MODEL: R3S-PA8  
Remote I/O R3 Series  
RELATED PRODUCTS  
• Interface module (model: R3-NC1, R3-NC3, R3-NE1,  
R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NFx, R3-NML3.  
R3-NF2: Firmware version V0.05 or later)  
TOTALIZED PULSE INPUT MODULE  
(Pi 8 points, 32 Bits, Tension clamp terminal block)  
Note:  
27.5 (1.08)  
• Count reset by host PC/PLC:  
Available with this unit and the above mentioned interface  
modules of firmware version V2.00 or later, except R3-NFx  
(R3-NM3: Firmware version V1.00 or later). Notice that  
Count reset by host PC/PLC via R3-NFx or interface module  
of previous versions of firmware is unable.  
130 (5.12)  
• Count preset by host PC/PLC:  
It is only available in combination with this unit displayed  
'SW3-4 RESET/PRESET' on the right side panel and the  
interface module R3-NMx or R3-NE1 of firmware version  
V2.00 or later. Count preset is not available for other  
combination (R3-NM3: Firmware version V1.00 or later).  
Notice that this function is not available in the same time as  
count preset by host PC/PLC.  
120 (4.72)  
mm (inch)  
MODEL: R3S-PA8[1][2]  
ORDERING INFORMATION  
• Code number: R3S-PA8[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3S-PA8W/PRS/Q)  
• In the FL-net Configuration Builder software (model: R3-  
NFLBLD), the number of channel for this module is  
displayed as 16 because data has 8 channels x 2 words.  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: Separable tension clamp terminal (applicable wire  
NO. OF CHANNELS  
8: 8  
size: 0.2 to 1.5 mm , stripped length 10 mm)  
2
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Input to internal bus or internal power  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with excitation abnormality;  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
[2] OPTIONS (multiple selections)  
EX-FACTORY SETTING  
blank: Enable count reset by host PC/PLC  
/PRS: Enable count preset by host PC/PLC  
Other Options  
Green in normal operating conditions.  
Input status indicator: Red LED;  
1 to 8: Turns on with the input ON.  
blank: none  
9 to 15: Unused  
/Q: Option other than the above (specify the specification)  
16: Turns on with the reset input ON.  
Count reset: Via DIP switch on the side or one pulse to reset  
input  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Count setting from host PC/PLC: Count reset/count preset is  
changeable via DIP switch on the side.  
/C02: Polyurethane coating  
/C03: Rubber coating  
INPUT SPECIFICATIONS  
Number of input: 9 (8 points + Count reset)  
Input resistance: 6 kΩ  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8457)  
Common: Negative commons, all points; 11 terminals  
Maximum frequency: 100 Hz  
R3S-PA8 SPECIFICATIONS  
ES-8935 Rev.6 Page 1/5  
http://www.m-system.co.jp/  
MODEL: R3S-PA8  
(ON/OFF time ≥ 5 msec.)  
ON state. Even when the count overflow set value is 1, the  
counter is reset to 0.  
This unit is designed to be able to accept a frequency up to  
100 Hz, however,‘chattering’ contact must be avoided for  
accurate measuring of such high frequency. Use mercury  
relays or similar ones that do not cause any chattering.  
Totalized pulse range: 0 - 9999999  
■ COUNT RESET WITH RESET SIGNAL  
With the Count Reset Input SW (DIP SW3-3) turned ON, the  
count reset signal value becomes effective.  
SW3-3 = OFF: invalid  
Count at overflow: Reset and restart at ‘0.’(Max. pulse  
range selectable from 10000 to 2147483647 using the  
R3CON PC Configurator Software. ‘0’ or ‘1’ from which  
restart counting at overflow is pre-settable. Refer to the  
R3CON Users Manual for detailed information.)  
INTERNAL EXCITATION  
SW3-3 = ON: valid  
One pulse supplied at the Count reset input terminal will be  
recognized as a reset signal.  
1) ERR LED turns on (red color) when the reset signal is  
received.  
2) In 1 second, the module starts resetting its counter.  
When the resetting is complete, the LED turns to green.  
3) After 1 second, ERR LED turns back to the state before  
the reset signal has been received.  
Sensing voltage: 13 V DC (max. 24 V with no load)  
ON voltage: ≥ 9 V (≤ 1.5 kΩ)  
OFF voltage: ≤ 4.5 V (≥ 18 kΩ)  
Note: Reset signals received while the module is processing  
(1) through (3) are ignored. Even when the count overflow  
set value is 1, the counter is reset to 0.  
■ COUNT RESET FROM HOST PC/PLC  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
Refer to “COUNTER SETTING FROM HOST PC/PLC” section  
