R3-NF3-M2 [MSYSTEM]

Remote I/O R3 Series T-Link INTERFACE MODULE;
R3-NF3-M2
型号: R3-NF3-M2
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series T-Link INTERFACE MODULE

文件: 总7页 (文件大小:193K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NF3  
0.2 to 2.5 mm , stripped length 7 mm)  
2
Remote I/O R3 Series  
Internal bus: Via the Installation Base  
(model: R3-BSx)  
T-Link INTERFACE MODULE  
(Fuji Electric T-Link capsule equivalent)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
27.5  
(1.08)  
Screw terminal: Nickel-plated steel  
Isolation: T-Link to internal bus or internal power to power  
input to RUN contact output to FG  
Input error data setting: Input value setting at input module  
error with side DIP SW  
130  
(5.12)  
Dual communication setting: Set with the side DIP switch  
Data allocation setting: Set with the side DIP switch  
I/O Points setting: Set with the front DIP switch  
Data setting: Set with the front DIP switch  
I/O Module Status setting: Set with the front DIP switch  
I/O Type setting: Set with the front DIP switch  
Analog Data Type setting: Set with the front DIP switch  
RUN indicator: Bi-color (green/red) LED; Green ON in normal  
communication; Red blinks when receiving data (Function  
selected with DIP SW)  
109  
(4.29)  
mm (inch)  
MODEL: R3–NF3–[1][2]  
ORDERING INFORMATION  
• Code number: R3-NF3-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NF3-M2/Q)  
ERR indicator: Bi-color (green/red) LED; Green ON in  
communication errors or minor failure, blinks at errors in the  
internal circuits; Red blinks when transmitting data  
(Function selected with DIP SW)  
• Specify the specification for option code /Q  
(e.g. /C01)  
RUN CONTACT OUTPUT  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
[1] POWER INPUT  
N: No power supply  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
AC Power  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)*  
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When  
7
DC Power  
driving an inductive load, external contact protection and  
noise quenching recommended.  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules or  
network modules with the internal power input options.  
T-Link SPECIFICATIONS  
Node address: Rotary switch; 00 – 99  
Configuration: Multi-drop  
[2] OPTIONS  
blank: none  
Communication: Half-duplex  
Baud rate: 500 kbps  
/Q: With options (specify the specification)  
Transmission media/distance:  
KPEV-SB, 0.75 mm  
2
× 1 pair, 700 m  
× 1 pair, 1000 m  
T-KPEV-SB, 1.25 mm  
2
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
INSTALLATION  
Power consumption  
AC: ≤ 22 VA  
/C02: Polyurethane coating  
/C03: Rubber coating  
DC: ≤ 9 W  
Current consumption (no power supply): 120 mA  
Output current (power supply): 230 mA continuous at 20 V  
DC; 380 mA for 10 minutes  
GENERAL SPECIFICATIONS  
Connection  
T-Link: Euro type connector terminal (applicable wire size:  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 1/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (T-Link to  
internal bus or internal power to power input to RUN contact  
output to FG)  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
Node Address Setting  
Rotary SW (MSB)  
SA1  
SA2  
RUN LED  
ERR LED  
Node Address Setting  
Rotary SW (LSB)  
DIP SW  
SW3  
ON  
SW2  
SW1  
RT+  
RT–  
SD  
T2  
Network  
SW6  
Configuration Jack  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
8:KS7  
7:KS6  
6:KS5  
5:KS4  
4:KS3  
3:KS2  
2:KS1  
1:KS0  
T1  
Euro Type  
Connector Terminal  
1
2
3
4
ON  
ON  
5
6
ON  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 2/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
TRANSMISSION DATA DESCRIPTIONS  
The DIP SW in the front of the module species I/O points, I/O type and with or without of I/O module status data setting.  
I/O DATA is assigned data allocation setting from module 1 orderly.  
The data of I/O module out of the setting area is invalid.  
When there is I/O module status data, use the data area of the last 2 words of the input data area as the status data. When the  
status data and I/O data overlap, the status data takes precedence.  
For example, when the number of I/O points is “16” and SW1 and SW2 are set as shown below.  
Slot 1  
Slot 2  
Slot 3  
Slot 4  
Slot 5  
Slot 6  
Slot 7  
4
4
4
1
1
1
1
Then the I/O data are assigned as in the gures below:  
IN THE CASE OF NO I/O MODULE STATUS (KS3: OFF)  
• I/O TYPE: INPUT ONLY or OUTPUT ONLY  
• I/O TYPE: INPUT / OUTPUT MIXED  
The side DIP SW (SW1, 2) determine data allocation of mod-  
ule (number of data) per module.  
The number of input points and the number of output points  
are assigned half numbers of KS0 to 1 respectively.  
The rst half of the data area is the input area and the second  
half is the output area.  
The number of data set by SW1 and SW2 is assigned to trans-  
mission data in order from slot 1.  
Please set the input module in slot 1 and 2, and output mod-  
ule after slot 3.  
15  
0
Begin  
Address +0  
15  
0
Begin  
Slot 1  
Slot 2  
Slot 3  
Address +0  
+2  
+4  
Slot 1  
Slot 2  
Slot 3  
+2  
+4  
Input  
(8 points)  
+6  
+6  
+8  
+8  
+10  
+12  
+14  
+10  
+12  
+14  
Slot 4  
Slot 5  
Slot 6  
Slot 7  
Output  
(8 points)  
Slot 4  
Slot 5  
Slot 6  
Slot 7  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 3/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
