R30MS4 [MSYSTEM]
Remote I/O R30 Series POTENTIOMETER INPUT MODULE;型号: | R30MS4 |
厂家: | M-SYSTEM |
描述: | Remote I/O R30 Series POTENTIOMETER INPUT MODULE 输入元件 |
文件: | 总5页 (文件大小:183K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R30MS4
Remote I/O R30 Series
CAUTION
■ UNUSED INPUT CHANNELS
Set unused channels to "CH disabled" with PC Configurator
software (model: R30CFG). Otherwise, unused channels left
open are unstable.
POTENTIOMETER INPUT MODULE
(4 points, isolated)
Functions & Features
• 4 channels for potentiometer input remote I/O module
• Isolation between input channels
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B
type USB cable. (provided by user)
25 [.98]
110
[4.33]
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R30BS)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the
section.
98
[3.86]
mm [inch]
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
MODEL: R30MS4S[1]
(Solderless terminals with insulation sleeve do not fit.)
Applicable wire size: 0.25 to 0.75 mm
2
ORDERING INFORMATION
• Code number: R30MS4S[1]
Specify a code from below for [1].
(e.g. R30MS4S/Q)
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to internal
bus or internal power
Input range: Selectable with PC configuration software
(model: R30CFG)
• Specify the specification for option code /Q
(e.g. /C01/SET)
Conversion rate: Selectable with PC configuration software
(model: R30CFG)
Status indicator LED: RUN, ERR
NO. OF CHANNELS
(refer to the instruction manual)
4: 4
■Recommended solderless terminal size - M3 (unit: mm)
3 max.
COMMUNICATION MODE
3.2 dia.
S: Single
[1] OPTIONS
blank: none
12 max.
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9004)
R30MS4 SPECIFICATIONS
ES-9004 Rev.3 Page 1/5
https://www.m-system.co.jp/
MODEL: R30MS4
INPUT SPECIFICATIONS
Module type: Analog input, 4 points
Potentiometer: 100 Ω – 20 kΩ
Minimum span: 50 % of total resistance
Excitation: 0.1 V DC
INSTALLATION
Current consumption: 60 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 160 g (0.35 lb)
PERFORMANCE
Conversion rate / conversion accuracy:
10 ms / ±0.8%, 20 ms / ±0.4%, 40 ms / ±0.2%, 80 ms /
±0.2% (*)
(*) Factory setting
Response time: Conversion rate x 2 + 50 msec. (0 - 90 %)
Data range: 0 – 10000 of the input range
Data allocation: 4
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Input delay time: 50 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the
power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
R30MS4 SPECIFICATIONS
ES-9004 Rev.3 Page 2/5
https://www.m-system.co.jp/
MODEL: R30MS4
CONFIGURATOR SOFTWARE SETTING
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
Unused setting
SETTING RANGE
CH enabled
DEFAULT SETTING
CH enabled
CH disabled
-320.00 – +320.00 (%) 0.00 (%)
Zero base
Full base
-320.00 – +320.00 (%) 0.00 (%)
Scaled range Zero
Scaled range Span
-32 000 – +32 000
-32 000 – +32 000
0
10 000
■ CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
DEFAULT SETTING
80 ms
Conversion rate
80 ms
40 ms
20 ms
10 ms
Normal input
Simulated data
Simulate input
Normal input
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Positioning Guide
Specifications
RUN LED
ERR LED
RUN
ERR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Input Terminal Block
Terminal Fixing Screw
Terminal Cover
■ BOTTOM VIEW
Base Fixing Screw
Lock Tab
R30MS4 SPECIFICATIONS
ES-9004 Rev.3 Page 3/5
https://www.m-system.co.jp/
MODEL: R30MS4
TERMINAL ASSIGNMENTS
1
NO.
1
ID
H1
S1
H2
S2
NC
H3
S3
H4
S4
NC
FUNCTION
Pot 1-H
NO.
11
ID
NC
L1
FUNCTION
No connection
Pot 1-L
H1
S1
H2
S2
11
NC
12
L1
13
NC
14
L2
15
NC
16
NC
17
L3
18
NC
19
L4
20
NC
2
3
4
5
2
Pot 1-S
12
13
14
15
16
17
18
19
20
3
Pot 2-H
NC
L2
No connection
Pot 2-L
4
Pot 2-S
5
No connection
Pot 3-H
NC
NC
L3
No connection
No connection
Pot 3-L
6
NC
7
Pot 3-S
6
8
Pot 4-H
NC
L4
No connection
Pot 4-L
H3
S3
H4
S4
9
Pot 4-S
7
8
9
10
No connection
NC
No connection
10
NC
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
25 [.98]
98 [3.86]
20–M3
SCREW
①
⑪
⑫
⑬
⑭
⑮
⑯
⑰
⑱
⑲
⑳
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
R30MS4 SPECIFICATIONS
ES-9004 Rev.3 Page 4/5
https://www.m-system.co.jp/
MODEL: R30MS4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN ERR
indicator indicator
Input Circuit
Input Circuit
Input Circuit
Input Circuit
H1
S1
L1
1
2
Comm.
Circuit
INTERNAL BUS
Input 1
Input 2
Input 3
Input 4
12
INTERNAL POWER
H2
S2
L2
3
4
5
14
10
11
13
15
16
18
20
Control
Circuit
H3
S3
L3
6
7
17
H4
S4
L4
8
9
19
■ Input Connection Examples
POTENTIOMETER
max.
+
3
2
1
Hn
Sn
Ln
–
min.
Specifications are subject to change without notice.
R30MS4 SPECIFICATIONS
ES-9004 Rev.3 Page 5/5
https://www.m-system.co.jp/
相关型号: