Module 5
Module 6
Module 7
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 3/7
http://www.m-system.co.jp/
MODEL: R3-NF1
■ WITH STATUS DATA (SW3-3: ON)
• I/O type: Input
Status data is assigned to the last 2 words.
Data of the slots 6 and 7 is unable.
• I/O type: Input/Output Mixed
Status data is assigned to the last 2 words of the input area.
Data on the words 3 and 4 of the slot 2 is unable.
15
0
15
0
Begin
Begin
+0
+2
+0
+2
Address
Address
Slot 1
Slot
Slot
1
2
Input
(8 points)
+4
+4
Slot 2
Module Status
Error Status
+6
+6
+8
+8
Slot
3
Slot 3
+10
+12
+14
+10
+12
+14
Output
(8 points)
Slot
Slot
4
5
Slot
4
5
6
7
Slot
Slot
Slot
Module Status
Error Status
• I/O type: Output
Status data cannot be assigned because there is no input data.
For output only, operate without status area.
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot
turns to “1,” and the unmounted slot to “0.”
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”
R3-TSx, R3-RSx, R3-US4 (T/C, RTD input): Input burnout
R3-DA16A: Power input in error or disconnected
R3-YSx: Output current error (e.g. load unconnected)
R3-PC16A: External power supply in error or disconnected
Every module which input is less than -15% or more than +115%
R3-US4 (voltage input): out of -10% to +110% input.
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 4/7
http://www.m-system.co.jp/
MODEL: R3-NF1
MODULE STATUS, ERROR STATUS
Shows each module's availability and error status.
15
0
Module 1
Module 2
Module 3
:
Module 16
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.
15
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.
For example, 135.4°F is converted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.
15
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.
15
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
0
0
+0
+1
Lower 16 bits
Higher 16 bits
15
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 5/7
http://www.m-system.co.jp/
MODEL: R3-NF1
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
15
0
+0
+1
Lower 16 bits
Higher 16 bits
0
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
15
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
0 : OFF
1 : ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
10 (.39)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
6–M3
SCREW
1
4
2
5
3
TERMINAL
COVER
6
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 6/7
http://www.m-system.co.jp/
MODEL: R3-NF1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
LED Rotary SW
Isolation
RT+
RT–
SD
T2
Control
Circuit
Communication
Circuit
Close to terminate.*
INTERNAL BUS
Shielded Twisted-pair
Cable
To Other
T-Link
Devices
Term. Resist.
DIP SW
–
+
T1
INTERNAL POWER
RUN +
RUN –
U (+)
1
4
2
3
6
RUN CONTACT OUTPUT
5
**
**
POWER INPUT
V (–)
**
FG
JACK
CONFIGURATION JACK
* When the module is at an end of the transmission line via twisted-pair calbe
(= when there is no cross wiring), close across the RT+ and RT– terminals with the
jumper included in the product package. Remove the jumper for all other locations.
**Not provided with ‘No Power Supply’ type module.
Caution: FG terminal is NOT a protective conductor terminal.
Specifications are subject to change without notice.
R3-NF1 SPECIFICATIONS
ES-8429 Rev.10 Page 7/7
http://www.m-system.co.jp/