WITH INPUT / OUTPUT MODULE STATUS (KS3: ON)  
• I/O TYPE: INPUT ONLY  
• I/O TYPE: INPUT / OUTPUT MIXED  
Status data is assigned to the last 2 words of the area.  
Slot 6 and 7 are invalid.  
Status data is assigned to the last 2 words of the area.  
Data in the 3rd and 4th words of slot 2 are invalid.  
15  
0
15  
0
Begin  
Begin  
+0  
+2  
+0  
+2  
Address  
Address  
Slot 1  
Slot  
Slot  
1
2
Input  
(8 points  
+4  
+4  
Slot 2  
Module  
Status  
Error  
+6  
+6  
Status  
+8  
+8  
Slot  
3
Slot 3  
+10  
+12  
+14  
+10  
+12  
+14  
Output  
(8 points  
Slot  
Slot  
4
5
Slot  
4
5
6
7
Slot  
Slot  
Slot  
Module Status  
Error Status  
• I/O TYPE: OUTPUT  
Status data cannot be assigned because there is no input data.  
For output only, operate without status area.  
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot turns to  
“1,and the unmounted slot to “0.”  
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”  
R3-TSx, R3-RSx, R3-US4 (T/C, RTD input): Input burnout  
R3-DA16A: Power input in error or disconnected  
R3-YSx: Output current error (e.g. load unconnected)  
R3-PC16A: External power supply in error or disconnected  
Every module which input is less than -15% or more than +115%  
R3-US4 (voltage input): out of -10 to +110% input.  
MODULE STATUS, ERROR STATUS  
Shows each module's availability and error status.  
15  
0
Module 1  
Module 2  
Module 3  
:
Module 16  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 4/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
I/O DATA DESCRIPTIONS  
The data allocations for typical I/O modules are shown below.  
Refer to the manual for each module for detailed data allocations.  
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)  
16-bit binary data.  
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  
-15 to 0 % is a negative range represented in 2’s complement.  
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.  
15  
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)  
16-bit binary data.  
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.  
With °F temperature unit, the integer section of raw data is directly converted into the data.  
For example, 135.4°F is converted into 135.  
Minus temperature is converted into negative values, represented in 2’s complements.  
15  
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)  
16-bit binary data.  
Integer obtained by multiplying unit value (A) by 100.  
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.  
15  
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)  
32-bit binary data is used for accumulated counts and encoder positions.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
0
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
15  
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 5/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
32-bit binary data is used for BCD.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
15  
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
0
■ ANALOG 16 BITS BCD DATA  
The display range is -7999 to +7999. Change data within display range with configurator software (model: R3CON).  
■ ANALOG 32 BITS BCD DATA  
The display range is -1500 to +11500. Data allocation of module is doubled as usual. Pay attention I/O type.  
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)  
15  
0
Input 1 (Output 1)  
Input 2 (Output 2)  
Input 3 (Output 3)  
:
:
Input 16 (Output 16)  
0 : OFF  
1 : ON  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 (.39)  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
6–M3  
SCREW  
1
4
2
5
3
TERMINAL  
COVER  
6
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 6/7  
http://www.m-system.co.jp/  
MODEL: R3-NF3  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
LED Rotary SW  
Isolation  
RT+  
RT–  
SD  
T2  
Control  
Circuit  
Communication  
Circuit  
Close to terminate.*  
INTERNAL BUS  
Shielded Twisted-pair  
Cable  
To Other  
T-Link  
Devices  
Term. Resist.  
DIP SW  
+
T1  
INTERNAL POWER  
RUN +  
RUN –  
U (+)  
1
4
2
3
6
RUN CONTACT OUTPUT  
5
**  
**  
POWER INPUT  
V (–)  
**  
FG  
JACK  
CONFIGURATION JACK  
* When the module is at an end of the transmission line via twisted-pair calbe  
(= when there is no cross wiring), close across the RT+ and RT– terminals with the  
jumper included in the product package. Remove the jumper for all other locations.  
**Not provided with ‘No Power Supply’ type module.  
Caution: FG terminal is NOT a protective conductor terminal.  
Specifications are subject to change without notice.  
R3-NF3 SPECIFICATIONS  
ES-8288 Rev.2 Page 7/7  
http://www.m-system.co.jp/  

相关型号:

R3-NF3-M2/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF3-R

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NF3-R/Q

Remote I/O R3 Series T-Link INTERFACE MODULE
MSYSTEM

R3-NFL1

Remote I/O R3 Series FL-net INTERFACE MODULE
MSYSTEM

R3-NFL1/CE

Remote I/O R3 Series FL-net INTERFACE MODULE
MSYSTEM

R3-NFL1/Q

Remote I/O R3 Series FL-net INTERFACE MODULE
MSYSTEM

R3-NL1

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-K3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-K3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-L3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-L3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-R

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM