R5T-PA22S/Q [MSYSTEM]

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE;
R5T-PA22S/Q
型号: R5T-PA22S/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE

输入元件
文件: 总3页 (文件大小:116K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R5T-PA2  
steel  
Remote I/O R5 Series  
Isolation: Pi 1 to Pi 2 to internal bus or internal power  
RUN indicator: Bi-color (red/green) LED;  
TOTALIZED PULSE INPUT MODULE  
(screw terminal block; Pi 2 points)  
18 (.71)  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
Input status indicator: Red LED; turns on with the input ON.  
Count reset: Via DIP switches on the side  
90  
(3.54)  
INPUT SPECIFICATIONS  
Input: Dry contact, 2 points  
Common: All negatives  
137  
(5.39)  
Contact detecting: Max. 24 V DC  
mm (inch)  
ON voltage, current: ≥ 15 V, ≥ 2.5 mA  
OFF voltage, current: ≤ 6 V, ≤ 1 mA  
Maximum frequency: 100 Hz (duty ratio 30 – 70 %)  
Totalized pulse range: 1 – 10000 (‘0’ at reset)  
Max. pulse range selectable from 100 to 60000 using the  
R5CON PC Configurator Software. Refer to the R5CON Users  
Manual for detailed information.  
MODEL: R5T–PA2[1]{2]  
ORDERING INFORMATION  
• Code number: R5T-PA2[1][2]  
Specify a code from below for each [1] and [2].  
(e.g. R5T-PA2W/Q)  
Count at overflow: Reset and restart at ‘1.’  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 110 g (0.24 lb)  
NO. OF CHANNELS  
2: 2-point inputs  
[1] COMMUNICATION MODE  
S: Single  
PERFORMANCE  
Data allocation: 2  
W: Dual  
Response time: ≤ 0.1 sec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(Pi 1 to Pi 2 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
STANDARDS & APPROVALS  
EU conformity:  
/C02: Polyurethane coating  
EMC Directive  
/C03: Rubber coating  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
EN 50581  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R5-BS)  
Input: M3.5 screw terminal block (torque 0.8 N·m)  
Internal power: Via the base (model: R5-BS)  
Screw terminal: Nickel-plated steel (standard) or stainless  
R5T-PA2 SPECIFICATIONS  
ES-7573 Rev.8 Page 1/3  
http://www.m-system.co.jp/  
MODEL: R5T-PA2  
FUNCTIONS  
Counter Reset  
1) Remove Network Module or its cables and interrupt  
communication with other devices.  
2) Turn ON the Counter Reset SW (SW8) on the module.  
3) Return the module to the base and turn the power supply  
on.  
4) Red RUN LED turns on and the module starts resetting its  
counter. When the resetting is complete, the LED light turns  
to green. DO NOT remove the power while the red light is  
on.  
5) After the green LED is confirmed, turn the power supply  
off.  
6) Turn OFF the Counter Reset SW (SW8).  
7) Return the Network module onto the base and turn the  
power supply on.  
Note: Counter Reset SW must be turned OFF after this  
procedure because the module does not start counting with  
ON state.  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
RUN LED  
RUN  
1
2
3
4
Status Indicator LED  
1 2 3 4 5 6 7 8  
4
5
6
3
Counter  
Reset  
1
2
Counter Reset SW is normally OFF during operation.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
LOCKING CLAMP  
18 (.71)  
38.5 (1.52)  
98.5 (3.88)  
TERMINAL COVER  
8.2 (.32)  
6–M3.5  
TERMINAL  
SCREWS  
4
5
2
6
3
7.2 (.28)  
POSITIONING GUIDE  
1
R5T-PA2 SPECIFICATIONS  
ES-7573 Rev.8 Page 2/3  
http://www.m-system.co.jp/  
MODEL: R5T-PA2  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN INPUT STATUS  
LED INDICATOR LED  
• • • •  
Isolation  
Isolation  
INTERNAL BUS A  
1
3
Communication  
Circuit  
1
3
4
6
2
5
Pi 1  
COM1(–)  
Pi 2  
INTERNAL BUS B*  
Control  
Circuit  
INTERNAL POWER  
COM2(–)  
DIP SW  
*For dual redundant communication.  
Note: Italic typed numbers correspond to the LEDs on the front panel.  
Specifications are subject to change without notice.  
R5T-PA2 SPECIFICATIONS  
ES-7573 Rev.8 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

R5T-PA22W

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PA22W/Q

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PC22S

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22S/Q

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22W

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22W/Q

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PT1S

Remote I/O R5 Series
MSYSTEM

R5T-PT1S/Q

Remote I/O R5 Series
MSYSTEM

R5T-PT1W

Remote I/O R5 Series
MSYSTEM

R5T-PT1W/Q

Remote I/O R5 Series
MSYSTEM

R5T-PT2S

Remote I/O R5 Series
MSYSTEM

R5T-PT2S/Q

Remote I/O R5 Series
MSYSTEM