CPU001-BB [ETC]

CPU001-BB;
CPU001-BB
型号: CPU001-BB
厂家: ETC    ETC
描述:

CPU001-BB

文件: 总5页 (文件大小:89K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
CPU Module  
March 1999  
GFK-1536C  
Product Information _________________________________  
Module Installation _________________________________  
Revision:  
CPU001-BB  
Modules must be mounted on a  
horizontal DIN rail.  
Firmware version:  
Compatibility:  
1.10  
1
1. Allow sufficient finger clearance  
for opening CPU door.  
VersaPro software version 1.0  
2
2. Allow adequate clearance for  
serial port cables.  
New Features ____________________________________  
133.35mm  
(5.25in)  
3. Allow adequate space for power  
wiring.  
This version of CPU001 provides:  
Support for intelligent I/O modules.  
Scaling function blocks.  
The CPU with power supply attached  
fits into a 70mm deep enclosure.  
66.80mm  
(2.63in)  
Two new function blocks can be used to scale input data.  
Rated thermal specifications for the  
CPU module is based on a clearance  
of 2” above and below the equipment  
and 1” to the left of the CPU module.  
One function block is for unipolar (unsigned) input data. The other  
function block is for bipolar (signed) input data.  
3
Drum Sequencer function block.  
This new function block works like a mechanical drum sequencer.  
It allows a sequence of output combinations to be selected in turn.  
See the heading “The Drum Sequencer Function” for more  
information.  
Installing the CPU on the DIN Rail  
The CPU and connecting carriers must be  
installed on the same section of 35mm x  
7.5mm DIN rail. The rail must have a  
conductive (unpainted) finish for proper  
grounding. For best stability, the DIN rail  
should be installed on a panel using  
screws spaced approximately 6 inches  
(5.24cm) apart.  
Specifications  
Size  
2.63” (66.8mm) x 5.04” (128mm)  
2048 In, 2048 Out  
128 In, 128 Out  
2048 words  
I/O Discrete Points  
I/O Analog Words  
Registers  
The CPU snaps easily onto the DIN rail.  
No tools are required for mounting or  
grounding to the DIN rail.  
Discrete Internal Bits  
Discrete Temporary Bits  
Global Discrete Bits  
Program Memory  
Boolean execution speed  
Floating Point  
1024 points  
Before joining module carriers to the CPU, remove the connector cover on  
the righthand side of the CPU. Do not discard this cover, you will need to  
install it on the last carrier, to protect the connector pins from contamination  
and damage during use.  
256 points  
1280 points  
12288 bytes  
1.8ms/K (typical)  
Yes  
Panel-Mounting __________________________________  
If excessive vibration is a factor the CPU should also be screwed down to  
the mounting panel.  
Override  
Yes  
Note 1. Tolerances are +/- 0.13mm (0.005in) non-cumulative.  
Built-in ports  
RS-232, RS-485  
SNP Slave, RTU Slave, Serial I/O  
System flash, battery-backed RAM  
Yes  
Note 2. 1.1-1.4Nm (10-12 in/lbs) of torque should be applied to M3.5 (#6-  
32) steel screw threaded into material containing internal threads  
and having a minimum thickness of 2.4mm (0.093in).  
Built-in communications  
Type of memory storage  
Battery-Backed Real-time Clock  
SEE NOTE 2.  
M3.5 (#6) SCREW  
4.3mm  
Realtime clock accuracy (used  
for timers or timer contacts)  
100ppm (0.01%) or +/- 9sec/day  
0.170in  
SPLIT LOCK  
WASHER  
Time-of-day clock accuracy  
23ppm (.0023%)or +/- 2sec/day @ 30C;  
100 ppm ((0.01%) or +/- 9sec/day @ full  
temperature range.  
FLAT WASHER  
4.3mm  
0.170in  
15.9mm  
0.62in REF  
5.1mm  
0.200in  
Preinstallation Check _____________________________  
TAPPED  
HOLE IN  
PANEL  
CPU  
Carefully inspect all shipping containers for damage. If any equipment  
is damaged, notify the delivery service immediately. Save the damaged  
shipping container for inspection by the delivery service. After  
unpacking the equipment, record all serial numbers. Save the shipping  
containers and packing material in case it is necessary to transport or  
ship any part of the system.  
Removing the CPU from the DIN Rail ___________________  
1. Turn off power to the power supply.  
2. (If the CPU is attached to the panel with a screw) remove the power  
supply module. Remove the panel-mount screw.  
3. Slide the CPU away from the other modules until the connector on the  
right side disengages from the next carrier.  
4. With a small flathead screwdriver, pull the DIN rail latch outward while  
tilting the other end of the module down to disengage it from the DIN  
rail.  
1
CPU Module  
March 1999  
GFK-1536C  
Activating or Replacing the Backup Battery  
______________  
Observing the Module LEDs _________________________  
PWR  
The LEDs indicate the presence of power and show the  
operating mode and status of the CPU.  
The CPU is shipped with a battery already installed. The battery holder  
is located in the top side of the CPU module. Before the first use,  
activate the battery by pulling and removing the insulator tab.  
OK  
RUN  
FAULT  
FORCE  
PORT 1  
PORT 2  
To replace the battery, use a small screwdriver to gently pry open the  
battery holder. Replace battery only with IC200ACC001 from your PLC  
supplier, or with Panasonic battery: BR2032. Use of another battery  
may present a risk of fire or explosion.  
POWER  
OK  
ON when the CPU is receiving 5V power from the power  
supply. Does not indicate the status of the 3.3V power  
output.  
ON indicates the CPU has passed its powerup diagnostics  
and is functioning properly. OFF indicates a CPU problem.  
Fast blinking indicates the CPU is running its powerup  
diagnostics. Slow blinking indicates the CPU is configuring  
I/O modules. Simultaneous blinking of this LED and the  
green Run LED indicates the CPU is in boot mode and is  
waiting for a firmware download through port 1.  
Caution  
Battery may explode if mistreated.  
Do not recharge, disassemble, heat above 100 deg.C (212 deg.F) or  
incinerate.  
Autoconfiguration __________________________________  
RUN  
Green when the CPU is in Run mode. Amber indicates the  
CPU is in Stop/IO Scan mode. If this LED is OFF but OK is  
ON, the CPU is in Stop/No IO Scan mode.  
At powerup, the CPU by default automatically generates a configuration  
that includes all of the modules that are physically present in the  
system, starting at slot 1. Autoconfiguration stops at the first empty slot  
or faulted module.  
If RUN is flashing green and the Fault LED is ON, the  
Run/Stop switch was moved to Run position while a fatal  
fault existed.  
Switching the PLC Operating Mode ____________________  
FAULT  
ON if the CPU is in Stop/Faulted mode because a fatal fault  
has occurred. To turn off the Fault LED, clear both the I/O  
Fault Table and the PLC Fault Table. If this LED is blinking  
and the OK LED is OFF, a fatal fault has occurred during  
self-diagnostics. Please contact PLC Field Service.  
The CPU Run/Stop mode switch  
is located behind the module  
door. This switch can be used to  
RUN/ON  
place the CPU in Stop or Run  
mode. By default. Run/Stop mode  
STOP/OFF  
FORCE  
ON if an override is active on a bit reference.  
operation is enabled. The same  
switch can also be configured to  
prevent writing to program or  
configuration memory and forcing  
or overriding discrete data. It  
defaults to disabled memory  
protection.  
PORT 1 & 2 Blinking indicates activity on that port.  
Using the CPU Serial Ports __________________________  
The CPU’s two serial ports are software-configurable for SNP slave, RTU  
slave, or Serial I/O operation. If a port is being used for RTU, it automatically  
switches to SNP slave mode if necessary. Both ports’ default configuration  
is SNP slave mode. If configured for Serial I/O, a port automatically reverts  
to SNP slave when the CPU is in Stop mode.  
Run/Stop Mode Operation ____________________________  
Either port can be software-configured to set up communications between  
the CPU and various serial devices. An external device can obtain power  
from Port 2 if it requires 100mA or less at 5VDC.  
If Run/Stop mode switch operation is enabled, the switch can be used  
to place the CPU in Run mode.  
If the CPU has non-fatal faults and is not in Stop/Fault mode, placing  
the switch in Run position causes the CPU to go to Run mode. Faults  
are NOT cleared.  
Port 1 is an RS-232 port with a 9-pin female D-sub  
PORT 1  
connector. It is used as the boot loader port for  
upgrading the CPU firmware. The pinout of port 1  
If the CPU has fatal faults and is in Stop/Fault mode, placing the switch  
in Run position causes the Run LED to blink for 5 seconds. While the  
Run LED is blinking, the CPU switch can be used to clear the fault  
table and put the CPU in Run mode. After the switch has been in Run  
position for at least ½ second, move it to Stop position for at least ½  
second. Then move it back to Run position. The faults are cleared and  
the CPU goes to Run mode. The LED stops blinking and stays on.  
This can be repeated if necessary.  
1
5
allows a simple, straight-through cable to connect  
with a standard AT-style RS-232 port. Cable  
shielding attaches to the shell. Port 1 screw locks  
are threaded #4-40.  
Port 2 is an RS-485 port with a 15-pin female D-sub  
connector. This can be attached directly to an RS-  
485 to RS-232 adapter (IC690ACC901). Port 2  
screw locks are threaded (metric) M3x0.5).  
RS232  
PORT 2  
If the switch is not toggled, after 5 seconds the Run LED goes off and  
the CPU remains in Stop/Fault mode. Faults stay in the fault table.  
1
8
Cable Lengths and Baud Rates  
Maximum cable lengths (the total number of feet  
from the CPU to the last device) are:  
Port 1 (RS-232) = 15 meters (50 ft.)  
Port 2 (RS-485) = 1200 meters (4000 ft.)  
Both ports support configurable baud rates from  
4800 to 38.4k bps.  
RS485  
2
CPU Module  
March 1999  
GFK-1536C  
Pin Assignments for Port 2 __________________________  
Pin Assignments for Port 1 ___________________________  
Pin  
1
Signal  
SHLD  
Direction  
--  
Function  
Pin  
1
Signal  
n/c  
Direction  
Function  
Cable Shield Drain wire  
connection  
--  
2, 3, 4  
5
n/c  
--  
2
TXD  
RXD  
n/c  
Output  
Input  
Transmit Data output  
P5V  
Output  
+5.1VDC to power external level  
converters (100mA max.)  
3
Receive Data input  
4
--  
6
7
8
9
RTSA  
GND  
CTSB’  
RT  
Output  
--  
Request to Send (A) output  
0V/GND reference signal  
Clear to Send (B) input  
5
GND  
n/c  
--  
0V/GND signal reference  
6
--  
Input  
--  
7
CTS  
RTS  
n/c  
Input  
Clear to Send input  
Request to Send output  
--  
Resistor Termination (120 ohm)  
for RDA’  
8
Output  
9
10  
RDA’  
RDB’  
SDA  
Input  
Input  
Output  
Output  
Output  
Input  
--  
Receive Data (A) input  
Receive Data (B) input  
Transmit Data (A) output  
Transmit Data (B) output  
Request to Send (B) output  
Clear to Send (A) input  
Shell  
SHLD  
--  
Cable Shield wire connection / 100%  
(Continuous) shielding cable shield  
connection  
11  
12  
13  
SDB  
14  
RTSB  
CTSA’  
SHLD  
Cable Diagram for Attachment to a PC __________________  
15  
Shell  
Cable Shield wire connection /  
100% (Continuous) shielding  
cable shield connection  
PC 9-Pin  
Serial Port  
9-pin female  
(2) RXD  
(3) TXD  
(5) GND  
CPU  
Port 1  
1
2
3
1
2
3
9-pin male  
(2) TXD  
(3) RXD  
(5) GND  
(7) CTS  
(8) RTS  
6
7
8
9
6
7
8
9
See the PLC User’s Manual for cable diagrams.  
(7) RTS  
(8) CTS  
4
5
4
5
Connector and Cable Specifications for Port 2 ___________  
The shield must attach to shell of  
Vendor Part numbers below are provided for reference only. Any part that  
meets the same specification can be used.  
connectors on both ends of the cable.  
Cable:  
Belden  
8105  
Low Capacitance Computer cable, overall braid over foil  
shield  
5 Twisted-pairs †  
Connector and Cable Specifications for Port 1 ___________  
Shield Drain Wire †  
30 Volt / 80°C (176°F)  
Vendor Part numbers below are provided for reference only. Any part  
that meets the same specification can be used.  
24 AWG tinned copper, 7x32 stranding  
Velocity of Propagation = 78%  
Nominal Impedance = 100†  
Cable:  
Belden  
9610  
Computer cable, overall braid over foil shield  
5 conductor †  
30 Volt / 80°C (176°F)  
Type:  
Crimp  
Vendor:  
ITT/Cannon  
AMP  
Plug:  
Pin:  
030-2487-017  
66506-9  
15 Pin Male  
Connector:  
DAA15PK87F0  
205206-1  
ZDA15P  
24 AWG tinned copper, 7x32 stranding  
Solder  
ITT/Cannon  
AMP  
--  
--  
Vendor:  
ITT/Cannon  
AMP  
9 Pin Male  
Connector:  
Type:  
Crimp  
Plug:  
Pin:  
747908-2  
DEA9PK87F0  
205204-1  
ZDE9P  
030-2487-017  
Connector  
Shell:  
Kit*– ITT Cannon DA121073-50 [15-pin size backshell kit]:  
66506-9  
Metal-Plated Plastic (Plastic with Nickel over Copper) †  
Cable Grounding Clamp (included)  
40° cable exit design to maintain low-profile installation  
Solder  
ITT/Cannon  
AMP  
--  
--  
747904-2  
Plus – ITT Cannon 250-8501-009 [Extended Jackscrew]:  
Threaded with (metric) M3x0.5 for secure attachment †  
Order Qty 2 for each cable shell ordered  
Connector  
Shell:  
Kit* – ITT Cannon DE121073-54 [9-pin size backshell kit]:  
Metal-Plated Plastic (Plastic with Nickel over Copper) †  
Cable Grounding Clamp (included)  
40° cable exit design to maintain low-profile installation  
Plus – ITT Cannon 250-8501-010 [Extended Jackscrew]:  
Threaded with #4-40 for secure attachment to port †  
Order Qty 2 for each cable shell ordered  
*
Critical Information – any other part selected should meet or exceed this  
criteria.  
Use of this kit maintains the 70mm installed depth.  
*
Critical Information – any other part selected should meet or exceed  
this criteria.  
Use of this kit maintains the 70mm installed depth.  
3
CPU Module  
March 1999  
GFK-1536C  
Firmware Upgrades ______________________________  
Operating Notes/Restrictions _______________________  
CPU001 firmware resides in FLASH memory. This firmware may  
be upgraded via serial download from an appropriate personal  
computer to CPU serial port 1 (RS-232). Firmware upgrades  
through port 2 (RS-485) are not supported.  
1. If the input to a trigonometric function is either infinity or “not a  
number” (NaN), the output result is indeterminate.  
Avoid the use of infinity or not a number inputs.  
2. If large real exponent values are input to the Real Exponential function  
block, the output values are indeterminate.  
To determine the current version of firmware on an existing  
CPU001, connect a programmer to the CPU and look in the  
Status/Memory Information.  
3. When autoconfiguring a system at powerup, if multiple intelligent  
modules (modules other than basic I/O modules) are present in the  
system, some may not be configured. They are instead logged as extra  
modules.  
Upgrading CPU001-BA  
: Any CPU001 version BA may be  
upgraded to version BB.  
Upgrading CPU001-AA:  
Any CPU001-AA with a date code of  
Either clear the hardware configuration or store a valid  
configuration to resolve this problem.  
903 or greater may be upgraded to version BB without updating the  
hardware. (Date code is a 3-digit code found just below the Bar  
Code marking on the CPU module). AA models with date codes  
prior to 903 require a hardware modification; these units are not  
field upgradable to version BB.  
4. In rare instances, the CPU watchdog timer may expire if a booster  
power supply is power-cycled and the CPU power supply is not power  
cycled. This only occurs of there is an intelligent module that receives  
its power from a booster power supply. When the watchdog timer  
expires, it causes a CPU reset and fatal PLC fault.  
To upgrade the firmware of a CPU001 to Release 1.10 use  
Upgrade Kit #44A747796-G01.  
