MODEL: R3-PA8
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
TOTALIZED PULSE INPUT MODULE
(Pi 8 points, 32 Bits)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
27.5 [1.08]
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8457)
130
[5.12]
RELATED PRODUCTS
• Interface module (model: R3-NC1, R3-NC3, R3-NE1,
R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NFx, R3-NML3.
R3-NF2: Firmware version V0.05 or later)
109
[4.29]
Note:
mm [inch]
• Count reset by host PC/PLC:
Available with this unit and the above mentioned interface
modules of firmware version V2.00 or later, except R3-NFx
(R3-NM3: Firmware version V1.00 or later). Notice that
Count reset by host PC/PLC via R3-NFx or interface module
of previous versions of firmware is unable.
MODEL: R3-PA8[1][2]
ORDERING INFORMATION
• Code number: R3-PA8[1][2]
• Count preset by host PC/PLC:
It is only available in combination with this unit displayed
'SW3-4 RESET/PRESET' on the right side panel and the
interface module R3-NMx or R3-NE1 of firmware version
V2.00 or later. Count preset is not available for other
combination (R3-NM3: Firmware version V1.00 or later).
Notice that this function is not available in the same time as
count preset by host PC/PLC.
Specify a code from below for each of [1] and [2].
(e.g. R3-PA8W/A/CE/PRS/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
8: 8
• In the FL-net Configuration Builder software (model: R3-
NFLBLD), the number of channel for this module is
displayed as 16 because data has 8 channels x 2 words.
[1] COMMUNICATION MODE
S: Single
W: Dual
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base
(model: R3-BSx)
[2] OPTIONS (multiple selections)
Excitation
Blank: Internal (negative common)
/A: External (24 V DC, negative common)
Standards & Approvals
Screw terminal: Nickel-plated steel
Isolation: Input to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with excitation abnormality;
blank: Without CE
/CE: CE marking
EX-FACTORY SETTING
blank: Enable count reset by host PC/PLC
/PRS: Enable count preset by host PC/PLC
Other Options
blank: none
Green in normal operating conditions.
Input status indicator: Red LED;
/Q: Option other than the above (specify the specification)
1 to 8: Turns on with the input ON.
9 to 15: Unused
16: Turns on with the reset input ON.
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 1/5
https://www.m-system.co.jp/
MODEL: R3-PA8
Count reset: Via DIP switch on the side or one pulse to reset
input
EMS EN 61000-6-2
RoHS Directive
Count setting from host PC/PLC: Count reset/count preset is
changeable via DIP switch on the side.
COUNT RESET
There are three different ways to reset count value.
INPUT SPECIFICATIONS
■ COUNT RESET WITH DIP SW
Number of input: 9 (8 points + Count reset)
1) Remove Network Module or its cables and interrupt
communication with other devices.
Input resistance: 6 kΩ
Common: Negative commons, all points; 2 terminals
Maximum frequency: 100 Hz
2) Turn ON the Count Reset SW (DIP SW3-1) on R3-PA8
module.
(ON/OFF time ≥ 5 msec.)
3) Return the module to the base and turn the power supply
on.
This unit is designed to be able to accept a frequency up to
100 Hz, however,‘chattering’ contact must be avoided for
accurate measuring of such high frequency. Use mercury
relays or similar ones that do not cause any chattering.
Totalized pulse range: 0 - 9999999
4) ERR LED turns on and the module starts resetting its
counter. When the resetting is complete, the LED turns to
green. DO NOT remove the power while the red LED is on.
5) After confirming that ERR LED is green, turn the power
supply off.
Count at overflow: Reset and restart at ‘0.’
Max. pulse range selectable from 10000 to 2147483647
using the R3CON PC Configurator Software. ‘0’ or ‘1’ from
which restart counting at overflow is pre-settable. Refer to
the R3CON Users Manual for detailed information.
■ R3-PA8x (internal excitation)
6) Turn OFF the Count Reset SW (DIP SW3-1).
7) Return the Network module onto the base and turn the
power supply on.
Note: Count Reset SW must be turned OFF after this
procedure because the module does not start counting with
ON state. Even when the count overflow set value is 1, the
counter is reset to 0.
Sensing voltage: 13 V DC (max. 24 V with no load)
ON voltage: ≥ 9 V (≤ 1.5 kΩ)
OFF voltage: ≤ 4.5 V (≥ 18 kΩ)
■ COUNT RESET WITH RESET SIGNAL
■ R3-PA8x/A (external excitation)
With the Count Reset Input SW (DIP SW3-3) turned ON, the
count reset signal value becomes effective.
SW3-3 = OFF: invalid
Sensing voltage: 24 V DC
ON voltage: ≥ 9 V (≤ 12 kΩ)
OFF voltage: ≤ 4.5 V (≥ 36 kΩ)
SW3-3 = ON: valid
One pulse supplied at the Count reset input terminal will be
recognized as a reset signal.
INSTALLATION
1) ERR LED turns on (red color) when the reset signal is
received.
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
2) In 1 second, the module starts resetting its counter.
When the resetting is complete, the LED turns to green.
3) After 1 second, ERR LED turns back to the state before
the reset signal has been received.
Note: Reset signals received while the module is processing
(1) through (3) are ignored. Even when the count overflow
set value is 1, the counter is reset to 0.
■ COUNT RESET FROM HOST PC/PLC
PERFORMANCE
Data allocation: 16
Current consumption: 70 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Refer to “COUNTER SETTING FROM HOST PC/PLC” section
hereafter.
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 2/5
https://www.m-system.co.jp/
MODEL: R3-PA8
EXTERNAL VIEW
■ FRONT VIEW
RUN LED
■ SIDE VIEW
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Status Indicator LED
ERR LED
1
2
3
4
5
6
7
8
9
10
Functions
11
12
13
14
15
16
17
18
19
20
SW3
Count Setting
from Host PC/PLC
4
Count Reset Input
3
2
1
Count Reset
ON
Set the Count Reset SW to OFF to start counting.
COUNTER SETTING FROM HOST PC/PLC
■ COUNTER RESET
(Available for R3-NC1, R3-NC3, R3-NE1, R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NML3 (Firmware version 2.00 or later,
R3-NM3: Firmware version V1.00 or later))
Setting SW3-4 OFF and turning power on enable the function.
The bits indicating the channels to reset counter are allocated in the !rst word from host PC/PLC.
When these bits are changed from 0 to 1, the counter is reset. When it is con!rmed that the counter is reset, return to 0.
Notice that if the bit remains at 1, the next reset will not work.
15
0
Count reset CH.1
Count reset CH.2
Count reset CH.3
Count reset CH.4
Count reset CH.8
Unused
Unused
■ COUNTER PRESET
(Available in combination with R3-NE1, R3-NMx (Firmware version 2.00 or later, R3-NM3: Firmware version V1.00 or later), and
R3-PA8 displayed ‘SW3-4 RESET/PRESET’ on the right side)
Setting SW3-4 ON and turning power on enable the function.
Write the preset value to the Holding Resisters, which has same address as the Input Resisters.
• Input Resisters
• Holding Resisters
Address
n+0
Address
n+0
Preset value of Input 1
Preset value of Input 2
Input 1
Input 2
n+1
n+1
n+2
n+2
n+3
n+3
n+14
n+15
n+14
n+15
Preset value of Input 8
Input 8
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 3/5
https://www.m-system.co.jp/
MODEL: R3-PA8
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■R3-PA8x
■R3-PA8x/A
STATUS
RUN LED ERR LED INDICATOR LED
Input Circuit
Input Circuit
INTERNAL BUS A
1
2
1
2
Communication
Circuit
1
2
1
2
Pi 1
Pi 1
Pi 2
Pi 3
Pi 4
Pi 5
Pi 6
Pi 7
Pi 8
INTERNAL BUS B*
Pi 2
Pi 3
Pi 4
Pi 5
Pi 6
Pi 7
Pi 8
Control
Circuit
3
3
3
3
4
4
INTERNAL POWER
4
4
5
5
5
5
DIP SW
6
6
6
6
7
7
7
7
8
8
8
8
9
9
11
12
13
14
15
16
17
18
9
11
12
13
14
15
16
17
18
9
10
11
12
13
14
15
16
10
11
12
13
14
15
16
**
**
Count
Reset
Count
Reset
COM (+)
+24V
**
19
10
20
19
10
20
0V
0V
Numbers in italic indicate LED No.s assigned to the front panel LEDs.
*For dual redundant communication.
**DO NOT use the terminals No. 9, 11 through 17 and 19.
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 4/5
https://www.m-system.co.jp/
MODEL: R3-PA8
Specifications are subject to change without notice.
R3-PA8 SPECIFICATIONS
ES-8457 Rev.10 Page 5/5
https://www.m-system.co.jp/