FCX – AX SERIES  
ABSOLUTE PRESSURE TRANSMITTER  
...  
FHA, FKA 3  
DATA SHEET  
The FCX – AX absolute pressure transmitter accurately  
measures absolute pressure and transmits a proportional 4  
to 20mA signal.  
The transmitter utilizes a unique micromachined capaci-  
tance silicon sensor with state-of-the-art microprocessor  
tech-nology to provide exceptional performance and func-  
tionality.  
FEATURES  
1. High accuracy  
0.2% accuracy for all calibrated spans is a standard fea-  
ture for all AP models covering 1.6kPa{0.016bar} range  
to 3000kPa{30bar} high pressure range. 0.1% accuracy  
is available as option. Fuji's micro-capacitance silicon  
sensor assures this accuracy for all suppressed calibra-  
tion ranges without additional adjustment.  
SPECIFICATIONS  
2. Minimum environmental influence  
Functional specifications  
The "Advanced Floating Cell" design which protects the  
pressure sensor against changes in temperature, and  
overpressure substantially reduces total measurement  
error in actual field applications.  
Type:  
Model FHA: 4 to 20mA  
Model FKA: 4 to 20mA with digital signal  
3. Replaceable Communication Module  
Service:  
Liquid, gas, or vapour  
Fuji micro-electronics manufacturing technology offers  
replaceable communication module that makes FCX – AX  
transmitter very unique in design. In case of change in  
communication protocol, all that needs to be done is just  
to replace the module and the transmitter gets upgraded  
to the new version.  
Span, range, and overrange limit:  
Span limit  
[kPa abs] {bar abs}  
Overrange  
limit  
[MPa]  
{bar}  
Range limit  
[kPa abs]  
{bar abs}  
Type  
Max.  
Min.  
4. Fuji/HART bilingual communication module  
The communication module is "bilingual" to speak both Fuji  
proprietary protocol and HART. Any HART compatible  
devices can communicate with FCX – AX series transmitters.  
5. Application flexibility  
FHA  
1.6  
{0.016}  
13  
{0.13}  
50  
{0.5}  
300  
{3}  
FKA  
1.6  
{0.016}  
1.6  
{0.016}  
5
{0.05}  
30  
FHA/FKA  
F
F
F
F
A
A
A
A
01  
02  
03  
04  
16  
0 to +16  
0.5  
{5}  
0.5  
{5}  
1.5  
{15}  
9
{0.16}  
130  
{1.3}  
500  
{5}  
{0 to +0.16}  
0 to +130  
{0 to +1.3}  
0 to +500  
{0 to +5}  
Various options that render the FCX – AX suitable for  
almost any process applications include:  
3000  
{30}  
0 to +3000  
{0 to +30}  
{0.3}  
{90}  
Analog indicator at either the electronics side or ter-  
minal side  
Remark: To minimize environmental influence, span should be greater  
than 1/40 of the max. span in most applications.  
Full range of hazardous area approvals  
Built-in RFI filter and lightning arrester  
4 12 -digits LCD meter  
Stainless steel electronics housing  
Wide selection of materials  
The maximum span of each sensor can be converted to  
different units using factors as below.  
1MPa abs=103kPa abs=10bar abs=10.19716kgf/cm2 abs  
=145.0377psi abs  
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,  
Over Scale: 20.8 to 21.6mA)  
1kPa abs=10mbar abs=101.9716mmH2O abs=  
4.01463inH2O abs=7.50062mmHg abs  
Burnout signal level is adjustable using Model FXW hand  
Held Communicator (HHC) to comply with NAMUR NE43.  
(Available for amplifier unit from version 24 and FXW(HHC) version  
5.3.)  
Output signal:  
Model FHA: 4 to 20mA DC 2-wire  
Model FKA: 4 to 20mA DC with digital signal super-  
imposed on the 4 to 20mA signal.  
7. Dry calibration without reference pressure  
Thanks to the best combination of unique construction  
of mechanical parts (Sensor unit) and high performance  
electronics circuit (Electronics unit), reliability of dry  
calibration without reference pressure is at equal level  
as wet calibration.  
Power supply:  
Transmitter operates on 10.5V to 45V DC  
at transmitter terminals.  
10.5V to 32V DC for the units with op-  
tional arrester.  
EDSX5-71  
Date Mar. 15, 1999  
...  
FHA, FKA 3  
Load limitations: see figure below  
[]  
“Output Overscale”:  
Approx. 21.6mA  
(Adjustable within the range 20.8mA to  
21.6mA from HHC)  
2000  
“Output Underscale”:  
1533Ω  
Approx. 3.8mA  
(Adjustable within the range 3.2mA to  
3.8mA from HHC)  
1500  
1000  
600Ω  
4
3.8  
20 20.8  
3.2  
Operating  
area  
24V  
500  
250  
Over scale  
Burnout  
45V  
50  
0
21.6  
Normal operating range  
Probable under range  
Under scale  
Burnout  
10 16.1  
10.5V  
Probable over range  
[ V ]  
Power voltage  
Loop-check output:  
Note: For communication with HHC (Model: FXW), min. of 250is required.  
Model FHA: Transmitter can output constant signal of  
4mA, 12mA, or 20mA if MODE SWITCH  
is set to the loop check mode.  
Model FKA: Transmitter can be configured to provide  
constant signal 3.8mA through 21.6mA  
by HHC.  
Hazardous locations: (Approval pending)  
Type N  
Nonincendive  
Authorities  
Flameproof  
Intrinsic safety  
BASEEFA  
Factory  
Mutual  
Ex ds IIC T5, T6  
Class I II III  
Div. 1  
Groups B thru. G Groups A thru. F  
Class I II III  
Div. 1  
EEx ia IIC T4, T5  
Class I II III  
Div. 1  
Ex N II T5  
Class I II III  
Div. 2  
Groups A thru. G  
Class I II III  
Div. 2  
Temperature limit: Ambient: –40 to +85°C  
(–20 to +80°C for LCD indicator)  
(–40 to +60°C for arrester option)  
For explosionproof units (flameproof or  
intrinsic safety), ambient temperature  
must be within the limits specified by  
each standard.  
CSA  
Class I II III  
Div. 1  
Groups C thru. G Groups A thru. G Groups A thru. G  
RIIS  
SAA  
Ex ds IIB+H2 T4  
Ex d II C T5, T6  
IP 66/67  
Ex n II C T5, T6  
IP 66/67  
Ex ia II C T5, T6  
IP 66/67  
Process: – 40 to +85°C for silicone fill  
sensor  
Storage: – 40 to +90°C  
Zero/span adjustment:  
Model FHA: Zero is adjustable from the external  
adjustment screw.  
Humidity limit: O to 100% RH  
Communication: (Model FKA only)  
With HHC (Model FXW, consult Data  
Sheet No. EDS8-47), following informa-  
tion can be remotely displayed or recon-  
figured.  
The adjustment screw can also function  
to adjust span when MODE SWITCH  
(located on the electronics unit) is in the  
span mode. INHIBIT mode to disable the  
adjustment screw is also available.  
Model FKA: Zero and span are adjustable from the  
HHC. Zero is also adjustable externally  
from the adjustment screw.  
Adjustable electrical damping  
Model FHA: The time constant is adjustable to 0, 0.3,  
1.2, 4.8, or 19.2 seconds.  
Items  
Display  
Set  
Tag No.  
Model No.  
v
v
v
v
Damping:  
Serial No.  
Engineering unit  
v
v
v
Range limit  
Measuring range  
Damping  
v
v
v
v
v
Model FKA: The time constant is adjustable between  
0 to 38.4 seconds. (9 steps)  
Output mode  
Burnout direction  
Adjustment  
Output adjust  
Data  
Self diagnoses  
Printer  
v
v
v
v
v
v
v
v
v
v
v
Zero elevation/suppression:  
Zero can be elevated within the specified  
range limit of each sensor model.  
Normal/reverse action:  
Model FHA: Selectable by moving a jumper pin located  
on the electronics unit.  
External switch lock  
Transmitter display(*)  
v
v
Model FKA: Configurable from HHC.  
Indication:  
Note: (*) HHC's version must be more than 5.0 (or  
Analog indicator or 4 21 -digit LCD meter,  
as specified.  
FXW  
1– 2), to use this function.  
Burnout direction:If self-diagnostic detect transmitter fail-  
ure, the analog signal will be driven to ei-  
ther “Output Hold”, “Output Overscale”  
or “Output Underscale” modes.  
Model FHA: Unless otherwise specified in the order,  
the transmitter will be shipped in “Output  
Hold” mode.  
Performance specifications  
Accuracy rating: (including linearity, hysteresis, and re-  
peatability).  
(Standard)  
(Output signal just before failure happens  
is maintained.)  
Model FKA: Selectable from HHC  
“Output Hold”:  
For spans greater than 1/10 of URL: ±0.2% of span  
For spans below 1/10 of URL (Model FKA only):  
0.1 x URL  
± (0.1 + 0.1  
)% of span  
Output signal is hold as the value just be-  
fore failure happens.  
Span  
2
(Option)  
Non-wetted parts material:  
Electronics housing: Low copper die-cast  
(Not available for Max span 16kPa abs, 130kPa abs)  
For spans greater than 1/10 of URL: ±0.1% of span  
For spans below 1/10 of URL (Model FKA only):  
0.1 x URL  
aluminum alloy (standard), finished  
with polyester coating, or 316 stainless  
steel (SCS14 per JIS G5121), as  
specified.  
± (0.05 + 0.05  
)% of span  
Span  
0.1% of calibrated span  
Bolts and nut: Cr-Mo alloy (standard) or  
304 stainless steel  
Linearity:  
Stability:  
±0.2% of upper range limit (URL) for 24  
Fill fluid: Silicone oil  
months  
Mounting bracket: Carbon steel with  
epoxy coating or 304 stainless steel,  
as specified  
Temperature effect:  
Effect per 28°C change between the  
limits of – 40°C and +85°C  
Environmental protection:  
URL  
Span  
URL  
Zero shift: ±(0.125+0.1  
Total effect: ±(0.15+0.1  
)%  
)%  
IEC IP67 and NEMA 4X  
Mounting:  
On 60.5mm (JIS 50A) pipe using mounting  
bracket, direct wall mounting, or direct  
process mounting.  
Span  
Double the effects for material code (7th  
digit in code symbols) "H", "M", and "T".  
Mass{weight}:  
Transmitter approximately 3.4kg without  
options.  
Add; 0.5kg for mounting bracket  
0.8kg for indicator option  
4.5kg for stainless steel housing  
option  
Overrange effect: Zero shift; 0.2% of URL for any overrange  
to maximum limit  
Supply voltage effect:  
Less than 0.05% of calibrated span per  
10V  
RFI effect:  
Less than 0.2% of URL for the frequen-  
cies of 20 to 1000MHz and field strength  
30V/m when electronics covers on.  
(Classification: 2-abc: 0.2% span per  
SAMA PMC 33.1)  
Optional features  
Indicator:  
A plug-in analog indicator (1.5% accuracy)  
can be housed in the electronics compart-  
ment or in the terminal box of the housing.  
An optional 4 21 digits LCD meter is also  
available.  
Step response: Time constant. 0.2 s  
Dead time: approximately 0.3 s  
(without electrical damping)  
Mounting position effect:  
Arrester:  
A built-in arrester protects the electronics  
from lightning surges.  
Zero shift, less than 0.1kPa{1mbar} for a  
10° tilt in any plane.  
Lightning surge immunity:  
4KV (1.2 × 50µs)  
No effect on span. This error can be cor-  
rected by adjusting zero.  
Dielectric strength:  
Degreasing:  
Process-wetted parts are cleaned, but the  
fill fluid is standard silicone oil. Not for  
use on oxygen or chlorine measurement.  
500V AC, 50/60Hz 1 min., between circuit  
and earth.  
NACE specification:  
Metallic materials for all pressure bound-  
Insulation resistance:  
ary parts comply with NACE MR-01-75.  
304 stainless steel bolts and nuts, ASTM  
B7M or L7M bolts and 2HM nuts (Class  
II) are available.  
More than 100Mat 500V DC.  
Turn-on time:  
4 sec  
Internal resistance for external field indicator:  
12or less  
Customer tag:  
A stainless steel tag for customer tag data  
is wired to the transmitter.  
Physical specifications  
Coating of cell: Cell's surface is finished with epoxy/  
polyurethane double coating. Specify if  
Electrical connections:  
environment is extremely corrosive.  
G1/2, 1/2-14NPT, Pg13.5, or M20 x 1.5  
conduit, as specified.  
Process connections:  
1/4-18 NPT or Rc1/4, as specified.  
Process-wetted parts material:  
ACCESSORIES  
Oval flanges:  
(Model FFP, refer to Data Sheet No.  
EDS6-10)  
Material  
code  
Converts process connection to 1/2-14  
NPT or to Rc1/2; in carbon steel or in 316  
stainless steel.  
Wetted  
Process cover  
(7th digit  
in "Code  
symbols")  
Diaphragm  
Vent/drain  
sensor body  
Hand held communicator:  
(Model FXW, refer to Data Sheet No.EDS  
316  
V
H
M
T
316  
stainless steel  
316  
316L  
stainless steel  
Hastelloy-C  
316  
stainless steel  
316  
stainless steel  
Hastelloy-C  
lining  
8-47)  
stainless steel  
stainless steel  
Communication module: (Standard for model FKA)  
By adding communication module,  
remote setting function becomes avail-  
Monel lining  
316  
stainless steel  
316  
Monel  
316  
stainless steel  
316  
Tantalum  
lining  
Tantalum  
stainless steel  
stainless steel  
able for FHA.  
Remark: When the communication module is  
connected, the operation mode of ex-  
ternal zero/span adjustment screw is  
limited to zero adjustment only.  
Notes: Sensor O-rings: Viton  
Availability of above material design depends on  
ranges.  
Refer to "Code symbols".  
3
...  
FHA, FKA 3  
CODE SYMBOLS  
1
2
3
4
5
6
7
8
9
10 11 12 13  
14 15  
Description  
0
3
Type  
FHA  
FKA  
4 to 20mA, Output type  
4 to 20mA with digital signal, Output type  
Connections  
Process  
connection  
Oval flange  
screw  
Conduit  
connection  
S
T
V
W
X
Rc1/4  
7/16-20UNF  
7/16-20UNF  
M10  
M10  
7/16-20UNF  
G 1/2  
1/4-18NPT  
1/4-18NPT  
1/4-18NPT  
1/4-18NPT  
1/2-14NPT  
Pg 13.5  
M20 × 1.5  
Pg 13.5  
Span limit  
Span limit FHA/FKA  
[kPa abs]{bar abs}(*)  
Process cover  
Diaphragm  
Wetted cell body  
1.6/1.6…16/16  
{0.016/0.016…0.16/0.16  
316 stainless steel  
316 stainless steel  
316 stainless steel  
316L stainless steel 316 stainless steel  
1V  
1H  
1M  
Hast. C  
Monel  
Hast. C lining  
Monel lining  
13/1.6…130/130  
{0.13/0.016…1.3/1.3}  
2V  
2H  
2M  
2T  
316 stainless steel  
316 stainless steel  
316 stainless steel  
316 stainless steel  
316L stainless steel 316 stainless steel  
Hast. C  
Monel  
Hast. C lining  
Monel lining  
Tantalum  
Tantalum lining  
50/5…500/500  
{0.5/0.05…5/5}  
3V  
3H  
3M  
3T  
316 stainless steel  
316 stainless steel  
316 stainless steel  
316 stainless steel  
316L stainlesssteel  
Hast. C  
Monel  
316 stainless steel  
Hast. C lining  
Monel lining  
Tantalum  
Tantalum lining  
300/30…3000/3000  
{3/0.3…30/30}  
4V  
4H  
4M  
4T  
316stainless steel  
316stainless steel  
316 stainless steel  
316 stainless steel  
316L stainless steel 316 stainless steel  
Hast. C  
Monel  
Hast. C lining  
Monel lining  
Tantalum  
Tantalum lining  
Note: * 100: 1 turn down is possible for model FKA, but should be used at a span greater  
than 1/40 of the maximum span for better performance.  
The product conforms to the requirements of the  
Electromagnetic compatibility Directive 89/336/EEC as  
detailed within the technical construction file number  
TN510412. The applicable standards used to demonstrate  
compliance are :-  
EMI (Emission)  
EN50081-1 : 1992  
Test item  
Frequency range  
Basic standard  
Applicable Electro-  
magnetic Radiation  
Disturbance  
EN55022  
Class B  
30-1000MHz  
EMS (Immunity) EN50082-1 : 1992  
Test  
specification  
Basic  
standard  
Performance  
criteria  
No. Test item  
Electrostatic  
discharge  
1
8kV (Air)  
IEC 801-2:1984  
IEC 801-3:1984  
B
A
Radio-frequency 27-500MHz  
electromagnetic 3V/m  
field.  
2
3
(Unmodulated)  
0.5kV, 5/50  
(Tr/Th) ns  
5kHz Rep.  
Fast transients  
common mode  
IEC 801-4:1988  
B
"LVD - The transmitter is not covered by the requirements  
of the LVD standard."  
4
1
2
3
4
5
6
7
8
9
10 11 12 13  
14 15  
F H A  
F K A  
0
3
0
3
Description  
Indicator and arrester  
Indicator  
Arrester  
A
B
D
J
None  
None  
Analog, 0 to 100% linear scale  
Analog, custom scale  
Analog, double scale  
None  
None  
None  
None (JIS and SI unit)  
E
F
Yes  
Analog, 0 to 100% linear scale  
Analog, custom scale  
Analog, double scale  
Digital, 0 to 100%  
Digital, custom scale  
Digital, 0 to 100%  
Digital, custom scale  
Yes  
H
K
L
Yes  
Yes (JIS and SI unit)  
None  
P
Q
S
None (Model FKA only)  
Yes  
Yes (Model FKA only)  
Approvals for hazardous locations (Approval pending)  
A
B
C
D
E
None (for ordinary locations)  
JIS, Flameproof (Conduit seal)  
(Available for 4th digit code “S“)  
JIS, Flameproof (Cable gland seal)  
FM, Flameproof (or explosionproof)  
(Available for 4th digit code “S“)  
(Available for 4th digit code “T“)  
CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“)  
BASEEFA, Flameproof (Conduit seal)  
M
N
H
J
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)  
FM, Intrinsic safety and nonincendive  
CSA, Intrinsic safety and nonincendive  
K
CENELEC, Intrinsic safety  
P
CENELEC, Intrinsic safety and BASEEFA, Type N  
SAA Flameproof (Conduit seal)(Available for 4th digit code “S,T,W)  
SAA Intrinsic safety(Available for 4th digit code “S,T,W)  
SAA Type– N(non-sparking)(Available for 4th digit code “S,T,W)  
R
T
Q
Side vent/ drain and mounting bracket  
Side vent/drain  
None  
Mounting bracket  
None  
A
B
C
D
E
F
None  
Yes, carbon steel  
Yes, stainless steel  
None  
None  
Yes  
Yes  
Yes, carbon steel  
Yes, stainless steel  
Yes  
Stainless steel parts  
Stainless steel tag plate  
Stainless steel elec. housing  
Coating of cell  
None  
None  
None  
None  
Yes  
Y
B
C
E
None  
Yes  
None  
None  
Yes  
None  
Yes  
Yes  
M
N
P
None  
Yes  
None  
None  
Yes  
Yes  
None  
Yes  
Yes  
Q
Yes  
Yes  
Special applications and fill fluid  
Treatment  
Fill fluid  
Y
G
N
None (standard)  
Silicone oil  
Silicone oil  
Degreasing  
NACE specification  
Silicone oil (7th digit code "T" and 15th digit code  
"A", "B" are not available)  
Sensor O-ring  
A
Viton  
Bolt/nut  
A
B
C
D
E
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut  
Cr-Mo alloy hexagon bolt/nut  
NACE bolt/nut (ASTM A193 B7M/A194 2HM)  
NACE bolt/nut (ASTM A320 L7M/A194 2HM)  
304 stainless steel/304 stainless steel (*1)  
* (1) In case of tropical use, select stainless bolts and nuts.  
5
...  
FHA, FKA 3  
OUTLINE DIAGRAM (Unit:mm)  
Vent/drain plug  
(When the vent/drain plug attatched on  
the upper side of the detector)  
Fastener  
(In case of 10th  
digit code “B,C,M,N“)  
Zero/span ADJ. screw  
In case of 4th  
digit code  
“S,V,W,X“  
Mtg. Pipe  
“A“  
Press. conn.  
JIS 50A (2")  
Up  
Down  
38  
58  
“B“  
U - Bolt M8  
Conduit conn.  
30  
With field ind.  
(option)  
224  
Vent/drain plug  
4 Holes  
9 dia.  
Cable gland (option)  
see note  
51  
71  
(27)  
Earth terminal  
(both side )  
see table1  
“C“  
Conduit conn.  
Detail “A“  
DETAIL “B“  
Detail “C“  
(press conn.)  
(Conduit conn.)  
ø18.5  
H
ø13  
ø
15  
Oval flange  
screw  
see table1 1  
Side vent  
(option)  
ø7  
2-M8 × 12  
G 1/2  
D
See table 1  
see table 1  
27  
70  
50  
Oval flange  
screw  
Conduit conn.  
Press. conn.  
H
F
Earth  
terminal  
4th digit  
code  
D
120  
E
7/16-20UNF  
Screw depth13  
7/16-20UNF  
Screw depth13  
M10  
Screw depth13  
7M10  
Screw depth13  
7/16-20UNF  
Screw depth13  
S
T
V
G1/2  
1/2  
–14NPT  
17  
Rc1/4  
M4  
8
16  
8
1/4–18NPT  
No. 8-32UNC  
M4  
5
CONNECTION  
DIAGRAM  
Pg13.5  
4.5 1/4–18NPT  
+
CK+ CK–  
16  
8
5
W
X
M20 × 1.5  
1/4–18NPT  
M4  
M4  
Pg13.5  
4.5 1/4–18NPT  
Table 1  
+
S
V
Note1) : Cable gland is supplied in case of flamproof packing type.  
ø11 cable is suitable.  
T
H
K
H
A
F
0
3
V
W
X
M
T
Head office  
Sales Div.  
International Sales Dept.  
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan  
Phone: 81-42-585-6201, 6202  
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan  
Phone: 81-3-5435-7111  
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm  
Fax: 81-42-585-6187, 6189  
Printed in Japan  
Information in this catalog is subject to change without notice.  

相关型号:

EDSX5-72

FFCCXX – –AAX SSEERRIIEESS REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-73

FCX – AX SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-74

FCX – AX SERIES SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-75

FCX – C SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-76A

FCX – C SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-77

FCX –AX SERIES PRESSURE TRANSMITTER Hydroseal® Diaphragm Version
FUJI

EDSX5-79J

ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-80K

PRESSURE TRANSMITTER
FUJI

EDSX5-82K

SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-83J

REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-85D

ELECTRONIC TRANSMITTER with FIELDBUS
FUJI

EDSX5-86D

PRESSURE TRANSMITTER
FUJI