R7G-SC-SHL1-R/Q [MSYSTEM]
Remote I/O R7 Series GATEWAY MODULE;型号: | R7G-SC-SHL1-R/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R7 Series GATEWAY MODULE |
文件: | 总6页 (文件大小:298K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R7G
Remote I/O R7 Series
GATEWAY MODULE
FUNCTIONS & FEATURES
The Gateway Module for CC-Link and HLS (Hi-speedLink
System) connects discrete I/O between the networks each
other. The module hands over 32 point inputs of CC-Link to
32 point outputs of HLS or 32 point inputs of HLS to 32 point
outputs of CC-Link.
CAUTION
In this module, the transmission between CC-Link and HLS is
not synchronized. Therefore, if one of the networks read
the transmitted data before completion of its update by the
other network, the data may be uncertain as 16-bit data. If
the correct 16-bit data is necessary, arrange the host
application program.
MODEL: R7G-SC-S[1]-R[2]
Refer to the instruction manual.
ORDERING INFORMATION
• Code number: R7G-SC-S[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. R7G-SC-SHL-R/Q)
GENERAL SPECIFICATIONS
Connection
• Specify the specification for option code /Q
(e.g. /C01)
• Power supply, CC-Link: Screwless spring terminal
Applicable wire size: 0.2 - 1.25 mm
2
Stripped length: 10 mm
Module type of network 1
S: Slave
Recommended solderless terminal
AI0,25-10YE 0.25 mm
AI0,34-10TQ 0.34 mm
AI0,5-10WH 0.5 mm
AI0,75-10GY 0.75 mm
A1-10 1.0 mm (Phoenix Contact)
A1,5-10 1.5 mm (Phoenix Contact)
2
(Phoenix Contact)
2
(Phoenix Contact)
Type of network 1
C: CC-Link
2
(Phoenix Contact)
(Phoenix Contact)
2
2
2
Module type of network 2
• HLS: RJ-45 Connectors
S: Slave
Recommended cable connector:
TM21P-88P (Hirose Electric)
[1] Type of network 2
HL: HLS (Hi-speedLink System) Full-duplex
(not included in the package)
Isolation: CC-Link or FG to HLS to power
Station address setting: Rotary switch
(For the detail refer to the instruction manual.)
Transfer rate
HL1: HLS (Hi-speedLink System) Half-duplex
POWER INPUT
DC Power
• CC-Link Rotary switch
R: 24 V DC
• HLS DIP switch
(For the detail refer to the instruction manual.)
Power LED: Green LED turns on when the power is supplied.
Status indicator LED
[2] OPTIONS
blank: none
• CC-Link: Red LEDs indicate communication status.
• HLS: Green LEDs indicate communication status.
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
COMMUNICATION
■ HLS COMMUNICATION
Network: Full-duplex or half-duplex
Transmission distance:
/C02: Polyurethane coating
/C03: Rubber coating
• 12 Mbps: 100 meters (328 ft)
• 6 Mbps: 200 meters (656 ft)
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 1/6
http://www.m-system.co.jp/
MODEL: R7G
Network cable:
• Full-duplex communication: ZHY262PS, ZHT262PS
• Half-duplex communication: ZHY221PS
(Shinko Seisen Industry Co., Ltd.)
Data allocation: 2
Terminating resistor: Built-in (Selected with the DIP SW;
factory setting: disabled)
■ CC-LINK COMMUNICATION
CC-LinkVer.1.10
Network cable: CC-Link cable designated by Mitsubishi
Electric
Station Type: Remote I/O
Data allocation: 2 (1 station x 2)
Terminating resistor: Built-in (Selected with the DIP SW;
factory setting: disabled)
INSTALLATION
Power input
•DC:
Operational voltage range 24 V DC ±10 %;
ripple 10 %p-p max., approx. 1.8 W
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 150 g (0.33 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(CC-Link or FG to HLS to power)
EXTERNAL VIEW
Operating Mode Setting DIP SW (SW1)
CC-Link Station Address Setting Rotary SW
CC-Link Baud Rate Setting Rotary SW
CC-Link Status Indicator LED
HLS Station Address Setting Rotay SW
HLS Status Indicator LED
X10
X1
X10
X1
6M C1 C2
12M H1 H2
H
C
RUN1 ERR1 SD1 RD1
RUN2 ERR2 SD2 RD2
PWR
RUN1 RUN2
STATION ADD.
HLS
STATION ADD.
B.RATE
CC-Link
CC-Link Terminating
Resistor SW
Power Supply
Terminals
HLS Terminating Resistor SW
CC-Link Terminals
HLS RJ-45 Connectors
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 2/6
http://www.m-system.co.jp/
MODEL: R7G
CONNECTION DIAGRAMS
■ POWER SUPPLY AND TRANSMISSION WIRING
• Power supply
• CC-Link
1
2
3
1
2
3
4
5
1. +24V
2. 0V
3. FG
Power Supply (24V DC)
Power Supply (0V)
FG
1. DA
2. DB
3. DG
4. SLD
5. FG
blue
white
yellow
Shield
FG
• HLS
Full-duplex communication
Half-duplex communication
12345678
12345678
1. NC
2. NC
3. TXD+
4. TXD–
No connection
No connection
Network (Slave, transmission +)
Network (Slave, transmission –)
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD1
No connection
No connection
Network (+)
Network (–)
No connection
No connection
No connection
Shield
5. RXD+ Network (Master, transmission+)
6. RXD– Network (Master, transmission–)
7. NC
8. SLD1
No connection
Shield
■ Master Module wirng
• CC-Link
Master Module
Remote Module
Remote Module
Terminating Resistor
DA
Terminating Resistor
blue
DA
DB
DA
DB
white
yellow
DB
DG
SLD
FG
DG
SLD
FG
DG
SLD
FG
• HLS
Full-duplex communication
Master Module
Slave Module
Slave Module
Terminating Resistor
TXD–
Terminating Resistor
RXD–
RXD+
TXD–
TXD+
SLD1
RXD–
RXD+
TXD–
TXD+
SLD1
TXD+
Terminating Resistor
RXD–
Terminating Resistor
RXD+
SLD1
Half-duplex communication
Master Module
Slave Module
Slave Module
Terminating Resistor
Terminating Resistor
TR+
TR+
TR–
SLD1
TR+
TR–
SLD1
TR–
SLD1
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 3/6
http://www.m-system.co.jp/
MODEL: R7G
INDICATOR LED
■ CC-Link STATUS INDICATOR LED
RUNx ERRx SDx*1
RDx
ON
STATUS*2
ON
BL
BL
Communicates normally with occasional CRC errors due to noise interference.
Communicates normally but the Baud Rate and/or Station Address switches failed.
ON
BL
BL
ON
ERRx LED blinks approximately in 0.5 seconds intervals.
ON
ON
BL
BL
BL
OFF
OFF
BL
OFF
ON
----
CRC error found in the received data. Unable to respond.
ON
BL
OFF
ON
----
ON
OFF
OFF
OFF
OFF
BL
Normal communication
ON
BL
OFF
ON
----
ON
OFF
OFF
BL
Unable to receive data addressed to the station.
ON
OFF
ON
----
OFF
OFF
OFF
OFF
OFF
OFF
Performs the interval-timed responses but CRC error found in receiving the refresh data.
BL
BL
OFF
ON
----
BL
OFF
OFF
BL
CRC error found in the data addressed to the station.
----
BL
OFF
ON
OFF
OFF
Link is not started.
BL
OFF
----
No data addressed to the station. Or unable to receive data addressed to the station
due to noise interference. (Missing parts of the data sent from the master)
Unable to receive data due to wire breakdown
Faulty Baud Rate and/or Station Address setting
Power input removed. Or power supply failure.
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF/ON
OFF
OFF
OFF = OFF, ON = ON, BL = Blinking
*1. SDx LEDs may look not blinking but ON with high baud rate and fewer connected modules.
*2. LEDs indicated with “----” in STATUS rarely occurs in normal operation. (LED failure or the like as possible cause).
DATA ALLOCATION
CC-Link
HLS
Interval-timed Response(X)
Do
F E D C B A 9 8 7 6 5 4 3 2 1 0
F E D C B A 9 8 7 6 5 4 3 2 1 0
RX(n+0)
RX(n+1)
RX(n+2)
RX(n+3)
CH1
CH2
CH1
CH2
{(80+2m) +1}H
{(80+2m) +3}H
{(80+2m) +0}H
{(80+2m) +2}H
Unused
Unused
Refresh Data(Y)
F E D C B A 9 8 7 6 5 4 3 2 1 0
Di
F E D C B A 9 8 7 6 5 4 3 2 1 0
RY(n+0)
RY(n+1)
RY(n+2)
RY(n+3)
Unused
CH1
CH2
CH1
CH2
{(100+2m) +1}H
{(100+2m) +3}H
{(100+2m) +0}H
{(100+2m) +2}H
Unused
n: CC-Link station address selected with rotary SW.
m: HLS module address selected with rotary SW.
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 4/6
http://www.m-system.co.jp/
MODEL: R7G
I/O DATA DESCRIPTIONS
15
0
Input 0 (Output 0)
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 7 (Output 7)
Input 8 (Output 8)
Input 15 (Output 15)
0: OFF
1: ON
DIMENSIONS unit: mm (inch)
18 (0.71)
53 (2.09)
115 (4.53)
DIN RAIL
35mm wide
30 (1.18)
[5 (.20)]
R7G SPECIFICATIONS
ES-7817 Rev.3 Page 5/6
http://www.m-system.co.jp/
MODEL: R7G
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Isolation
DA
DB
1
2
3
4
5
1
2
3
4
5
6
7
8
NC
NC
CC-Link
comm.
circuit
Control
circuit
HLS
comm.
circuit
CC-Link
comm.(IN)
DG
SLD
FG
TXD+(TR+)
TXD–(TR–)
RXD+
HLS
comm.
(IN)
RXD–
DA
DB
1
2
3
4
5
NC
SLD1
CC-Link
comm.(OUT)
DG
SLD
FG
1
2
3
4
5
6
7
8
NC
NC
TXD+(TR+)
TXD–(TR–)
RXD+
RXD–
NC
HLS
comm.
(OUT)
24V DC
0V
1
2
3
POWER (IN)
FG
24V DC
0V
1
2
3
SLD1
POWER (OUT)
FG
SYSTEM CONFIGURATION EXAMPLES
HLS
Master
CC-Link
Master
HLS
CC-Link
...
...
Gateway module
Model: R7G
HLS I/O module
Model: R7HL
CC-Link I/O module
Model:R7C
Specifications are subject to change without notice.