R3-GFL1S/CE [MSYSTEM]
Remote I/O R3 Series FL-net INTERFACE MODULE;型号: | R3-GFL1S/CE |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series FL-net INTERFACE MODULE |
文件: | 总6页 (文件大小:150K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-GFL1
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
FL-net INTERFACE MODULE
(OPCN-2, Ver.2.0 supported)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
• Usable as a gateway between different protocols
combined with R3 interface modules
FUNCTIONS & FEATURES
• FL-net (OPCN-2), Ethernet based, controller level network,
compatible remote I/O
■ R3-GFL1 enables the other interface module to access
field signals as virtual I/O data via FL-net. No ladder
programming is required to assign these I/O signals.
■ Any PC or PLC compatible with FL-net, up to 254 nodes,
can retrieve the updated data by accessing the common
memory without interfering with the communication traffic.
■ Analog and discrete input signals cyclically transmitted
from other devices can be output as virtual analog signal.
The FL-net Configuration Builder software (model: R3-
NFLBLD) is used to assign these virtual analog signals on
the common memory in the bit or word units.
• 10 Mbps/100 Mbps cyclic transmission for the maximum
of 4k bits + 256 words (1 word = 16 bits) allows data
shared among the devices connected to the bus
• FL-net bus extended to max. 500 meters, up to 2.5
kilometers with a repeater
• No need of ladder programming
Typical Applications
• A gateway between FL-net and Modbus
■ Request/Response type message communication,
accessing I/O data only when necessary, is also possible.
27.5 [1.08]
CAUTION !
• FL-net standard requires a dedicated Ethernet bus for the
FL-net compatible devices. Connecting the R3-GFL1 to a
general-purpose LAN, or connecting a general-purpose
TCP/IP device to FL-net is Not allowed.
139
[5.47]
• FL-net uses UDP/IP protocol for transmission. ISDN, ADSL
or similar types of LAN are Not to be used.
109
[4.29]
mm [inch]
CAUTION
• When selecting network modules, note that this unit is not
designed to be used with network modules of certain types
or versions.
MODEL: R3-GFL1S[1]
ORDERING INFORMATION
• Code number: R3-GFL1S[1]
Specify a code from below for [1].
(e.g. R3-GFL1S/CE/Q)
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx,
and R3-NLx.
• This unit CAN be used with:
R3-NM3 and R3-NML3 of firmware version V1.00 or higher;
R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1,
R3-NM4, and R3-NP1 of firmware version V2.00 or higher;
and
• Specify the specification for option code /Q
(e.g. /C01)
other models of any firmware versions.
COMMUNICATION MODE
S: Single
RELATED PRODUCTS
• FL-net configuration builder (Model: R3-NFLBLD)
[1] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Downloadable at M-System’s web site.
/CE: CE marking
GENERAL SPECIFICATIONS
Connection
Other Options
blank: none
FL-net: RJ-45 connector
/Q: Option other than the above (specify the specification)
Internal bus: Via the Installation Base (model: R3-BSx)
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 1/6
https://www.m-system.co.jp/
MODEL: R3-GFL1
Internal power: Via the Installation Base (model: R3-BSx)
RUN contact output: Euro type connector terminal
4 k bits (area 1) + 256 words (area 2) / node
Max. message data size: 1024 bytes (per transmission
cycle)
(applicable wire size: 0.2 to 2.5 mm2, stripped length 7
mm)
Performance (2k bits + 2k words / node, 32 nodes in total)
Token cycle time: 50 milliseconds (1.56 milliseconds/ node
in average)
RUN/CFG selector: Toggle switch; RUN or Configuration
Isolation: Ethernet to internal bus or internal power to RUN
contact output
Message transmission time: 500 milliseconds (1 : 1
unidirectional message)
Indicator LEDs
RUN: Green LED turns on when the CPU, internal bus and
field bus on the other interface module are in normal
conditions.
INSTALLATION
Current consumption: 150 mA
ERR: Red LED turns on in an abnormality of the system.
LNK: Red LED turns on while the R3-GFL1 is participating
FL-net (normal communication)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
HER: Red LED turns on in an abnormality of I/O data.
PER: Red LED blinks on with the parameter setting error.
CFG: Red LED blinks in high speed at the startup; blinks in
low speed while the builder software is used.
TX: Green LED turns on while transmitting.
RX: Amber LED turns on while receiving.
Module allocation: Set with the side DIP switch.
■ RUN CONTACT OUTPUT
PERFORMANCE
Data allocation: 16 × n (Module allocation: 1 to 8)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact
output)
RUN contact: Relay turns on when the CPU, the internal bus
function and the field bus on the other interface module are
in normal conditions.
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Rated load: 250 V AC @0.5A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(< 50 V AC, < 75 V DC for EU conformity)
Maximum switching voltage: 250 V AC or 220 V DC
Maximum switching power: 62.5 VA or 60 W
Minimum load: 10 mV DC @ 1 mA
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
Mechanical life: 5 × 10 cycles (rate 300/min.)
7
EMS EN 61000-6-2
RoHS Directive
When driving an inductive load, external contact protection
and noise quenching are recommended.
FL-net SPECIFICATIONS
FL-net: Ver.2.0 supported
Physical layer standard: IEEE 802.3u
Data link layer: 10BASE-T / 100BASE-TX
Baud rate: 10 / 100 Mbps, Auto Negotiation
Protocol: FL-net (OPCN-2) (UDP/IP)
Transmission media: 10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length: 100 meters
Max. number of nodes: 254
IP address: FL-net Configuration Builder is used to set up the
IP address and the network address.