To avoid this problem, supply power to the CPU and associated  
booster power supplies from the same source.  
5. An END function must not be used within a subblock (subroutine).  
Execution of this function within a subblock causes a fatal CPU fault.  
Use of END function blocks should normally be reserved for program  
debug. If needed for this purpose, they may only be used within the  
main program.  
Problems Fixed  
1. The state of the Force LED on the CPU is maintained if the CPU is  
power-cycled.  
2. Hold Last State, if configured for input modules, is handled correctly if  
the module is “lost”.  
3. Fault Status bits %SC009-13 are updated when the CPU is powered  
up after having been powered down without a battery for a long time.  
Product Revision History ____________________________  
-AA  
-BA  
-BB  
Initial Product Release (Firmware Version 1.00)  
Updated Hardware to support Intelligent I/O modules  
Firmware Version 1.10  
4
CPU Module  
March 1999  
GFK-1536C  
Description  
Input/  
Output  
Choices  
The Drum Sequencer Function _____________________  
Please add the following information about the Drum Sequencer  
function to your copy of the PLC User’s Manual.  
The beginning reference address of the function's parameter  
block. The length of the Control Block is five words. A more  
complete description of what is contained within this block is  
listed below.  
Control  
Block  
R
Description of the Drum Sequencer Function  
The Drum Sequencer function is a special program instruction that  
operates like a mechanical drum sequencer.  
Value between 1 and 128 denoting the number of steps.  
Length  
OK  
CONST  
OK is energized if Enable is On and no error condition is  
detected. If Enable is Off this output will always be off.  
Flow, none  
The Drum Sequencer steps through a set of potential output bit  
patterns and selects one based on inputs to the function block. The  
selected value is copied to a group of 16 discrete output references.  
A word of memory containing the element of the Pattern  
Array that corresponds to the current ACTIVE STEP.  
OUT I,Q,M,T,G,  
R,AI,AQ  
DRUM  
Enable  
OK  
This optional bit reference is set whenever the function block  
is enabled and ACTIVE STEP is not equal to PRESET  
STEP.  
Drum I,Q,M,T,G,  
Control Block  
Coil  
none  
Step  
Reset  
Out  
Length  
Drum Coil  
This optional bit reference is set if the dwell time for the  
current step has expired.  
Dwell I,Q,M,T,G,  
Timeout none  
Pattern  
Dwell Timeout  
Timeout Fault  
First Follower  
Dwell Time  
Fault Timeout  
This optional bit reference will be set if the if the drum has  
been in a particular step longer than the step's specified  
FAULT TIMEOUT  
Timeout I,Q,M,T,G,  
Fault  
none  
This optional array of bits has one element for each step of  
the Drum Sequencer. No more than one bit in the array will  
be ON at any time and that bit will correspond to the value of  
ACTIVE STEP.  
First  
Follower  
I,Q,M,T,G,  
none  
Power flow to the Enable input causes the Drum Sequencer to copy the  
content of the selected reference pattern to the Out reference.  
Power flow to the Reset input or to the Step input selects the reference  
to be copied.  
Parameter Block for the DRUM SEQ Function  
The Control Block input is the beginning reference for the Drum  
Sequencer function’s parameter block, which includes various  
information necessary to use the function block.  
The parameter block (control block) for the Drum Sequencer function  
contains various information needed to operate the drum sequencer.  
Active Step  
Preset Step  
Step Control  
Timer Control  
Address  
Parameters of the DRUM SEQ Function  
Address + 1  
Description  
Input/  
Choices  
Address + 2  
Output  
Address + 3, Address + 4  
The Enable input controls execution of the function.  
Enable  
Step  
Flow  
Flow  
Active Step  
The active step value specifies the element of the  
The Step input can be used to go one step forward in the  
sequence. When the Enable input receives power flow and  
the Step input makes an off to on transition, the drum  
sequencer moves one step. . When Reset is active, the  
function ignores the step input.  
PATTERN array to copy to the OUT output memory location. This is used  
as the array index into the Pattern, Dwell Time, Fault Timeout, and First  
Follower arrays.  
Preset Step  
output when the RESET is ON.  
Step Control  
both the STEP input and the ENABLE input. The Step Control word is  
reserved for use by the function block, and must not be written to.  
A word input which is copied to the ACTIVE STEP  
The Reset input can be used to select a specific step in the  
sequence. When Enable and Reset both receive power flow,  
the function copies the Preset Step value in the Control  
Block to the Active Step reference, also in the Control Block.  
Then the function block copies the value in the Preset Step  
reference to the Out reference bits. When Reset is active,  
the function ignores the Step input.  
Reset  
Flow  
A word that is used to detect OFF to ON transitions on  
Timer Control  
Two words of data that hold values needed to run the  
timer. These values are reserved for use by the function block, and must  
not be written to.  
The starting address of an array of words, each representing  
one step of the Drum Sequencer. The value of each word  
represents the desired combination of outputs for a particular  
value of ACTIVE STEP. The number or elements in the  
array is equal to the Length input.  
Pattern R, AI, AQ  
Notes on Using the Drum Sequencer Function ________  
The Dwell Timeout Output Bit is cleared the first time the drum is in a  
new step. This is true:  
1.  
2.  
Whether the drum is introduced to a new step by changing the  
Active Step or by using the Step Input.  
This optional input array of words has one element for each  
element in the Pattern array. Each value in the array  
represents the dwell time for the corresponding step of the  
drum sequencer in .1 second units. When the dwell time  
expires for a given step the Dwell Timeout bit will be set.  
Dwell  
Time  
R, AI, AQ,  
none  
Regardless of the Dwell Time Array value associated with the  
step (even if it is 0).  
During the first sweep the Active Step is initialized.  
The Active and Preset Step of the Drum Sequencer's control block  
must be initialized for the Drum Sequencer to work or to pass power  
flow. Even if the Active Step is in the correct range(between 1 and  
length of the pattern array) and the Preset Step is not used, the drum  
will not function if the Preset Step is not in the proper range.  
If a Dwell Time is specified the drum can not sequence into  
its next step until the Dwell Time has expired.  
This optional input array of words has one element for each  
element in the Pattern array. Each value in the array  
represents the fault timeout for the corresponding step of the  
drum sequencer in .1 second units. When the fault timeout  
has expired the fault timeout bit will be set.  
Fault  
Timeout  
R, AI, AQ,  
none  
5

相关型号:

CPU144C

INVERTER TRANSFORMERS
SUMIDA

CPU165MF

IGBT SIP MODULE Fast IGBT
INFINEON

CPU165MFPBF

Insulated Gate Bipolar Transistor, 42A I(C), 600V V(BR)CES, N-Channel,
INFINEON

CPU165MK

IGBT SIP MODULE Short Circuit Rated UltraFast IGBT
INFINEON

CPU165MM

IGBT SIP MODULE Short Circuit Rated Fast IGBT
INFINEON

CPU165MMPBF

Insulated Gate Bipolar Transistor, 42A I(C), 600V V(BR)CES, N-Channel,
INFINEON

CPU165MU

IGBT SIP MODULE Ultra-Fast IGBT
INFINEON

CPU16RM

M68HC16 Family CPU16 Reference Manual
ETC

CPU32RM

CPU32 Reference Manual
ETC

CPU362MF

Insulated Gate Bipolar Transistor, 600V V(BR)CES, N-Channel
INFINEON

CPU362MU

Insulated Gate Bipolar Transistor, 600V V(BR)CES, N-Channel
INFINEON

CPU362MUPBF

Insulated Gate Bipolar Transistor, 600V V(BR)CES, N-Channel
INFINEON