R3-NF1-N [MSYSTEM]

Remote I/O R3 Series T-Link INTERFACE MODULE;
R3-NF1-N
型号: R3-NF1-N
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series T-Link INTERFACE MODULE

文件: 总7页 (文件大小:183K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NF1  
Remote I/O R3 Series  
GENERAL SPECIFICATIONS  
Connection  
T-Link: Euro type connector terminal (applicable wire size:  
T-Link INTERFACE MODULE  
(Fuji Electric T-Link use)  
0.2 to 2.5 mm , stripped length 7 mm)  
2
Internal bus: Via the Installation Base  
27.5 (1.08)  
(model: R3-BSx)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
130  
(5.12)  
Screw terminal: Nickel-plated steel  
Isolation: T-Link to internal bus or internal power to power  
input to RUN contact output to FG  
119  
(4.69)  
mm (inch)  
Input error data setting: Input value setting at input module  
error with side DIP SW  
Dual communication setting: Set with the side DIP switch  
Data allocation setting: Set with the side DIP switch  
Status data setting: WITHOUT / WITH (side DIP SW)  
(Not available with firmware version earlier than 1.02)  
I/O points setting: 4, 8, 16, 64 (front DIP SW)  
I/O type setting: Input only, output only, input/output mixed  
(front DIP SW)  
MODEL: R3–NF1–[1][2]  
ORDERING INFORMATION  
• Code number: R3-NF1-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NF1-R/Q)  
RUN indicator: Bi-color (green/red) LED; Green ON in normal  
communication; Red ON when receiving data (Function  
selected with DIP SW)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
ERR indicator: Bi-color (green/red) LED;  
Green ON or blinking at communication error (Blinking with  
setting errors); Red ON at transmitting data (Function  
selected with DIP SW)  
[1] POWER INPUT  
N: No power supply  
RUN CONTACT OUTPUT  
AC Power  
RUN contact: Turns ON while the green RUN LED is ON (T-  
Link in normal communication).  
K3: 100 – 120 V AC  
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *  
L3: 200 – 240 V AC  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *  
DC Power  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules or  
network modules with the internal power input options.  
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When  
7
driving an inductive load, external contact protection and  
noise quenching recommended.  
[2] OPTIONS  
blank: none  
T-Link SPECIFICATIONS  
Node address: Rotary switch; 00 – 99  
Configuration: Multi-drop  
/Q: With options (specify the specification)  
Communication: Half-duplex  
Baud rate: 500 kbps  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Transmission media/distance:  
KPEV-SB, 0.75 mm  
2
× 1 pair, 700 m  
× 1 pair, 1000 m  
/C02: Polyurethane coating  
T-KPEV-SB, 1.25 mm  
2
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8429)  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 1/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
INSTALLATION  
Power consumption  
AC: Approx. 25 VA  
DC: Approx. 14 W  
Current consumption (no power supply): 130 mA  
Output current (power supply): 250 mA continuous at 20 V  
DC; 400 mA for 10 minutes  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (T-Link to  
internal bus or internal power to power input to RUN contact  
output to FG)  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
Node Address Setting  
Rotary SW (MSB)  
SA1  
SA2  
RUN LED  
ERR LED  
Node Address Setting  
Rotary SW (LSB)  
DIP SW  
SW3  
ON  
SW2  
SW1  
RT+  
RT–  
SD  
T2  
Network  
SW6  
Configuration Jack  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
8:N.U  
7:N.U.  
6:KS5  
5:KS4  
4:KS3  
3:KS2  
2:KS1  
1:KS0  
T1  
Euro Type  
Connector Terminal  
1
2
3
4
ON  
ON  
5
6
ON  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 2/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
TRANSMISSION DATA DESCRIPTIONS  
The DIP switches on the front of the module specify each I/O module’s I/O points and I/O type. The DIP switches on the side of the module specify status data.  
The allocation area, which is set in order from the slot No. 1, is assigned to the I/O data. I/O module s data exceeding the configured area is unable.  
With input status data ON, the last 2 words of the input data area are used as status data. The status data settng is avaliable for firmware version  
1.02 or later. For other versions SW3-3 setting is ignored and the device works as if SW3-3 is off. When I/O data and the status area are duplicated,  
status data takes priority.  
For example, when the total number of I/O points is of 16, the data areas are assigned as shown below:  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
4
4
4
1
1
1
1
Then the I/O data are assigned as in the figures below:  
WITHOUT STATUS DATA (SW3-3: OFF)  
INPUT-ONLY or OUTPUT-ONLY DATA  
I/O MIXED DATA  
Half of the words specified with the KS0 through KS3 are as-  
signed to the inputs, the other half to the outputs.  
Module 1 is always assigned to the input. Insert the input  
modules to the slots 1 and 2, and the output modules to the  
slots 3 through 7.  
Data areas specified with the side DIP switches are assigned  
to each module from Module 1 through Module 7 in turn.  
If the total number of I/O points is of 4 or 8, non-existing  
data are not sent/received.  
15  
0
15  
0
Begin  
Begin  
Address +0  
Address +0  
Module 1  
Module 2  
Module 3  
Module 1  
Module 2  
Module 3  
+2  
+4  
+2  
+4  
Input  
(8 points)  
+6  
+6  
+8  
+8  
+10  
+12  
+14  
+10  
+12  
+14  
Output  
(8 points)  
Module 4  
Module 5  
Module 6  
Module 7  
Module 4  
Module 5  
Module 6  
Module 7  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 3/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
WITH STATUS DATA (SW3-3: ON)  
• I/O type: Input  
Status data is assigned to the last 2 words.  
Data of the slots 6 and 7 is unable.  
• I/O type: Input/Output Mixed  
Status data is assigned to the last 2 words of the input area.  
Data on the words 3 and 4 of the slot 2 is unable.  
15  
0
15  
0
Begin  
Begin  
+0  
+2  
+0  
+2  
Address  
Address  
Slot 1  
Slot  
Slot  
1
2
Input  
(8 points)  
+4  
+4  
Slot 2  
Module Status  
Error Status  
+6  
+6  
+8  
+8  
Slot  
3
Slot 3  
+10  
+12  
+14  
+10  
+12  
+14  
Output  
(8 points)  
Slot  
Slot  
4
5
Slot  
4
5
6
7
Slot  
Slot  
Slot  
Module Status  
Error Status  
• I/O type: Output  
Status data cannot be assigned because there is no input data.  
For output only, operate without status area.  
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot  
turns to “1,” and the unmounted slot to “0.”  
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”  
R3-TSx, R3-RSx, R3-US4 (T/C, RTD input): Input burnout  
R3-DA16A: Power input in error or disconnected  
R3-YSx: Output current error (e.g. load unconnected)  
R3-PC16A: External power supply in error or disconnected  
Every module which input is less than -15% or more than +115%  
R3-US4 (voltage input): out of -10% to +110% input.  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 4/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
MODULE STATUS, ERROR STATUS  
Shows each module's availability and error status.  
15  
0
Module 1  
Module 2  
Module 3  
:
Module 16  
I/O DATA DESCRIPTIONS  
The data allocations for typical I/O modules are shown below.  
Refer to the manual for each module for detailed data allocations.  
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)  
16-bit binary data.  
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  
-15 to 0 % is a negative range represented in 2’s complement.  
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.  
15  
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)  
16-bit binary data.  
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.  
With °F temperature unit, the integer section of raw data is directly converted into the data.  
For example, 135.4°F is converted into 135.  
Minus temperature is converted into negative values, represented in 2’s complements.  
15  
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)  
16-bit binary data.  
Integer obtained by multiplying unit value (A) by 100.  
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.  
15  
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)  
32-bit binary data is used for accumulated counts and encoder positions.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
0
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
15  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 5/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)  
32-bit binary data is used for BCD.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
15  
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
0
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)  
15  
0
Input 1 (Output 1)  
Input 2 (Output 2)  
Input 3 (Output 3)  
:
:
Input 16 (Output 16)  
0 : OFF  
1 : ON  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 (.39)  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
6–M3  
SCREW  
1
4
2
5
3
TERMINAL  
COVER  
6
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 6/7  
http://www.m-system.co.jp/  
MODEL: R3-NF1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
LED Rotary SW  
Isolation  
RT+  
RT–  
SD  
T2  
Control  
Circuit  
Communication  
Circuit  
Close to terminate.*  
INTERNAL BUS  
Shielded Twisted-pair  
Cable  
To Other  
T-Link  
Devices  
Term. Resist.  
DIP SW  
+
T1  
INTERNAL POWER  
RUN +  
RUN –  
U (+)  
1
4
2
3
6
RUN CONTACT OUTPUT  
5
**  
**  
POWER INPUT  
V (–)  
**  
FG  
JACK  
CONFIGURATION JACK  
* When the module is at an end of the transmission line via twisted-pair calbe  
(= when there is no cross wiring), close across the RT+ and RT– terminals with the  
jumper included in the product package. Remove the jumper for all other locations.  
**Not provided with ‘No Power Supply’ type module.  
Caution: FG terminal is NOT a protective conductor terminal.  
Specifications are subject to change without notice.  
R3-NF1 SPECIFICATIONS  
ES-8429 Rev.10 Page 7/7  
http://www.m-system.co.jp/  

相关型号:

R3-NF1-N/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF1-R

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF1-R/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-K3

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-K3/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-L3

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-L3/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-R

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF2-R/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF3

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF3-M2

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM