MODEL: WL40MW1VN
Wireless I/O WL40VN Series
FUNCTIONS & FEATURES
This unit
• Incorporates 920MHz band wireless module.
• Works as a gateway between wireless and RS-485 using
Modbus-RTU protocol.
WIRELESS GATEWAY
(Modbus-RTU Transparent 920MHz Band Wireless Device
(child device) for Vietnam)
For use in Vietnam only.
RELATED PRODUCTS
60 (2.36)
For related products of wireless device, refer to M-System's
web site.
[260
(10.24)]
• PC configurator software (model: W920FCFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the unit to the PC.
Please refer to the internet software download site or the
users manual for the PC configurator software for applicable
cable types.
155 (6.10)
mm (inch)
Maintenance software
Maintenance console: MH920 Console International (model:
MH920CI) (OKI)
MODEL: WL40MW1VN-[1][2]
(Maintenance software is downloadable at M-System’s web
site.)
Coaxial cable
ORDERING INFORMATION
• Code number: WL40MW1VN-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. WL40MW1VN-R/E/Q)
• 7.5 m extension cable for rooftop antenna (model: CX-
SAC0SAD0Q0750) (OKI)
Using 7.5 m coaxial cable for extension decreases
transmission distance.
• Specify the specification for option code /Q
(e.g. /C01)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.25 W)
[1] POWER INPUT
DC Power
S: 12 V DC
GENERAL SPECIFICATIONS
Connection
(Operational voltage range 12 V ±10 %, ripple 10 %p-p max.)
R: 24 V DC
Wireless network: SMA coaxial connector
RS-485: Tension clamp (Front Twinconnection)
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Applicable wire size: 0.2 - 1.5 mm
Power supply: Tension clamp (Front Twinconnection)
Applicable wire size: 0.2 - 2.5 mm , stripped length 10 mm
2
, stripped length 10 mm
[2] OPTIONS (multiple selections)
Antenna
2
Maintenance: Mini USB type B female connector
Isolation: Power input to Modbus to FE1 to antenna
connector
/S: Sleeve antenna
/E: Rooftop antenna
Other Options
Indicator LED: Power
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 1/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
Weight
MODBUS COMMUNICATION
Protocol: Modbus-RTU
Unit: Approx. 260 g (0.57 lb)
Sleeve antenna (standard): 27 g (0.95 oz)
Rooftop antenna: 52 g (1.83 oz)
Configuration: Bus type multi-drop
Standard: Conforms to TIA/EIA-485-A
Communication: Half-duplex, asynchronous, no procedure
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(power input to Modbus to FE1 to antenna connector)
Status indicator LED: ERR, RD, SD
Max. no. of connections at once: 31
Transmission setting: PC configurator software
Data: RTU (Binary)
STANDARDS & APPROVALS
QCVN 47: 2015 / BTTTT
Baud rate: 4800, 9600, 19.2k, 38.4 k (bps)
Parity: None, even or odd
QCVN 96: 2015 / BTTTT
Stop bit: 1 or 2
WIRELESS SPECIFICATIONS
Communication Standard: IEEE 802.15.4g
Frequency: 920MHz band (918.4 - 922.4 MHz)
Max. Transmission power: 20mW
Bandwidth: 400 kHz
Modulation: GFSK
Baud rate: Max. 100 kbps
Channels: 1 to 7ch
Security: 128bit AES
Indicator LEDs: 920Run, 920Link, 920ERR
Protocol: Modbus-RTU
Communication module: Router module incorporated (Oki
Electric Industry Co., Ltd. )
Radio parameters setting: by PC configurator software
Antenna
•Sleeve antenna (Model: MH920-ANT-F (S))
Indoor use
Non-waterproof
Non-directional
Gain: 3.0dBi max.
•Rooftop antenna (Model: MH920-ANT-F (R))
Outdoor/indoor use
Cable length: 2.5 m
Waterproof performance: IPx6 (except connector)
Non-directional
Gain: 2.0dBi max.
INSTALLATION
Current consumption:
24 V DC: ≤ 70 mA
12 V DC: ≤130 mA
Operating temperature: -20 to +60°C (-4 to +140°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 2/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
CONFIGURATOR SOFTWARE SETTING
With configurator software, settings shown below are available.
Refer to the users manual of W920FCFG for detailed operation.
■ WIRELESS SETTING
ITEM
SETTING RANGE
DEFAULT
0000
Preferred PAN ID (group number)
Radio channel number
Short address
0000 – FFFE (hexadecimal, 4 digits)
1 – 7 (selectable up to 7 channels)
0000 – FFFD (hexadecimal, 4 digits)
None
0000
Network name
English one-byte characters within 16 characters
(one-byte space, “-”, “_”, “.”, “@” are usable.)
Blank
Encryption key
0000...0 – FFFF...F
(hexadecimal, 32 digits)
0000...0
Monitoring unit time of 1% duty (sec.)
Transmitter power output
10 – 3600 (sec.)
0.16mW / 1mW / 20mW
No / Yes
600 (sec.)
20mW
Low-speed moving mode
No
Device type in a network,
Number of devices in a network
Child (xed), 1 to 30 devices /
Child (xed), 31 to 60 devices /
Child (xed), 61 to 100 devices /
Child (xed) + child (moving)
Child (xed), 1 to 30 devices
Set network quality
Standard (recommended) /
Frequency of route switching and delay (higher) /
Frequency of route switching and delay (highest)
Standard (recommended)
Network join mode
Fixed route
V3-compatible mode / Fast join mode
No / Yes
V3-compatible mode
No
Destination short address
Temporary detour
0000 – FFFD (hexadecimal, 4 digits)
No / Yes
0000
Yes
Packet ltering
None / Yes (polling type)
1.0 – 60.0 (sec.)
Yes (polling type)
1.0 (sec.)
3.0 (sec.)
Three times
Filter timeout on polling
920Run timeout
1.0 – 60.0 (sec.)
Retry times before route switching
Once / Twice / Three times
Note: For version con rmation of communication module, refer to the users manual of W920FCFG.
■ MODBUS SETTING
ITEM
SETTING RANGE
38400 / 19200 / 9600 / 4800 bps
Odd / Even / None
1 bit / 2 bits
DEFAULT
38400 bps
Odd
Transfer rate
Parity bit
Stop bit
1 bit
EXTERNAL VIEW
■ FRONT VIEW
Status Indicator LED
Antenna Connector
Power
SD
RD
920Link
920Run
920ERR
ERR
Status Indicator LED
Maintenance Connector
Configuration Jack
CFG2
DA
DB
DG
SLD
CFG1
FE
Connector for
RS-485 Communication
24V
0V
NC
NC
FE1
Connector for Power Input *
* Power input defers depending on the power input code you select.
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 3/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
COMMUNICATION CABLE CONNECTIONS
■ WIRING CONNECTION WITH SLAVE DEVICES
WL40MW1VN
REMOTE UNIT
REMOTE UNIT
TERMINATOR
TERMINATOR
DA
DB
DA
DB
DA
DB
DG
SLD
FE
DG
SLD
FE
DG
SLD
FE
*
* Connect SLD and FE for reducing noise interference if necessary.
Note: Be sure to connect the terminating resistor included in the product package to the unit
at both ends of communication line.
The terminator must be connected across “DA” and “DB”.
TERMINAL ASSIGNMENTS
■ CONNECTORS FOR POWER INPUT
Unit side connector: MSTBV2,5/5-GF-5,08AU (Phoenix Contact)
Cable side connector: TFKC2,5/5-STF-5,08AU (Phoenix Contact)
• Power input code: R (24 V DC)
• Power input code: S (12 V DC)
ID
24V
0V
FUNCTION
ID
12V
0V
FUNCTION
Power input 24 V
Power input 0 V
Not used
Power input 12 V
Power input 0 V
Not used
24V
0V
12V
0V
NC
NC
FE1
NC
NC
FE1
NC
NC
FE1
NC
NC
FE1
Not used
Not used
Power input earth
Power input earth
■ CONNECTOR FOR RS-485 COMMUNICATION
Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact)
Cable side connector: TFMC1,5/5-STF-3,5 (Phoenix Contact)
ID
DA
FUNCTION
DA
DA
DB
DG
SLD
FE
DB
DG
SLD
FE
DB
DG
Shield
Functional earth
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 4/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
MODBUS FUNCTION CODES & SUPPORTED CODES
Modbus function codes are shown below.
■ DATA AND CONTROL FUNCTION
CODE NAME
01
02
03
04
05
06
08
15
16
Read Coil Status
Digital output from the slave (read/write)
Read Input Status
Read Holding Registers
Read Input Registers
Force Single Coil
Status of digital inputs to the slave (read only)
General purpose register within the slave (read/write)
Collected data from the !eld by the slave (read only)
Digital output from the slave (read/write)
Preset Single Register
Diagnostics
General purpose register within the slave (read/write)
Force Multiple Coils
Preset Multiple Registers
Digital output from the slave (read/write)
General purpose register within the slave (read/write)
■ EXCEPTION CODE
CODE NAME
01
02
03
04
05
06
07
Illegal Function
Function code is not allowable for the slave
Address is not available within the slave
Data is not valid for the function
Illegal Data Address
Illegal Data Value
Slave Device Failure
Acknowledge
Slave Device Busy
Negative Acknowledge
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 5/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
EXTERNAL DIMENSIONS unit: mm (inch)
• With sleeve antenna
DIN RAIL
35mm wide
60 (2.36)
45 (1.77)
107 (4.21)
3 (.12)
[200 (7.87)]
• With rooftop antenna
ø3 (.12)
ø1.2 (.05)
8 (.31) Hex.
DIN RAIL
35mm wide
ø27
approx. 2500 (98.4)
(1.06)
107 (4.21)
20
(.79)
3 (.12)
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 6/7
http://www.m-system.co.jp/
MODEL: WL40MW1VN
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
LED
Two-way
Antenna Connector
DA
wireless circuit
Isolation
DB
To Other
Modbus Devices
DG
SLD
FE
Maintenance Connector USB Connector
Configuration Jack
Jack
Control
Circuit
24V*
Power Input
0V
NC
NC
FE1
* Power input defers depending on the power input code you select.
SYSTEM CONFIGURATION EXAMPLES
PC side as Modbus/Master communicates with child devices via wireless module using Modbus/TCP and RTU protocol,
and also communicates with slave devices in multi drop connection (RS-485).
LAN cable
(STP cable)
RS-485
Slave Device
Slave Device
MAX. 31
Slave Device
Wireless gateway
(model: WL40MW1VN)
PC
Modbus/Master
Wireless gateway
(model: WL40EW2VN)
Specifications are subject to change without notice.
WL40MW1VN SPECIFICATIONS
ES-9118 Rev.0 Page 7/7
http://www.m-system.co.jp/