ECS130US15 [XPPOWER]

AC-DC Regulated Power Supply Module, 130W;
ECS130US15
型号: ECS130US15
厂家: XP POWER LIMITED    XP POWER LIMITED
描述:

AC-DC Regulated Power Supply Module, 130W

输出元件
文件: 总5页 (文件大小:932K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
65/100/130 Watts  
ECS Series  
xppower.com  
IT & Medical Safety Approvals  
65/80/100 W - Convection-cooled Ratings  
Class I & Class II Construction  
Industry Standard 2”x 4”Package  
<0.5 W No Load Input Power  
Low Leakage Current  
3 Year Warranty  
Specification  
Input  
General  
Efficiency  
Isolation  
• Up to 90% model dependent  
Input Voltage  
• 80-264 VAC (275 VAC ECS65)  
(120-370 VDC), derate output power  
<90 VAC, see derating curves  
• 4000 VAC Input to Output, 2 x MOPP,  
1500 VAC Input to Ground, 1 x MOPP,  
500 VDC Output to Ground, 1 x MOPP  
(1)  
Input Frequency  
Input Current  
• 47-400 Hz  
Switching Frequency  
Power Density  
• 65 KHz typical  
• 65 W: 1.0/0.6 A typical at 115/230 VAC  
100 W: 1.5/0.9 A typical at 115/230 VAC,  
130 W: 1.9/1.1 A typical at 115/230 VAC  
full load  
• 40 A max at 230 VAC, cold start at 25 ˚C  
• EN61000-3-2, class A  
3
3
• 65 W: 7.7 W/in , 100 W: 10 W/in ,  
3
130 W: 13 W/in  
MTBF  
• 65 W: 850 kHrs, 100 W: 834 kHrs,  
130 W: 715 kHrs to MIL-HDBK-217F  
at 25 ˚C, GB  
Inrush Current  
Power Factor  
No Load Input Power • <0.5 W  
Environmental  
Operating Temperature • -20 ˚C (-40 ˚C, ECS130) to +70 ˚C derate  
linearly from +50 ˚C at 2.5%/˚C to 50%  
load at +70 ˚C.  
Earth Leakage Current • 65/130 W: 260 µA at 264 VAC/60 Hz max  
100 W: 230 µA at 264 VAC/60 Hz max  
Input Protection  
• Internal T3.15/T5 A/250 V fuse in line and  
neutral  
Cooling  
• Convection & fan cooled ratings(see tables)  
• 95% RH, non-condensing  
• -40 ˚C to +85 ˚C  
• 65-100 W: 3000 m, 130 W: 5000m  
• 30 g pk, half sine, 6 axes  
• 2 g rms, 5 Hz to 500 Hz, 3 axes  
Operating Humidity  
Storage Temperature  
Operating Altitude  
Shock  
Output  
Output Voltage  
Output Voltage Trim  
Initial Set Accuracy  
Minimum Load  
Start Up Delay  
Start Up Rise Time  
Hold Up Time  
• 12-48 VDC (see tables)  
10%  
1%  
Vibration  
• No minimum load required  
• 1 s typical  
• 50 ms  
EMC & Safety  
Low Voltage PSU EMC • EN61204-3, high severity level  
Emissions  
• EN55011/22 level B conducted  
EN55011/22 level A radiated, level B  
Suffix ‘-B’ models  
• EN61000-3-2, class A  
• EN61000-3-3  
• EN61000-4-2, 6 kV Contact, 15 kV Air  
Discharge, Perf Criteria A  
• EN61000-4-3, level 3 Perf Criteria A  
• EN61000-4-4, level 3 Perf Criteria A  
• EN61000-4-5, installation class 3  
Perf Criteria A  
• EN61000-4-6, level 3 Perf Criteria A  
• EN61000-4-11, 30% 10 ms, 60% 100 ms,  
100% 5000 ms, Perf Criteria A, B, B,  
EN60601-1-2, 30% 500 ms, 60% 100 ms,  
100% 10 ms, 100% 5000 ms, Perf Criteria  
A, A, A, B - 230 VAC. Consult longform  
datasheet for 115 V operation.  
• 16 ms min at 115 VAC  
Drift  
0.2% after 20 min warm up  
0.5% max  
1%  
Line Regulation  
Load Regulation  
Over/Undershoot  
Transient Response  
Harmonic Currents  
Voltage Flicker  
ESD Immunity  
• 5% typical  
• 4% max. deviation, recovery to within  
1% in 500 µs for a 50-75-50% load  
change  
Radiated Immunity  
EFT/Burst  
Surge  
Ripple & Noise  
• 1% pk-pk, 20 MHz bandwidth  
Overvoltage Protection 115-140% Vnom, recycle input to reset  
Overload Protection 110-160%  
Short Circuit Protection • Continuous trip and restart (hiccup mode)  
Conducted Immunity  
Dips & Interruptions  
Temperature  
Coefficient  
• 0.05%/˚C  
Safety Approvals  
• IEC60950-1 CB report, CSA 22.2  
No. 60950-1, UL60950-1, TUV EN60950-1  
IEC60601-1 CB report, CSA 22.2  
Notes  
No. 60601-1, ANSI/AMMI ES60601-1,  
TUV 60601-1, including risk management  
1. Safety approvals cover frequency 47-63 Hz.  
Equipment Protection • Class I & II (ECS65 Non ‘-B’ models,  
Class  
Class I only)  
ECS65  
Models and Ratings  
Output Power  
Output Voltage  
Output Current  
Model Number(1)  
65 W  
65 W  
65 W  
65 W  
65 W  
65 W  
12.0 VDC  
15.0 VDC  
18.5 VDC  
24.0 VDC  
28.0 VDC  
48.0 VDC  
5.4 A  
4.3 A  
3.4 A  
2.7 A  
2.3 A  
1.4 A  
ECS65US12  
ECS65US15  
ECS65US18  
ECS65US24  
ECS65US28  
ECS65US48  
Notes  
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER  
for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations.  
Mechanical Details  
4.00 (101.6)  
3.750 (95.25)  
1.05  
(26.7)  
0.125 (3.17)  
C4  
1
2.00 (50.8)  
1.75 (44.45)  
2
1
C5  
J1  
T1  
1
4
J2  
0.95 (24.1)  
0.96 (24.5)  
0.25 Faston Ground Tab  
0.125 (3.18)  
0.20 (5.1)  
Q1  
0.14 (3.5)  
SMD Component Height  
0.20 (5.1)  
4 X ø.156 (3.96) Mounting Holes  
ø.312 (7.92) Clearance top and bottom  
Input Connector J1  
Molex PN 09-65-2038  
Output Connector J2  
Molex PN 09-65-2048  
Pin 1  
Pin 2  
0.25” Faston  
Line  
Neutral  
Earth  
Pin 1  
Pin 2  
Pin 3  
Pin 4  
+V1  
+V1  
RTN  
RTN  
J1 mates with Molex Housing PN 09-50-1031, J2 mates with  
Molex Housing PN 09-50-1041 and both with Molex Series 5194  
Crimp Terminals  
Notes  
1. All dimensions in inches (mm).  
2. Weight: 0.386 lbs (175 g)  
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)  
Derating Curve - ECS65 Models  
100  
90  
100  
90  
Open Frame  
80  
80  
70  
60  
50  
40  
70  
60  
50  
40  
37.5  
30  
80  
85  
90  
275  
75  
40  
50  
60  
-20  
Input Voltage (VAC)  
AmbientTemperature (ºC)  
ECS100  
Models and Ratings  
Output Power  
Output Voltage  
Output Current  
Model Number(1)  
Forced Cooled (10 CFM)  
Convection-cooled  
100 W  
100 W  
100 W  
100 W  
100 W  
100 W  
80 W  
80 W  
80 W  
80 W  
80 W  
80 W  
12.0 VDC  
15.0 VDC  
18.0 VDC  
24.0 VDC  
28.0 VDC  
48.0 VDC  
8.3 A  
6.7 A  
5.5 A  
4.2 A  
3.6 A  
2.1 A  
ECS100US12  
ECS100US15  
ECS100US18  
ECS100US24  
ECS100US28  
ECS100US48  
Notes  
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER  
for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations. ‘-C’ not available for ‘-B’ models.  
Mechanical Details  
1.25 (31.8)  
4.00 (101.6)  
3.750 (95.25)  
0.125 (3.18)  
C4  
Voltage  
Adj.  
1.750  
2.00 +0.06/-0.00  
(50.8 +1.5/-0.00)  
(44.45)  
J1  
C5  
T1  
J2  
Output Connector J2  
Molex PN 09-65-2048  
1.01  
1.00  
(25.4)  
(25.7)  
Pin 1  
Pin 2  
Pin 3  
Pin 4  
+V1  
+V1  
RTN  
RTN  
Q1  
0.25 Faston  
Ground Tab  
0.20 (5.1)  
0.14 (3.5)  
0.125 (3.18)  
0.20 (5.1)  
SMD Component  
Height  
4 X ø.156 (3.96) Mounting Holes  
Input Connector J1  
ø.312 (7.92) Clearance top and bottom  
Molex PN 09-65-2038  
Pin 1  
Pin 2  
0.25” Faston  
Line  
Neutral  
Earth  
‘-B’ Model  
4.50 (114.3)  
3.75 (95.25)  
1.25 (31.8)  
0.37 (9.52)  
J1 mates with Molex Housing  
PN 09-50-1031, J2 mates with  
Molex Housing PN 09-50-1041  
and both with Molex Series  
5194 Crimp Terminals  
2.00 +0.06/-0.00  
(50.8 +1.5/-0.00)  
1.75  
J1  
(44.45)  
Notes  
J2  
0.20  
(5.1)  
1. All dimensions in inches  
(mm).  
Tolerance .xx = 0.02  
(0.50); .xxx = 0.01 (0.25)  
2. Weight: 0.386 lbs (175 g)  
1.00  
1.01  
(25.4)  
(25.7)  
0.20 (5.1)  
0.14 (3.5)  
0.125 (3.18)  
SMD Component  
Height  
4 X ø.156 (3.96) Mounting Holes  
ø.312 (7.92) Clearance top and bottom  
0.10 (2.5)  
0.25 Faston Ground Tab  
Derating Curve - ECS100 Models  
100  
90  
100  
90  
Force-cooled >10 CFM  
Convection-cooled  
80  
80  
70  
60  
50  
40  
70  
60  
50  
40  
30  
Convection-cooled with cover  
+70  
80  
85  
90  
264  
-20  
+40  
+50  
+60  
Input Voltage (VAC)  
Ambient Temperature (ºC)  
ECS130  
Models and Ratings  
Output Power  
Output Voltage  
Output Current  
Model Number(1)  
Forced Cooled (10 CFM)  
Convection-cooled  
130 W  
130 W  
130 W  
130 W  
130 W  
130 W  
100 W  
100 W  
100 W  
100 W  
100 W  
100 W  
12.0 VDC  
15.0 VDC  
18.0 VDC  
24.0 VDC  
28.0 VDC  
48.0 VDC  
10.9 A  
8.7 A  
7.3 A  
5.4 A  
4.7 A  
2.7 A  
ECS130US12  
ECS130US15  
ECS130US18  
ECS130US24  
ECS130US28  
ECS130US48  
Notes  
1. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER for standalone cover, see derating curve.  
The cover is not suitable for Class II installations. ‘-C’.  
Mechanical Details  
4.00 (101.6)  
1.28  
0.125 (3.17)  
1.75 (44.45)  
3.750 (95.25)  
(32.5)  
Voltage Adjust  
C4  
2.00 +0.06/-0.00  
(50.8 +1.5/-0.00)  
N
J1 2  
1
4
1
T1  
L
J2  
C5  
1.00 (25.4)  
1.05 (26.7)  
0.20 (5.1)  
Q1  
0.12 (3.18)  
0.15 (3.8)  
SMD COMPONENT HEIGHT  
0.20 (5.1)  
.25 FASTON  
GROUND TAB  
4X 0.156 (3.96) MOUNTING HOLES  
0.312 (7.92) CLEARANCE TOP AND BOTTOM  
Output Connector J2  
Molex PN 09-65-2048  
Input Connector J1  
Notes  
Molex PN 09-65-2038  
1. All dimensions in inches (mm).  
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)  
2. Weight: 0.386 lbs (175 g)  
Pin 1  
Pin 2  
Pin 3  
Pin 4  
+V1  
+V1  
RTN  
RTN  
Pin 1  
Pin 2  
0.25” Faston  
Line  
Neutral  
Earth  
J1 mates with Molex Housing PN 09-50-1031, J2 mates with Molex Housing PN 09-50-1041  
and both with Molex Series 5194 Crimp Terminals  
Derating Curve - ECS130 Models  
130  
130  
120  
110  
120  
110  
Forced-cooled >10 CFM  
Convection-cooled  
Forced-cooled >10 CFM  
Convection-cooled  
100  
90  
100  
90  
80  
70  
80  
70  
60  
60  
Convection-cooled with cover  
Convection-cooled with cover  
50  
40  
30  
20  
10  
50  
40  
30  
20  
10  
80  
90  
100  
264  
-40  
-20  
0
50  
60  
70  
Input Voltage (VAC)  
Ambient Temperature (ºC)  
ECS65/100/130  
Mechanical Details  
Covered Version (not available for ECS100-B Models)  
4.49 (114.0)  
2.52  
Input Connector  
Output Connector  
(64.0)  
0.25 (0.6) Ground  
Faston Terminal  
0.807  
(20.50)  
1.54  
(39.0)  
2 x M3 x 0.5 THD  
0.16 (4.0)  
Max Screw Penetration  
4.055 (103.00)  
4.055 (103.00)  
0.22  
(5.5)  
0.22  
(5.5)  
0.79  
(20.0)  
0.984  
(25.00)  
4 x M3 x 0.5 THD  
0.16 (4.0) Max Screw Penetration  
Notes  
1. All dimensions in inches (mm).  
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)  
2. Weight: 0.8 lbs (360 g)  
Thermal Considerations - All Models  
In order to ensure safe and reliable operation of the PSU in the most adverse conditions permitted in the end-use equipment, the temperature of the components  
listed in the table below must not be exceeded. See mechanical drawing for component locations. Temperature should be monitored using K type thermocouples  
placed on the hottest part of the component (out of any direct air flow).  
Temperature Measurements (Ambient 50 °C)  
Component  
Max Temperature °C  
110 °C  
T1  
C5  
C4  
Q1  
100 °C  
100 °C  
110 °C  
20-Jan-17  

相关型号:

ECS130US15-C

AC-DC Regulated Power Supply Module, 130W
XPPOWER

ECS130US18

AC-DC Regulated Power Supply Module, 130W
XPPOWER

ECS130US24

Convection & Forced Cooled Ratings
XPPOWER

ECS130US24-C

AC-DC Regulated Power Supply Module, 130W
XPPOWER

ECS130US28

AC-DC Regulated Power Supply Module, 130W
XPPOWER

ECS130US28-C

AC-DC Regulated Power Supply Module, 130W
XPPOWER

ECS130US48

Convection & Forced Cooled Ratings
XPPOWER

ECS1X5

Peripheral IC
ETC

ECS1X5-1.0

Micro Peripheral IC
ECS

ECS2100

Peripheral IC
ETC

ECS21P2131

COMMON MODE NOISE FILTERS
ABCO

ECS21P2181

COMMON MODE NOISE FILTERS
ABCO