R3Y-DS8NS/Q [MSYSTEM]
Remote I/O R3 Series 4 â 20 mA INPUT MODULE;型号: | R3Y-DS8NS/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series 4 â 20 mA INPUT MODULE 输入元件 |
文件: | 总4页 (文件大小:126K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3Y-DS8N
/C03: Rubber coating
Remote I/O R3 Series
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8369)
4 – 20 mA INPUT MODULE
(2-wire transmitter excitation supply; 8 points, non-isolated,
connector type)
RELATED PRODUCTS
• Connector terminal block (model: CNT)
27.5 [1.08]
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Connection
130
[5.12]
Internal bus: Via the Installation Base (model: R3-BSx)
Input: 40-pin connector (Fujitsu FCN-365P040-AU)
Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Input to internal bus or internal power
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response
failure);
110
[4.33]
mm [inch]
MODEL: R3Y–DS8N[1][2]
ORDERING INFORMATION
• Code number: R3Y-DS8N[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3Y-DS8NW/CE/Q)
Green in normal operating conditions.
• Specify the specification for option code /Q
(e.g. /C01/SET)
SUPPLY OUTPUT
Sensor excitation: 24 V DC, ≥ 300 mA
NO. OF CHANNELS
8: 8
• Shortcircuit Protection
Current limited: Approx. 30 mA per channel
Protected time duration: No limit
ISOLATION
N: Non-isolated between inputs
INPUT SPECIFICATIONS
■ DC Current: 4 – 20 mA DC
Input resistance: 250 Ω resistor incorporated
[1] COMMUNICATION MODE
S: Single
W: Dual
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 160 g (0.35 lb)
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
PERFORMANCE
Conversion accuracy: Refer to the table at the end of this
/Q: With options (specify the specification)
section.
Conversion rate: 160 / 80 / 40 / 20 msec. selectable
(factory default: 160 msec.)
Data range: 0 – 10000
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Data allocation: 8
/C02: Polyurethane coating
Current consumption: 60 mA
R3Y-DS8N SPECIFICATIONS
ES-8968 Rev.8 Page 1/4
https://www.m-system.co.jp/
MODEL: R3Y-DS8N
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Conversion accuracy
RATE
160 msec. 80 msec.
0.0ꢀ5 0.15
40 msec.
0.25
20 msec.
0.45
ACCURACY
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
ERR LED
• Pin Assignment
B A
20 20
Input Connector
SW3
4
3
2
1
Conv.
Rate
ON
B
A
1
1
EXTERNAL DIMENSIONS unit: mm [inch]
27.5 [1.08]
110 [4.33]
POSITIONING
GUIDE
R3Y-DS8N SPECIFICATIONS
ES-8968 Rev.8 Page 2/4
https://www.m-system.co.jp/
MODEL: R3Y-DS8N
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
24V DC
24V DC
24V DC
24V DC
ERR LED
DIP SW
RUN LED
Input Circuit
Current
Limiter
20A/20B
18A/18B
+
Communication
Circuit
INTERNAL BUS A
INPUT 1 2W-XMTR (EXC)
–
INTERNAL BUS B*
250Ω
INTERNAL POWER
Current
Limiter
16A/16B
14A/14B
+
INPUT 2 2W-XMTR (EXC)
–
250Ω
Current
Limiter
12A/12B
10A/10B
+
INPUT 3 2W-XMTR (EXC)
–
250Ω
Current
Limiter
8A/8B
6A/6B
+
INPUT 4 2W-XMTR (EXC)
–
250Ω
Control
Circuit
24V DC
24V DC
24V DC
Current
Limiter
19A/19B
17A/17B
+
INPUT 5 2W-XMTR (EXC)
–
250Ω
Current
Limiter
15A/15B
13A/13B
+
INPUT 6 2W-XMTR (EXC)
–
250Ω
Current
Limiter
11A/11B
9A/9B
+
INPUT 7 2W-XMTR (EXC)
–
250Ω
24V DC
Current
Limiter
7A/7B
5A/5B
+
INPUT 8 2W-XMTR (EXC)
–
250Ω
24V DC
3A/3B
4A/4B
1A/1B
2A/2B
SENSOR
EXCITATION
24V DC
*For dual redundant communication.
Caution
Input value is less than -15% for the open input terminals, then the host PC/PLC recognizes
and configures this as error. The unused channels can be specified and configured with the
PC Configurator Software (model: R3CON).
R3Y-DS8N SPECIFICATIONS
ES-8968 Rev.8 Page 3/4
https://www.m-system.co.jp/
MODEL: R3Y-DS8N
INPUT CONNECTOR (40-pin)
PIN NO.
1A
ASSIGNMENT
GND
GND
+24V
+24V
-IN8
PIN NO.
1B
ASSIGNMENT
GND
GND
+24V
+24V
-IN8
2A
2B
3A
3B
4A
4B
5A
5B
6A
-IN4
6B
-IN4
7A
+IN8
+IN4
-IN7
7B
+IN8
+IN4
-IN7
8A
8B
9A
9B
10A
11A
12A
13A
14A
15A
16A
17A
18A
19A
20A
-IN3
10B
11B
12B
13B
14B
15B
16B
17B
18B
19B
20B
-IN3
+IN7
+IN3
-IN6
+IN7
+IN3
-IN6
-IN2
-IN2
+IN6
+IN2
-IN5
+IN6
+IN2
-IN5
-IN1
-IN1
+IN5
+IN1
+IN5
+IN1
Specifications are subject to change without notice.
R3Y-DS8N SPECIFICATIONS
ES-8968 Rev.8 Page 4/4
https://www.m-system.co.jp/