Factory setting:
192.168.250.1 (IP address)
255.255.255.0 (network address)
Max. cyclic data size:
8 k bits (area 1) + 8 k words (area 2) / system
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 2/6
https://www.m-system.co.jp/
MODEL: R3-GFL1
FL-net DESCRIPTIONS
■ CYCLIC TRANSMISSION
• Transmitting virtual I/O value, this module's information
and node error of signal source.
• Supplying common memory word data transmitted from
another devices as virtual output.
• If the node that this module is accessing has been
removed from the common memory, the operations “Hold
output” and “Clear Output” are selectable.
■ MESSAGE TRANSMISSION
The module supports the FL-net defined functions listed in
the following table. Only the server function is supported.
Server function allows the module to build a response frame
to a request message.
Client function allows the module to transmit a request
message and to receive its response frame.
MESSAGE TYPE
Byte block read
Byte block write
Word block read
Word block write
Network parameter read
Network parameter write
Stop command
SERVER
No
CLIENT
No
No
No
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
No
No
Start command
No
Prole read
No
Transparent mode
Log data read
No
Yes
Yes
Yes
No
Log data clear
No
Message echoback
No
PC REQUIREMENTS (provided by the user)
The following PC environment is required to run the R3-NFLBLD program.
Operating system: Windows 7 (32-bit/64-bit) or Windows 10 (32-bit/64-bit)
Screen area: 1024 by 768 pixels
LAN card: Required to connect to Ethernet
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 3/6
https://www.m-system.co.jp/
MODEL: R3-GFL1
EXTERNAL VIEW
■
FRONT VIEW
■
SIDE VIEW
RUN LED
ERR LED
LNK LED
Main
Configuration Jack
MAIN
HER LED
(unused)
PER LED
CFG LED
RUN/CFG Selector
SW1
I/O
8
7
6
5
4
10BASE-T/100BASE-TX
RJ-45 Connector
ETHERNET
I/O Configuration Jack
RX
TX
RX LED
TX LED
3
2
1
Module
Allocation
ON
RUN Contact
Output
TRANSMISSION DATA DESCRIPTIONS
Use the DIP SW located at the side of the module to specify module allocation.
1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 8 modules (128 words
input, 128 words output) transmission is available. R3-GFL1 seems as if max. 8 I/O modules are mounted to 8 slots via FL-net.
The input of the module is processed as follows.
[FL-net Communication] --> [R3-GFL1 Module] --> [R3 Base] --> [R3 Communication Module]
The data set with output tab of R3-NFLBLD to input is transmitted to R3 communication module. Output is reversed. The data
set with transmitting area 1 and transmitting area 2 is transmitted to FL-net.
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot,
an internal bus error occurs. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the
data for more than 16 modules.
■ WHEN R3-GFL1 IS MOUNTED ON SLOT NO. 2 (4 modules)
Real I/O modules are mounted on Slots No. 1 and 2, however, the network module (R3-NE1) recognizes that each of Slots No. 1
to 5 is occupied. That is, R3-NE1 recognizes R3-SV4 mounted on Slot No.1 as it is and recognizes R3-GFL1 mounted on Slot
No.2 as divided into four modules and occupying Slots No. 2 to 5.
SLOT
REAL MODULE VERTUAL MODULE NO. OF WORDS
R3-BS08
Slot No.1
Slot No.2
Slot No.3
Slot No.4
Slot No.5
Slot No.6
Slot No.7
Slot No.8
R3-SV4
R3-GFL1
No module
No module
No module
No module
R3-NE1
R3-SV4
R3-GFL1 (1/4)
R3-GFL1 (2/4)
R3-GFL1 (3/4)
R3-GFL1 (4/4)
No module
R3-NE1
4Words
16Words
16Words
16Words
16Words
----
R3-
R3-
R3-
R3-
SV4 GFL1
NE1 PS1
1
2
3
4
5
6
7
8
----
R3-PS1
R3-PS1
----
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 4/6
https://www.m-system.co.jp/
MODEL: R3-GFL1
I/O DATA DESCRIPTIONS
■ MODULE STATUS, SOURCE NODE ERROR
Shows each module’s availability and error status.
15
0
Module 1 (Slot 1)
Module 2 (Slot 2)
Module 3 (Slot 3)
Module 8 (Slot 8)
■ ANALOG DATA
16-bit binary data.
15
0
EXTERNAL DIMENSIONS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 5/6
https://www.m-system.co.jp/
MODEL: R3-GFL1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
LED
JACK
JACK
RJ45
I/O CONFIGURATION JACK
MAIN CONFIGURATION JACK
10BASE-T/100BASE-TX
Main
Control
Circuit
I/O
Communication
Circuit
INTERNAL BUS
Control
Circuit
DIP SW
T1
T2
INTERNAL POWER
RUN CONTACT OUTPUT
SYSTEM CONFIGURATION EXAMPLES
128 channels PC recorder software
(Model: MSR128-V6)
RS-232-C
RS-232-C/RS-485 Converter
(Model: R2K-1)
CO
NF
IG
RUN
B
RA
TE
ER
R.1
ER
R.2
RS-485
R3- R3- R3-
GFL1 NM1 PS1
Hub
Ethernet
FL-net
Compatible PLC
R3- R3- R3- R3-
SV4 DA16 NFL1 PS1
Specifications are subject to change without notice.
R3-GFL1 SPECIFICATIONS
ES-8461 Rev.13 Page 6/6
https://www.m-system.co.jp/
相关型号: