FCX – AX SERIES
ABSOLUTE PRESSURE TRANSMITTER
...
FHA, FKA 3
DATA SHEET
The FCX – AX absolute pressure transmitter accurately
measures absolute pressure and transmits a proportional 4
to 20mA signal.
The transmitter utilizes a unique micromachined capaci-
tance silicon sensor with state-of-the-art microprocessor
tech-nology to provide exceptional performance and func-
tionality.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard fea-
ture for all AP models covering 1.6kPa{0.016bar} range
to 3000kPa{30bar} high pressure range. 0.1% accuracy
is available as option. Fuji's micro-capacitance silicon
sensor assures this accuracy for all suppressed calibra-
tion ranges without additional adjustment.
SPECIFICATIONS
2. Minimum environmental influence
Functional specifications
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
Type:
Model FHA: 4 to 20mA
Model FKA: 4 to 20mA with digital signal
3. Replaceable Communication Module
Service:
Liquid, gas, or vapour
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX – AX
transmitter very unique in design. In case of change in
communication protocol, all that needs to be done is just
to replace the module and the transmitter gets upgraded
to the new version.
Span, range, and overrange limit:
Span limit
[kPa abs] {bar abs}
Overrange
limit
[MPa]
{bar}
Range limit
[kPa abs]
{bar abs}
Type
Max.
Min.
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both Fuji
proprietary protocol and HART. Any HART compatible
devices can communicate with FCX – AX series transmitters.
5. Application flexibility
FHA
1.6
{0.016}
13
{0.13}
50
{0.5}
300
{3}
FKA
1.6
{0.016}
1.6
{0.016}
5
{0.05}
30
FHA/FKA
F
F
F
F
A
A
A
A
01
02
03
04
16
0 to +16
0.5
{5}
0.5
{5}
1.5
{15}
9
{0.16}
130
{1.3}
500
{5}
{0 to +0.16}
0 to +130
{0 to +1.3}
0 to +500
{0 to +5}
Various options that render the FCX – AX suitable for
almost any process applications include:
3000
{30}
0 to +3000
{0 to +30}
{0.3}
{90}
—
Analog indicator at either the electronics side or ter-
minal side
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
—
—
—
—
—
Full range of hazardous area approvals
Built-in RFI filter and lightning arrester
4 12 -digits LCD meter
Stainless steel electronics housing
Wide selection of materials
—
The maximum span of each sensor can be converted to
different units using factors as below.
1MPa abs=103kPa abs=10bar abs=10.19716kgf/cm2 abs
=145.0377psi abs
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
1kPa abs=10mbar abs=101.9716mmH2O abs=
4.01463inH2O abs=7.50062mmHg abs
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
Output signal:
Model FHA: 4 to 20mA DC 2-wire
Model FKA: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with op-
tional arrester.
EDSX5-71
Date Mar. 15, 1999
...
FHA, FKA 3
Load limitations: see figure below
[Ω]
“Output Overscale”:
Approx. 21.6mA
(Adjustable within the range 20.8mA to
21.6mA from HHC)
2000
“Output Underscale”:
1533Ω
Approx. 3.8mA
(Adjustable within the range 3.2mA to
3.8mA from HHC)
1500
1000
600Ω
4
3.8
20 20.8
3.2
Operating
area
24V
500
250
Over scale
Burnout
45V
50
0
21.6
Normal operating range
Probable under range
Under scale
Burnout
10 16.1
10.5V
Probable over range
[ V ]
Power voltage
Loop-check output:
Note: For communication with HHC (Model: FXW), min. of 250Ω is required.
Model FHA: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKA: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA
by HHC.
Hazardous locations: (Approval pending)
Type N
Nonincendive
Authorities
Flameproof
Intrinsic safety
BASEEFA
Factory
Mutual
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G Groups A thru. F
Class I II III
Div. 1
EEx ia IIC T4, T5
Class I II III
Div. 1
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Temperature limit: Ambient: –40 to +85°C
(–20 to +80°C for LCD indicator)
(–40 to +60°C for arrester option)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified by
each standard.
CSA
Class I II III
Div. 1
Groups C thru. G Groups A thru. G Groups A thru. G
RIIS
SAA
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP 66/67
—
—
Ex n II C T5, T6
IP 66/67
Ex ia II C T5, T6
IP 66/67
Process: – 40 to +85°C for silicone fill
sensor
Storage: – 40 to +90°C
Zero/span adjustment:
Model FHA: Zero is adjustable from the external
adjustment screw.
Humidity limit: O to 100% RH
Communication: (Model FKA only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following informa-
tion can be remotely displayed or recon-
figured.
The adjustment screw can also function
to adjust span when MODE SWITCH
(located on the electronics unit) is in the
span mode. INHIBIT mode to disable the
adjustment screw is also available.
Model FKA: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Adjustable electrical damping
Model FHA: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Items
Display
Set
Tag No.
Model No.
v
v
v
v
Damping:
Serial No.
Engineering unit
v
v
—
v
Range limit
Measuring range
Damping
v
v
v
—
v
v
Model FKA: The time constant is adjustable between
0 to 38.4 seconds. (9 steps)
Output mode
Burnout direction
Adjustment
Output adjust
Data
Self diagnoses
Printer
v
v
v
—
v
v
—
v
v
v
v
v
—
—
—
v
Zero elevation/suppression:
Zero can be elevated within the specified
range limit of each sensor model.
Normal/reverse action:
Model FHA: Selectable by moving a jumper pin located
on the electronics unit.
External switch lock
Transmitter display(*)
v
v
Model FKA: Configurable from HHC.
Indication:
Note: (*) HHC's version must be more than 5.0 (or
Analog indicator or 4 21 -digit LCD meter,
as specified.
FXW
1– 2), to use this function.
Burnout direction:If self-diagnostic detect transmitter fail-
ure, the analog signal will be driven to ei-
ther “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
Model FHA: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
Performance specifications
Accuracy rating: (including linearity, hysteresis, and re-
peatability).
(Standard)
(Output signal just before failure happens
is maintained.)
Model FKA: Selectable from HHC
“Output Hold”:
For spans greater than 1/10 of URL: ±0.2% of span
For spans below 1/10 of URL (Model FKA only):
0.1 x URL
± (0.1 + 0.1
)% of span
Output signal is hold as the value just be-
fore failure happens.
Span
2
(Option)
Non-wetted parts material:
Electronics housing: Low copper die-cast
(Not available for Max span 16kPa abs, 130kPa abs)
For spans greater than 1/10 of URL: ±0.1% of span
For spans below 1/10 of URL (Model FKA only):
0.1 x URL
aluminum alloy (standard), finished
with polyester coating, or 316 stainless
steel (SCS14 per JIS G5121), as
specified.
± (0.05 + 0.05
)% of span
Span
0.1% of calibrated span
Bolts and nut: Cr-Mo alloy (standard) or
304 stainless steel
Linearity:
Stability:
±0.2% of upper range limit (URL) for 24
Fill fluid: Silicone oil
months
Mounting bracket: Carbon steel with
epoxy coating or 304 stainless steel,
as specified
Temperature effect:
Effect per 28°C change between the
limits of – 40°C and +85°C
Environmental protection:
URL
Span
URL
Zero shift: ±(0.125+0.1
Total effect: ±(0.15+0.1
)%
)%
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A) pipe using mounting
bracket, direct wall mounting, or direct
process mounting.
Span
Double the effects for material code (7th
digit in code symbols) "H", "M", and "T".
Mass{weight}:
Transmitter approximately 3.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
Overrange effect: Zero shift; 0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequen-
cies of 20 to 1000MHz and field strength
30V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Optional features
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compart-
ment or in the terminal box of the housing.
An optional 4 21 digits LCD meter is also
available.
Step response: Time constant. 0.2 s
Dead time: approximately 0.3 s
(without electrical damping)
Mounting position effect:
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Zero shift, less than 0.1kPa{1mbar} for a
10° tilt in any plane.
Lightning surge immunity:
4KV (1.2 × 50µs)
No effect on span. This error can be cor-
rected by adjusting zero.
Dielectric strength:
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for
use on oxygen or chlorine measurement.
500V AC, 50/60Hz 1 min., between circuit
and earth.
NACE specification:
Metallic materials for all pressure bound-
Insulation resistance:
ary parts comply with NACE MR-01-75.
304 stainless steel bolts and nuts, ASTM
B7M or L7M bolts and 2HM nuts (Class
II) are available.
More than 100MΩ at 500V DC.
Turn-on time:
4 sec
Internal resistance for external field indicator:
12Ω or less
Customer tag:
A stainless steel tag for customer tag data
is wired to the transmitter.
Physical specifications
Coating of cell: Cell's surface is finished with epoxy/
polyurethane double coating. Specify if
Electrical connections:
environment is extremely corrosive.
G1/2, 1/2-14NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4, as specified.
Process-wetted parts material:
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Material
code
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Wetted
Process cover
(7th digit
in "Code
symbols")
Diaphragm
Vent/drain
sensor body
Hand held communicator:
(Model FXW, refer to Data Sheet No.EDS
316
V
H
M
T
316
stainless steel
316
316L
stainless steel
Hastelloy-C
316
stainless steel
316
stainless steel
Hastelloy-C
lining
8-47)
stainless steel
stainless steel
Communication module: (Standard for model FKA)
By adding communication module,
remote setting function becomes avail-
Monel lining
316
stainless steel
316
Monel
316
stainless steel
316
Tantalum
lining
Tantalum
stainless steel
stainless steel
able for FHA.
Remark: When the communication module is
connected, the operation mode of ex-
ternal zero/span adjustment screw is
limited to zero adjustment only.
Notes: Sensor O-rings: Viton
Availability of above material design depends on
ranges.
Refer to "Code symbols".
3
...
FHA, FKA 3
CODE SYMBOLS
1
2
3
4
5
6
7
8
9
10 11 12 13
14 15
Description
0
3
Type
FHA
FKA
4 to 20mA, Output type
4 to 20mA with digital signal, Output type
Connections
Process
connection
Oval flange
screw
Conduit
connection
S
T
V
W
X
Rc1/4
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
G 1/2
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/2-14NPT
Pg 13.5
M20 × 1.5
Pg 13.5
Span limit
Span limit FHA/FKA
[kPa abs]{bar abs}(*)
Process cover
Diaphragm
Wetted cell body
1.6/1.6…16/16
{0.016/0.016…0.16/0.16
316 stainless steel
316 stainless steel
316 stainless steel
316L stainless steel 316 stainless steel
1V
1H
1M
Hast. C
Monel
Hast. C lining
Monel lining
13/1.6…130/130
{0.13/0.016…1.3/1.3}
2V
2H
2M
2T
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316L stainless steel 316 stainless steel
Hast. C
Monel
Hast. C lining
Monel lining
Tantalum
Tantalum lining
50/5…500/500
{0.5/0.05…5/5}
3V
3H
3M
3T
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316L stainlesssteel
Hast. C
Monel
316 stainless steel
Hast. C lining
Monel lining
Tantalum
Tantalum lining
300/30…3000/3000
{3/0.3…30/30}
4V
4H
4M
4T
316stainless steel
316stainless steel
316 stainless steel
316 stainless steel
316L stainless steel 316 stainless steel
Hast. C
Monel
Hast. C lining
Monel lining
Tantalum
Tantalum lining
Note: * 100: 1 turn down is possible for model FKA, but should be used at a span greater
than 1/40 of the maximum span for better performance.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :-
EMI (Emission)
EN50081-1 : 1992
Test item
Frequency range
Basic standard
Applicable Electro-
magnetic Radiation
Disturbance
EN55022
Class B
30-1000MHz
EMS (Immunity) EN50082-1 : 1992
Test
specification
Basic
standard
Performance
criteria
No. Test item
Electrostatic
discharge
1
8kV (Air)
IEC 801-2:1984
IEC 801-3:1984
B
A
Radio-frequency 27-500MHz
electromagnetic 3V/m
field.
2
3
(Unmodulated)
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
Fast transients
common mode
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
4
1
2
3
4
5
6
7
8
9
10 11 12 13
14 15
F H A
F K A
0
3
0
3
Description
Indicator and arrester
Indicator
Arrester
A
B
D
J
None
None
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
None
None
None
None (JIS and SI unit)
E
F
Yes
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100%
Digital, custom scale
Yes
H
K
L
Yes
Yes (JIS and SI unit)
None
P
Q
S
None (Model FKA only)
Yes
Yes (Model FKA only)
Approvals for hazardous locations (Approval pending)
A
B
C
D
E
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
(Available for 4th digit code “S“)
JIS, Flameproof (Cable gland seal)
FM, Flameproof (or explosionproof)
(Available for 4th digit code “S“)
(Available for 4th digit code “T“)
CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“)
BASEEFA, Flameproof (Conduit seal)
M
N
H
J
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
K
CENELEC, Intrinsic safety
P
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit code “S,T,W)
SAA Intrinsic safety(Available for 4th digit code “S,T,W)
SAA Type– N(non-sparking)(Available for 4th digit code “S,T,W)
R
T
Q
Side vent/ drain and mounting bracket
Side vent/drain
None
Mounting bracket
None
A
B
C
D
E
F
None
Yes, carbon steel
Yes, stainless steel
None
None
Yes
Yes
Yes, carbon steel
Yes, stainless steel
Yes
Stainless steel parts
Stainless steel tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
None
Yes
Y
B
C
E
None
Yes
None
None
Yes
None
Yes
Yes
M
N
P
None
Yes
None
None
Yes
Yes
None
Yes
Yes
Q
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
Y
G
N
None (standard)
Silicone oil
Silicone oil
Degreasing
NACE specification
Silicone oil (7th digit code "T" and 15th digit code
"A", "B" are not available)
Sensor O-ring
A
Viton
Bolt/nut
A
B
C
D
E
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel/304 stainless steel (*1)
* (1) In case of tropical use, select stainless bolts and nuts.
5
...
FHA, FKA 3
OUTLINE DIAGRAM (Unit:mm)
Vent/drain plug
(When the vent/drain plug attatched on
the upper side of the detector)
Fastener
(In case of 10th
digit code “B,C,M,N“)
Zero/span ADJ. screw
In case of 4th
digit code
“S,V,W,X“
Mtg. Pipe
“A“
Press. conn.
JIS 50A (2")
Up
Down
38
58
“B“
U - Bolt M8
Conduit conn.
30
With field ind.
(option)
224
Vent/drain plug
4 Holes
9 dia.
Cable gland (option)
see note
51
71
(27)
Earth terminal
(both side )
see table1
“C“
Conduit conn.
Detail “A“
DETAIL “B“
Detail “C“
(press conn.)
(Conduit conn.)
ø18.5
H
ø13
ø
15
Oval flange
screw
see table1 1
Side vent
(option)
ø7
2-M8 × 12
G 1/2
D
See table 1
see table 1
27
70
50
Oval flange
screw
Conduit conn.
Press. conn.
H
F
Earth
terminal
4th digit
code
D
120
E
7/16-20UNF
Screw depth13
7/16-20UNF
Screw depth13
M10
Screw depth13
7M10
Screw depth13
7/16-20UNF
Screw depth13
S
T
V
G1/2
1/2
–14NPT
17
Rc1/4
M4
8
16
8
1/4–18NPT
No. 8-32UNC
M4
5
CONNECTION
DIAGRAM
Pg13.5
4.5 1/4–18NPT
–
+
CK+ CK–
16
8
5
W
X
M20 × 1.5
1/4–18NPT
M4
M4
Pg13.5
4.5 1/4–18NPT
Table 1
+
–
S
V
Note1) : Cable gland is supplied in case of flamproof packing type.
ø11 cable is suitable.
T
H
K
H
A
F
0
3
V
W
X
M
T
Head office
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Fax: 81-42-585-6187, 6189
Printed in Japan
Information in this catalog is subject to change without notice.