MODEL: MDP-DM3
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
LIGHTNING SURGE PROTECTOR FOR MsysNet USE
Functions & Features
• Designed specifically for the network
• No interruption of transmission signal by unplugging the
head element module
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN
rail mounting adapter
Lot.NO
MDEIJPAN1430B
PERFORMANCE
Max. continuous operating voltage (Uc):
B to C: ±5 V
M•STER
MODEL
B or C to A: 5 V
MODEL: MDP–DM3[1]
Line to earth: ±140 V
Voltage protection level (Up):
• @ 1 kV (100 A)
ORDERING INFORMATION
• Code number: MDP-DM3[1]
Specify a code from below for [1].
(e.g. MDP-DM3/A33/Q)
2 to 3: ±10 V
2 or 3 to 1: 10 V
Line to earth: ±650 V
• @ 2 kV (1 kA)
• Specify the specification for option code /Q
(e.g. /C01)
2 to 3: ±20 V
2 or 3 to 1: 20 V
Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
B to C: ≤ 0.2 mA @ ±5 V DC
B or C to A: ≤ 0.2 mA @ 5 V DC
Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
Nominal current (I ): 100 mA
N
Internal series resistance: 4 Ω ±10 % (including return)
Capacitance @ 1 MHz:
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Line to line: ≤ 20 nF
Line to earth: ≤ 50 pF
Input attenuation: -0.5 dB or less @ DC to 100 kHz, Zo =
110 Ω
/C02: Polyurethane coating
/C03: Rubber coating
Surge protection: IEC 61643-21 Categories C1, C2, D1
RELATED PRODUCTS
• Repeater (model: DALx)
• Multi-transmission module (model: 22LAx)
• Multi-transmission unit (model: DLAx)
APPLICABLE NETWORK
SIN-NET (conform to RS-422), MsysNet, MsysNet-mini,
MuNet (RS-485), EC Cable (model ECx-5P)
MDP-DM3 SPECIFICATIONS
ES-8110 Rev.10 Page 1/4
http://www.m-system.co.jp/
MODEL: MDP-DM3
CONNECTION EXAMPLES
*1
(Protected Device)
*1
(Protected Device)
MDP-DM3
MDP-DM3
Shielded Twisted-pair Cable
+
–
+
–
3
2
1
C
B
A
C
B
A
3
2
1
*2
*2
RS-422/485
Communication Line
SHLD
SHLD
*3
*3
FG
G
G
FG
*4
*4
Grounding
≤100Ω
Grounding
≤100Ω
*1. Applicable devices: M-System’s MsysNet or SIN-NET devices which employ RS-422/485 communication standards.
*2. Recommended cable length between the surge protector and the protected device: 1 meter at the maximum
*3. No connection is required if the protected device has no shield terminal.
*4. Cross wire between the protected device’s FG terminal and the surge protector’s G terminal, and ground to the earth
at the surge protector side.
Ground only the surge protector if the protected device has no FG terminal.
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
MDP-DM3 SPECIFICATIONS
ES-8110 Rev.10 Page 2/4
http://www.m-system.co.jp/
MODEL: MDP-DM3
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ STANDARD
80 (3.15)
53 (2.09)
2–5 (.20) dia.
MTG HOLE
31.5 (1.24)
27 (1.06)
HEAD ELEMENT
3
2
1
BASE
6–M4 TERMINAL SCREW
C
B
A
GROUND TERMINAL (G)
(used as mounting bracket)
■ WITH DIN RAIL MOUNTING ADAPTER
8.5
(.33)
[3.3 (.13)]
80 (3.15)
53 (2.09)
27 (1.06)
31.5 (1.24)
DIN RAIL
35mm wide
3
2
1
6–M4 TERMINAL SCREW
C
B
A
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MOUNTING REQUIREMENTS unit: mm (inch)
2–M4 SCREW
33 (1.30) min.
MDP-DM3 SPECIFICATIONS
ES-8110 Rev.10 Page 3/4
http://www.m-system.co.jp/
MODEL: MDP-DM3
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
2Ω
C
B
3
2
2Ω
ELEMENT
ZD
TO CABLE
TO EQUIPMENT
Discharge
Elements
ZD
A
1
BASE
G
GROUND TERMINAL
(used as mounting attachment)
Specifications are subject to change without notice.
MDP-DM3 SPECIFICATIONS
ES-8110 Rev.10 Page 4/4
http://www.m-system.co.jp/