R3Y-DS4 [MSYSTEM]

Remote I/O R3 Series 4 – 20 mA INPUT MODULE;
R3Y-DS4
型号: R3Y-DS4
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series 4 – 20 mA INPUT MODULE

输入元件
文件: 总4页 (文件大小:125K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3Y-DS4  
Remote I/O R3 Series  
RELATED PRODUCTS  
• Connector terminal block (model: CNT)  
• Special cable with 40-pin connector (model: FCN)  
4 – 20 mA INPUT MODULE  
(2-wire transmitter excitation supply; 4 points, isolated,  
connector type)  
GENERAL SPECIFICATIONS  
Connection  
27.5 (1.08)  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: 40-pin connector (Fujitsu FCN-365P040-AU)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
130  
(5.12)  
Conversion rate: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with input circuit abnormality (AD converter response  
failure);  
110  
(4.33)  
mm (inch)  
MODEL: R3Y–DS4[1][2]  
Green in normal operating conditions.  
ORDERING INFORMATION  
• Code number: R3Y-DS4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3Y-DS4W/Q)  
SUPPLY OUTPUT  
(across the terminals 20A/20B – 18A/18B, 16A/16B –  
14A/14B, 10A/10B – 8A/8B and 6A/6B – 4A/4B)  
Output voltage: 24 – 28 V DC with no load  
16 V DC min. at 22 mA  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Current rating: ≤ 22 mA DC  
NO. OF CHANNELS  
∙Shortcircuit Protection  
4: 4  
Current limited: Approx. 30 mA  
Protected time duration: No limit  
[1] COMMUNICATION MODE  
S: Single  
INPUT SPECIFICATIONS  
DC Current: 4 – 20 mA DC  
W: Dual  
Input resistance: 250 Ω resistor incorporated  
[2] OPTIONS  
blank: none  
INSTALLATION  
/Q: With options (specify the specification)  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 160 g (0.35 lb)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
PERFORMANCE  
Conversion accuracy: Refer to the table at the end of this  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8368)  
section.  
Conversion rate: 80 / 40 / 20 / 10 msec. selectable  
(factory default: 80 msec.)  
Data range: 0 – 10000  
Data allocation: 4  
Current consumption: 210 mA  
R3Y-DS4 SPECIFICATIONS  
ES-8966 Rev.3 Page 1/4  
http://www.m-system.co.jp/  
MODEL: R3Y-DS4  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.2 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 or  
input 2 or input 3 or input 4 to internal bus or internal  
power)  
500 V AC @ 1 minute (input 1 to input 2 to input 3 to  
input 4)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
Conversion accuracy:  
RATE  
80 msec. 40 msec. 20 msec. 10 msec.  
±±0±ꢀ5 ±±0.5 ±±0ꢁ5 ±±0ꢂ5  
Accuracy  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
• Pin Assignment  
B A  
20 20  
Input Connector  
SW3  
4
3
2
1
Conv.  
Rate  
ON  
B
A
1
1
EXTERNAL DIMENSIONS unit: mm (inch)  
27.5 (1.08)  
110 (4.33)  
POSITIONING  
GUIDE  
R3Y-DS4 SPECIFICATIONS  
ES-8966 Rev.3 Page 2/4  
http://www.m-system.co.jp/  
MODEL: R3Y-DS4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Excitation  
Supply  
+
+
+
+
+
+
+
+
20A/20B  
18A/18B  
19A/19B  
17A/17B  
16A/16B  
14A/14B  
15A/15B  
13A/13B  
10A/10B  
8A/8B  
RUN LED ERR LED DIP SW  
2W-XMTR (EXC)  
CURRENT INPUT  
Input Circuit  
INTERNAL BUS A  
INPUT 1  
INPUT 2  
INPUT 3  
INPUT 4  
Communication  
Circuit  
INTERNAL BUS B*  
250  
Control  
Circuit  
Excitation  
Supply  
INTERNAL  
POWER  
2W-XMTR (EXC)  
CURRENT INPUT  
Input Circuit  
1A/1B  
2A/2B  
250Ω  
Excitation  
Supply  
11A/11B  
12A/12B  
2W-XMTR (EXC)  
CURRENT INPUT  
Input Circuit  
9A/9B  
250Ω  
7A/7B  
Excitation  
Supply  
6A/6B  
2W-XMTR (EXC)  
CURRENT INPUT  
4A/4B  
Input Circuit  
5A/5B  
250Ω  
3A/3B  
*For dual redundant communication.  
Caution  
Input value is less than -15% for the open input, then the host PC/PLC recognizes and configures this as error.  
The unused channels can be specified and configured with the PC Configurator Software (model: R3CON).  
INPUT CONNECTOR (40-pin)  
PIN No. ASSIGNMENT  
PIN No. ASSIGNMENT  
1A  
2A  
NC  
1B  
2B  
NC  
NC  
NC  
3A  
– IN4  
3B  
– IN4  
4A  
– 2-WIRE XMTR4  
+ IN4  
4B  
– 2-WIRE XMTR4  
+ IN4  
5A  
5B  
6A  
+ 2-WIRE XMTR4  
– IN3  
6B  
+ 2-WIRE XMTR4  
– IN3  
7A  
7B  
8A  
– 2-WIRE XMTR3  
+ IN3  
8B  
– 2-WIRE XMTR3  
+ IN3  
9A  
9B  
10A  
11A  
12A  
13A  
14A  
15A  
16A  
17A  
18A  
19A  
20A  
+ 2-WIRE XMTR3  
NC  
10B  
11B  
12B  
13B  
14B  
15B  
16B  
17B  
18B  
19B  
20B  
+ 2-WIRE XMTR3  
NC  
NC  
NC  
– IN2  
– IN2  
– 2-WIRE XMTR2  
+ IN2  
– 2-WIRE XMTR2  
+ IN2  
+ 2-WIRE XMTR2  
– IN1  
+ 2-WIRE XMTR2  
– IN1  
– 2-WIRE XMTR1  
+ IN1  
– 2-WIRE XMTR1  
+ IN1  
+ 2-WIRE XMTR1  
+ 2-WIRE XMTR1  
R3Y-DS4 SPECIFICATIONS  
ES-8966 Rev.3 Page 3/4  
http://www.m-system.co.jp/  
MODEL: R3Y-DS4  
Specifications are subject to change without notice.  
R3Y-DS4 SPECIFICATIONS  
ES-8966 Rev.3 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

R3Y-DS8N

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NS

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NS/CE

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NS/Q

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NW

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NW/CE

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-DS8NW/Q

Remote I/O R3 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R3Y-MS8

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3Y-MS8S

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3Y-MS8S/CE

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3Y-MS8S/Q

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R3Y-MS8W

Remote I/O R3 Series POTENTIOMETER INPUT MODULE
MSYSTEM