hereafter.  
PERFORMANCE  
Data allocation: 16  
Current consumption: 70 mA  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(input to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
COUNT RESET  
There are three different ways to reset count value.  
■ COUNT RESET WITH DIP SW  
1) Remove Network Module or its cables and interrupt  
communication with other devices.  
2) Turn ON the Count Reset SW (DIP SW3-1) on R3S-PA8  
module.  
3) Return the module to the base and turn the power supply  
on.  
4) ERR LED turns on and the module starts resetting its  
counter. When the resetting is complete, the LED turns to  
green. DO NOT remove the power while the red LED is on.  
5) After confirming that ERR LED is green, turn the power  
supply off.  
6) Turn OFF the Count Reset SW (DIP SW3-1).  
7) Return the Network module onto the base and turn the  
power supply on.  
Note: Count Reset SW must be turned OFF after this  
procedure because the module does not start counting with  
R3S-PA8 SPECIFICATIONS  
ES-8935 Rev.6 Page 2/5  
http://www.m-system.co.jp/  
MODEL: R3S-PA8  
EXTERNAL VIEW  
FRONT VIEW  
RUN LED  
SIDE VIEW  
Status Indicator LED  
ERR LED  
Functions  
1
SW3  
Count Setting  
from Host PC/PLC  
4
Count  
3
Reset Input  
2
1
Count  
Reset  
ON  
20  
Set the Count Reset SW to OFF to start counting.  
COUNTER SETTING FROM HOST PC/PLC  
COUNTER RESET  
(Available for R3-NC1, R3-NC3, R3-NE1, R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NML3 (Firmware version 2.00 or later,  
R3-NM3: Firmware version V1.00 or later))  
Setting SW3-4 OFF and turning power on enable the function.  
The bits indicating the channels to reset counter are allocated in the rst word from host PC/PLC.  
When these bits are changed from 0 to 1, the counter is reset. When it is conrmed that the counter is reset, return to 0.  
Notice that if the bit remains at 1, the next reset will not work.  
15  
0
Count reset CH.1  
Count reset CH.2  
Count reset CH.3  
Count reset CH.4  
Count reset CH.8  
Unused  
Unused  
COUNTER PRESET  
(Available in combination with R3-NE1, R3-NMx (Firmware version 2.00 or later, R3-NM3: Firmware version V1.00 or later),  
and R3S-PA8 displayed ‘SW3-4 RESET/PRESET’ on the right side)  
Setting SW3-4 ON and turning power on enable the function.  
Write the preset value to the Holding Resisters, which has same address as the Input Resisters.  
• Input Resisters  
• Holding Resisters  
Address  
n+0  
Address  
n+0  
Preset value of Input 1  
Preset value of Input 2  
Input 1  
Input 2  
n+1  
n+1  
n+2  
n+2  
n+3  
n+3  
n+14  
n+15  
n+14  
n+15  
Preset value of Input 8  
Input 8  
R3S-PA8 SPECIFICATIONS  
ES-8935 Rev.6 Page 3/5  
http://www.m-system.co.jp/  
MODEL: R3S-PA8  
EXTERNAL DIMENSIONS unit: mm (inch)  
120 (4.72)  
109 (4.29)  
27.5 (1.08)  
POSITIONING  
GUIDE  
1
20  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED STATUS  
INDICATOR LED  
DIP SW  
Input Circuit  
1
2
1
3
Pi 1  
Pi 2  
Pi 3  
Pi 4  
Pi 5  
Pi 6  
Pi 7  
Pi 8  
INTERNAL BUS A  
Comm.  
Circuit  
INTERNAL BUS B*  
3
5
4
7
INTERNAL POWER  
5
Control  
Circuit  
9
6
11  
13  
15  
17  
2
7
8
16  
Count  
Reset  
0V  
4
6
8
10  
12  
14  
16  
18  
19  
20  
Numbers in italic indicate LED No.s assigned to the front panel LEDs.  
*For dual redundant communication.  
R3S-PA8 SPECIFICATIONS  
ES-8935 Rev.6 Page 4/5  
http://www.m-system.co.jp/  
MODEL: R3S-PA8  
INPUT TERMINAL ASSIGNMENT  
PIN No.  
1
FUNCTION  
Pi 1  
2
COM  
Pi 2  
3
4
COM  
Pi 3  
5
6
COM  
Pi 4  
7
8
COM  
Pi 5  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
COM  
Pi 6  
COM  
Pi 7  
COM  
Pi 8  
COM  
RESET  
COM  
COM  
COM  
Specifications are subject to change without notice.  
R3S-PA8 SPECIFICATIONS  
ES-8935 Rev.6 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

R3S-PA8W

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3S-PA8W/Q

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3S-RR8S

Remote I/O R3 Series
MSYSTEM

R3S-RR8S/Q

Remote I/O R3 Series
MSYSTEM

R3S-RR8W

Remote I/O R3 Series
MSYSTEM

R3S-RR8W/Q

Remote I/O R3 Series
MSYSTEM

R3S-RS4AS

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3S-RS4AS/Q

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3S-RS4AW

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3S-RS4AW/Q

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3S-SS8NS

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3S-SS8NS/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM