VS-CKBB6-2 [PANDUIT]

VeriSafe™ Absence of Voltage Tester The Safe Way to Verify the Absence of Voltage.;
VS-CKBB6-2
型号: VS-CKBB6-2
厂家: PANDUIT CORP.    PANDUIT CORP.
描述:

VeriSafe™ Absence of Voltage Tester The Safe Way to Verify the Absence of Voltage.

文件: 总8页 (文件大小:3461K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Product Bulletin  
VeriSafeAbsence of Voltage Tester  
The Safe Way to Verify the  
Absence of Voltage.  
When servicing electrical equipment, workers must  
comply with safety regulations that require a voltage  
verification test to validate the absence of voltage.  
This process includes a number of stages that can  
be complex and time-consuming when using  
hand-held portable test instruments.  
The patent-pending VeriSafeAbsence of Voltage  
Tester from Panduit simplifies this process by  
automating the voltage verification process.  
Once installed, a simple push of a button enables qualified electrical workers to verify the absence of voltage  
and see an active indication when the absence of voltage is confirmed. This provides a new and innovative way  
to safely, reliably, and efficiently verify the absence of voltage before accessing potentially dangerous electrical  
equipment.  
By automating this process, the VeriSafeAbsence of Voltage Tester  
• Reduces the risk of exposure of electrical hazards for improved worker safety  
• Reduces testing procedure time and complexity to improve productivity  
• Supports compliance when used as part of the lockout/tagout process  
described in NFPA 70E*  
The VeriSafeAbsence of Voltage Tester minimizes risk by verifying the absence of voltage before equipment  
is accessed, making it easier for qualified electrical workers to determine an electrically safe environment in a  
fraction of the time compared to hand-held portable test instruments.  
K e y F e a t u r e s  
Improved Safety & Risk Reduction  
B e n e f i t s  
Determine voltage status BEFORE equipment is accessed  
Prevents direct exposure to electrical hazards  
Easy to use, initiate test with the push of a button  
No additional tools required  
Increased Productivity  
Provides visual alert to abnormal power conditions  
Test sequence based on the steps in NFPA 70E for verification of an electrically safe  
work condition  
Simplified Process for Easier Compliance  
Automated test helps reduce operator errors  
Fail-safe design with active indications  
Safety functions meet SIL 3 per IEC 61508-1  
Reliable Results  
Designed for testing three-phase circuits up to 600V  
Install on line or load side of electrical disconnect  
Detects absence of AC and DC voltage  
Flexible Applications  
*The VeriSafe Absence of Voltage Tester satisfies the requirements for permanently mounted test devices described in  
NFPA 70E-2018 120.5 (7) Exception 1 when it is installed in accordance with the ratings and instructions in the VeriSafe  
AVT Installation Manual.  
VeriSafeAbsence of Voltage Tester  
E l e c t r i c a l S a f e t y  
Prior to performing de-energized work on electrical  
equipment, NFPA 70E requires that workers verify  
equipment is in an electrically safe state. Until proven  
otherwise, equipment must be treated as energized and  
necessary precautions must be observed.  
One of the steps in the process of verifying that equipment  
is in an electrically safe state involves a test for the absence  
of voltage.  
V e r i f y i n g t h e A b s e n c e o f V o l t a g e  
Before and after testing, the functionality of the tester must  
be verified on a known source. When using a portable tester,  
this is a time-consuming process and may involve exposure  
to electrical hazards.  
Using the VeriSafeAbsence of Voltage Tester reduces risk  
and ensures the entire process is performed in the proper  
sequence – every time, every test.  
C o m p a r i s o n o f T e s t i n g M e t h o d s  
Test  
the  
Check  
Retest  
the  
Perform  
Work  
Select  
Tester  
for  
Tester  
Voltage  
Tester  
Possible Exposure to Electrical Hazards  
Open  
Panel  
Activate the VeriSafe AVT  
Test  
Check  
for  
Retest  
Verify  
Verify  
the  
the  
Installation  
Installation  
Tester  
Voltage  
Tester  
Automatically Performed in Sequence  
No Exposure to Electrical Hazards  
2
VeriSafeAbsence of Voltage Tester  
M o r e t h a n a V o l t a g e I n d i c a t o r  
Voltage indicators warn of hazardous voltage, but cannot be used to confirm if equipment is de-energized. Absence  
of voltage testers are permanently-mounted test devices designed to verify that a circuit is de-energized prior to  
opening an electrical enclosure containing electrical conductors and circuit parts.  
Pressing the "TEST" button initiates  
the voltage test, indicated by the  
flashing YELLOW caution indicator.  
RED indicators illuminate  
when hazardous AC voltage  
is present.  
When voltage is not detected,  
indicators are not illuminated.  
This does not guarantee the  
absence of voltage.  
GREEN indicator illuminates  
only when the absence of  
voltage has been verified.  
Upstream Power: ON  
Upstream Power: OFF  
Upstream Power: OFF  
Upstream Power: OFF  
Absence of Voltage Testers are Fail-Safe and Reliable  
• Test each phase conductor or circuit part phase-to-phase and phase-to-ground for absence of voltage  
• Built-in test circuit verifies operation on a known voltage source before and after absence of voltage test  
• Verifies installation of hardwired test leads before and after absence of voltage test  
• Functional safety principles ensure hardware and firmware are designed to prevent and control dangerous  
failures of safety functions  
• Installed device ensures tester is rated for the application and is less susceptible to damage than  
portable testers  
• Automated test sequence helps reduces operator errors  
3
VeriSafeAbsence of Voltage Tester  
S y s t e m C o m p o n e n t s  
Indicator Module  
1
• 30mm knockout, mount on exterior of enclosure  
• Operate and maintain without exposure to electrical hazards  
• Instruction label with operating instructions  
2
AVT System Cable  
• Connects Isolation Module to Indicator Module  
• 600V cable available in multiple lengths for easy  
installation  
• Replaceable with connectors on each end  
Isolation Module  
3
4
• Prevents hazardous voltage from reaching door  
• Universal mounting (DIN rail or surface tabs)  
2
• Output contacts provide ability to create alarms or  
communicate with other systems  
Sensor Leads  
• Can be installed on line or load side of electrical disconnect  
• 2 leads per phase; must be physically separated from each other  
Simple Battery Replacement  
• Long-life industrial battery  
• Replaceable from outside the enclosure  
• Interior battery compartment is fingersafe (IP20)  
• No tools required  
4
VeriSafeAbsence of Voltage Tester  
1
3
4
1
Instruction Label  
5
VeriSafeAbsence of Voltage Tester  
D i m e n s i o n s *  
S c h e m a t i c s  
Three-Phase Delta: 3 Wire + PE  
Indicator Module  
4.67  
[119]  
Ø 1.913  
[48.6]  
1.54  
[39.1]  
PANEL  
KNOCKOUT  
0.180  
[4.6]  
Three-Phase WYE: 3 Wire + Neutral and PE  
0.080  
[2.0]  
Isolation Module  
3.96  
3.31  
[100.6]  
[84.1]  
DC System: 2 Wire +  
1.51  
[38.4]  
3.46  
[87.9]  
3.68  
[93.5]  
1.57  
[39.8]  
1.29  
[32.9]  
Warning: The AVT must be installed correctly and grounded as described in the installation instructions to provide proper indication of absence  
of voltage. Sensor leads, including ground, must not be mechanically connected to each other in order for the device to verify connection to  
the circuit.  
*Dimensions in inches [millimeters].  
6
VeriSafeAbsence of Voltage Tester  
Three-Phase WYE High Resistance  
Ground: 3 Wire + Neutral and PE  
Three-Phase WYE: 3 Wire + PE (No Neutral)  
Single-Phase: 2 Wire + PE  
Single-Phase: 3 Wire + PE  
Corner Grounded DELTA: 3 Wire + PE  
High-Leg DELTA: 3 Wire + Neutral + PE  
7
V o l t a g e V e r i f i c a t i o n S y s t e m  
Ordering Information  
Part Number  
Part Description  
VeriSafeAbsence of Voltage Testers  
VeriSafeAbsence of Voltage Tester with 2 ft. system cable, 3 ft. sensor leads.  
VeriSafeAbsence of Voltage Tester with 2 ft. system cable, 10 ft. sensor leads.  
VeriSafeAbsence of Voltage Tester with 8 ft. system cable, 10 ft. sensor leads.  
VS-AVT-C02-L03  
VS-AVT-C02-L10  
VS-AVT-C08-L10  
Accessories  
VS-AVT-CABLE-02  
VS-AVT-CABLE-08  
VeriSafeReplacement Cable, 2 ft.  
VeriSafeReplacement Cable, 8 ft.  
Sensor Lead Connection Kits  
VS-CKBB8-4  
VS-CKBB6-2  
VS-CKBB2-00  
VeriSafe Connection Kit for Tapping 8 to 4 AWG conductors.  
VeriSafe Connection Kit for Tapping 6 to 2 AWG conductors.  
VeriSafe Connection Kit for Tapping 2 to 2/0 AWG conductors.  
Equipment Retrofit Kits  
VS-AVT-RKBB2  
VS-AVT-RKBB3  
VS-AVT-RKBB4  
Complete kit to retrofit equipment with VeriSafe Absence of Voltage Tester. Includes AVT device with 10ft. sensor leads, 2ft. and 8ft. system  
cable, Connection Kit 8-4AWG power connectors, (12) cable ties, (6) cable ties mounts, (1) wire markers.  
Complete kit to retrofit equipment with VeriSafe Absence of Voltage Tester. Includes AVT device with 10ft. sensor leads, 2ft. and 8ft. system  
cable, Connection Kit 6-2AWG power connectors, (12) cable ties, (6) cable ties mounts, (1) wire markers.  
Complete kit to retrofit equipment with VeriSafe Absence of Voltage Tester. Includes AVT device with 10ft. sensor leads, 2ft. and 8ft. system  
cable, Connection Kit 2-2/0AWG power connectors, (12) cable ties, (6) cable ties mounts, (1) wire markers.  
Technical Specifications  
Applications  
Electrical System  
For use in 1 and 3-phase AC systems  
Voltage Detection Range  
Absence of Voltage Threshold  
Overvoltage Category  
Degree of Protection*  
Up to 600V AC (50/60Hz), 600V DC; Rated tolerance +10%  
3 V  
III (600 V)  
Indicator Module: For Flat Surface Mounting in a TYPE (UL, NEMA and CSA) 1, 12, 4, 4X, or IP66 Enclosure  
Isolation Module: Open Type, IP20  
Environment  
Operating Temperature  
Storage Temperature  
Humidity  
0°C to + 60°C (32°F to 140°F)  
-45°C to + 85°C (-49°F to +185°F)  
5 to 90% non-condensing; Rated 80% at 40°C, decreasing linearly to 50% at 60°C  
Pollution Degree  
Altitude  
3
Up to 2000 meters (1.24 miles)  
Battery  
Type  
Industrial 3.6V Lithium AA, see table in Maintenance section of installation guide for compatible batteries.  
Standards  
UL 1436  
Standard for outlet circuit testers and similar indicating devices  
CAN/CSA-C22.2 No. 160  
IEC / UL / CSA C22.2 No. 61010-1  
IEC / UL / CSA C22.2 No. 61010-2-030  
Voltage and Polarity Testers  
Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 1: General Requirements  
Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 2-030: Particular  
requirements for testing and measuring circuits  
UL 508 & CSA-C22.2 No. 14  
Industrial control equipment  
IEC 61508-1, -2, and -3 {SIL 3 Rating}  
Safety of Electrical/Electronic/programmable Electronic safety-related security systems –  
Part 1 General Requirements  
Part 2 Requirements for Electrical / Electronic / Programmable safety related systems  
Part 3 Software Requirements  
FCC - CFR 47 Part 15 Subpart B  
IEC 61326-1, -3-1, -3-1: corr 1  
EN 61326-1, -3-1  
Radio frequency devices  
Electrical equipment for measurement, control and laboratory use-EMC requirements - Part 1  
Part 3-1: Immunity requirements for safety-related systems and for equipment intended to perform safety-related functions  
(functional safety) - General industrial applications including corrigendum 1  
EN 55011, CISPR 11  
Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and methods of measurement  
IEC / EN61000-3-2  
IEC / EN61000-3-3  
Electromagnetic compatibility (EMC) - Part 3-2: Limits — Limits for harmonic current emissions (equipment input current 16 A  
per phase)  
EN 61000-6-2  
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments  
AS/NZS CISPR 11  
Australian / New Zealand Standard - Industrial, scientific and medical equipment—Radio-frequency disturbance characteristics—  
Limits and methods of measurement  
CAN - ICES-001  
CE  
Industrial, Scientific and Medical (ISM) radio frequency generators.  
Conformity Marking for European Economic Area  
Restriction of hazardous substances  
RoHS  
*Degree of protection specified is related to the Indicator Module only. To meet the TYPE (UL, NEMA and CSA) 1, 12, 4 or 4X requirements, mount on a flat surface of an enclosure meeting the  
appropriate UL TYPE or NEMA rating. Verify that the seal and o-rings are clean to ensure proper sealing.  

相关型号:

VS-CKBB8-4

VeriSafe™ Absence of Voltage Tester The Safe Way to Verify the Absence of Voltage.
PANDUIT

VS-CPV362M4FPBF

Insulated Gate Bipolar Transistor,
VISHAY

VS-CPV362M4UPBF

Insulated Gate Bipolar Transistor,
VISHAY

VS-CPV363M4UPBF

Insulated Gate Bipolar Transistor,
VISHAY

VS-EBU15006HF4

Rectifier Diode, 1 Phase, 1 Element, 150A, 600V V(RRM), Silicon, ROHS COMPLIANT, POWERTAB-1
VISHAY

VS-EBU8006HF4

Rectifier Diode, 1 Phase, 1 Element, 80A, 600V V(RRM), Silicon, ROHS COMPLIANT, POWERTAB-1
VISHAY

VS-EPH3006-F3

Hyperfast Rectifier, 30 A FRED Pt
VISHAY

VS-EPH3006-N3

Hyperfast Rectifier, 30 A FRED Pt
VISHAY

VS-EPH3006HN3

Rectifier Diode, 1 Phase, 1 Element, 30A, 600V V(RRM), Silicon, MODIFIED TO-247AC, 3/2 PIN
VISHAY

VS-EPH3006L-M3

Rectifier Diode, 1 Phase, 1 Element, 30A, 600V V(RRM), Silicon, TO-247,
VISHAY

VS-EPU3006-F3

Ultrafast Rectifier, 30 A FRED Pt
VISHAY

VS-EPU3006-N3

Ultrafast Rectifier, 30 A FRED Pt
VISHAY