MDP-DM3 [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MDP-DM3
型号: MDP-DM3
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总4页 (文件大小:122K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MDP-DM3  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
LIGHTNING SURGE PROTECTOR FOR MsysNet USE  
Functions & Features  
• Designed specifically for the network  
• No interruption of transmission signal by unplugging the  
head element module  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN  
rail mounting adapter  
Lot.NO  
MDEIJPAN1430B  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
B to C: ±5 V  
M•STER  
MODEL  
B or C to A: 5 V  
MODEL: MDP–DM3[1]  
Line to earth: ±140 V  
Voltage protection level (Up):  
• @ 1 kV (100 A)  
ORDERING INFORMATION  
• Code number: MDP-DM3[1]  
Specify a code from below for [1].  
(e.g. MDP-DM3/A33/Q)  
2 to 3: ±10 V  
2 or 3 to 1: 10 V  
Line to earth: ±650 V  
• @ 2 kV (1 kA)  
• Specify the specification for option code /Q  
(e.g. /C01)  
2 to 3: ±20 V  
2 or 3 to 1: 20 V  
Line to earth: ±800 V  
Response time: ≤ 0.1 μsec.  
Leakage current:  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
B to C: ≤ 0.2 mA @ ±5 V DC  
B or C to A: ≤ 0.2 mA @ 5 V DC  
Line to earth: ≤ 10 μA @ ±140 V DC  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
/A33: With adapter (model A-33)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
Nominal current (I ): 100 mA  
N
Internal series resistance: 4 Ω ±10 % (including return)  
Capacitance @ 1 MHz:  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Line to line: ≤ 20 nF  
Line to earth: ≤ 50 pF  
Input attenuation: -0.5 dB or less @ DC to 100 kHz, Zo =  
110 Ω  
/C02: Polyurethane coating  
/C03: Rubber coating  
Surge protection: IEC 61643-21 Categories C1, C2, D1  
RELATED PRODUCTS  
• Repeater (model: DALx)  
• Multi-transmission module (model: 22LAx)  
• Multi-transmission unit (model: DLAx)  
APPLICABLE NETWORK  
SIN-NET (conform to RS-422), MsysNet, MsysNet-mini,  
MuNet (RS-485), EC Cable (model ECx-5P)  
MDP-DM3 SPECIFICATIONS  
ES-8110 Rev.10 Page 1/4  
http://www.m-system.co.jp/  
MODEL: MDP-DM3  
CONNECTION EXAMPLES  
*1  
(Protected Device)  
*1  
(Protected Device)  
MDP-DM3  
MDP-DM3  
Shielded Twisted-pair Cable  
+
+
3
2
1
C
B
A
C
B
A
3
2
1
*2  
*2  
RS-422/485  
Communication Line  
SHLD  
SHLD  
*3  
*3  
FG  
G
G
FG  
*4  
*4  
Grounding  
≤100Ω  
Grounding  
≤100Ω  
*1. Applicable devices: M-System’s MsysNet or SIN-NET devices which employ RS-422/485 communication standards.  
*2. Recommended cable length between the surge protector and the protected device: 1 meter at the maximum  
*3. No connection is required if the protected device has no shield terminal.  
*4. Cross wire between the protected device’s FG terminal and the surge protector’s G terminal, and ground to the earth  
at the surge protector side.  
Ground only the surge protector if the protected device has no FG terminal.  
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
MDP-DM3 SPECIFICATIONS  
ES-8110 Rev.10 Page 2/4  
http://www.m-system.co.jp/  
MODEL: MDP-DM3  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
STANDARD  
80 (3.15)  
53 (2.09)  
2–5 (.20) dia.  
MTG HOLE  
31.5 (1.24)  
27 (1.06)  
HEAD ELEMENT  
3
2
1
BASE  
6–M4 TERMINAL SCREW  
C
B
A
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
(.33)  
[3.3 (.13)]  
80 (3.15)  
53 (2.09)  
27 (1.06)  
31.5 (1.24)  
DIN RAIL  
35mm wide  
3
2
1
6–M4 TERMINAL SCREW  
C
B
A
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MOUNTING REQUIREMENTS unit: mm (inch)  
2–M4 SCREW  
33 (1.30) min.  
MDP-DM3 SPECIFICATIONS  
ES-8110 Rev.10 Page 3/4  
http://www.m-system.co.jp/  
MODEL: MDP-DM3  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
2Ω  
C
B
3
2
2Ω  
ELEMENT  
ZD  
TO CABLE  
TO EQUIPMENT  
Discharge  
Elements  
ZD  
A
1
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
Specifications are subject to change without notice.  
MDP-DM3 SPECIFICATIONS  
ES-8110 Rev.10 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

MDP-DM3/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-DM3/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-EC

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-EC/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-EC/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-FT

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-FT/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-FT/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-JS/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-LC

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM