MODEL: R3-GFL1  
Remote I/O R3 Series  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
FL-net INTERFACE MODULE  
(OPCN-2, Ver.2.0 supported)  
/C02: Polyurethane coating  
/C03: Rubber coating  
Functions & Features  
• Usable as a gateway between different protocols  
combined with R3 interface modules  
FUNCTIONS & FEATURES  
• FL-net (OPCN-2), Ethernet based, controller level network,  
compatible remote I/O  
■ R3-GFL1 enables the other interface module to access  
field signals as virtual I/O data via FL-net. No ladder  
programming is required to assign these I/O signals.  
■ Any PC or PLC compatible with FL-net, up to 254 nodes,  
can retrieve the updated data by accessing the common  
memory without interfering with the communication traffic.  
■ Analog and discrete input signals cyclically transmitted  
from other devices can be output as virtual analog signal.  
The FL-net Configuration Builder software (model: R3-  
NFLBLD) is used to assign these virtual analog signals on  
the common memory in the bit or word units.  
• 10 Mbps/100 Mbps cyclic transmission for the maximum  
of 4k bits + 256 words (1 word = 16 bits) allows data  
shared among the devices connected to the bus  
• FL-net bus extended to max. 500 meters, up to 2.5  
kilometers with a repeater  
• No need of ladder programming  
Typical Applications  
• A gateway between FL-net and Modbus  
■ Request/Response type message communication,  
accessing I/O data only when necessary, is also possible.  
27.5 [1.08]  
CAUTION !  
• FL-net standard requires a dedicated Ethernet bus for the  
FL-net compatible devices. Connecting the R3-GFL1 to a  
general-purpose LAN, or connecting a general-purpose  
TCP/IP device to FL-net is Not allowed.  
139  
[5.47]  
• FL-net uses UDP/IP protocol for transmission. ISDN, ADSL  
or similar types of LAN are Not to be used.  
109  
[4.29]  
mm [inch]  
CAUTION  
• When selecting network modules, note that this unit is not  
designed to be used with network modules of certain types  
or versions.  
MODEL: R3-GFL1S[1]  
ORDERING INFORMATION  
• Code number: R3-GFL1S[1]  
Specify a code from below for [1].  
(e.g. R3-GFL1S/CE/Q)  
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx,  
and R3-NLx.  
• This unit CAN be used with:  
R3-NM3 and R3-NML3 of firmware version V1.00 or higher;  
R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1,  
R3-NM4, and R3-NP1 of firmware version V2.00 or higher;  
and  
• Specify the specification for option code /Q  
(e.g. /C01)  
other models of any firmware versions.  
COMMUNICATION MODE  
S: Single  
RELATED PRODUCTS  
• FL-net configuration builder (Model: R3-NFLBLD)  
[1] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Downloadable at M-System’s web site.  
/CE: CE marking  
GENERAL SPECIFICATIONS  
Connection  
Other Options  
blank: none  
FL-net: RJ-45 connector  
/Q: Option other than the above (specify the specification)  
Internal bus: Via the Installation Base (model: R3-BSx)  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 1/6  
https://www.m-system.co.jp/  
MODEL: R3-GFL1  
Internal power: Via the Installation Base (model: R3-BSx)  
RUN contact output: Euro type connector terminal  
4 k bits (area 1) + 256 words (area 2) / node  
Max. message data size: 1024 bytes (per transmission  
cycle)  
(applicable wire size: 0.2 to 2.5 mm2, stripped length 7  
mm)  
Performance (2k bits + 2k words / node, 32 nodes in total)  
Token cycle time: 50 milliseconds (1.56 milliseconds/ node  
in average)  
RUN/CFG selector: Toggle switch; RUN or Configuration  
Isolation: Ethernet to internal bus or internal power to RUN  
contact output  
Message transmission time: 500 milliseconds (1 : 1  
unidirectional message)  
Indicator LEDs  
RUN: Green LED turns on when the CPU, internal bus and  
field bus on the other interface module are in normal  
conditions.  
INSTALLATION  
Current consumption: 150 mA  
ERR: Red LED turns on in an abnormality of the system.  
LNK: Red LED turns on while the R3-GFL1 is participating  
FL-net (normal communication)  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
HER: Red LED turns on in an abnormality of I/O data.  
PER: Red LED blinks on with the parameter setting error.  
CFG: Red LED blinks in high speed at the startup; blinks in  
low speed while the builder software is used.  
TX: Green LED turns on while transmitting.  
RX: Amber LED turns on while receiving.  
Module allocation: Set with the side DIP switch.  
RUN CONTACT OUTPUT  
PERFORMANCE  
Data allocation: 16 × n (Module allocation: 1 to 8)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(Ethernet to internal bus or internal power to RUN contact  
output)  
RUN contact: Relay turns on when the CPU, the internal bus  
function and the field bus on the other interface module are  
in normal conditions.  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
Rated load: 250 V AC @0.5A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
(< 50 V AC, < 75 V DC for EU conformity)  
Maximum switching voltage: 250 V AC or 220 V DC  
Maximum switching power: 62.5 VA or 60 W  
Minimum load: 10 mV DC @ 1 mA  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
Mechanical life: 5 × 10 cycles (rate 300/min.)  
7
EMS EN 61000-6-2  
RoHS Directive  
When driving an inductive load, external contact protection  
and noise quenching are recommended.  
FL-net SPECIFICATIONS  
FL-net: Ver.2.0 supported  
Physical layer standard: IEEE 802.3u  
Data link layer: 10BASE-T / 100BASE-TX  
Baud rate: 10 / 100 Mbps, Auto Negotiation  
Protocol: FL-net (OPCN-2) (UDP/IP)  
Transmission media: 10BASE-T (STP cable, category 5)  
100BASE-TX (STP cable, category 5e)  
Max. segment length: 100 meters  
Max. number of nodes: 254  
IP address: FL-net Configuration Builder is used to set up the  
IP address and the network address.  
Factory setting:  
192.168.250.1 (IP address)  
255.255.255.0 (network address)  
Max. cyclic data size:  
8 k bits (area 1) + 8 k words (area 2) / system  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 2/6  
https://www.m-system.co.jp/  
MODEL: R3-GFL1  
FL-net DESCRIPTIONS  
CYCLIC TRANSMISSION  
• Transmitting virtual I/O value, this module's information  
and node error of signal source.  
• Supplying common memory word data transmitted from  
another devices as virtual output.  
• If the node that this module is accessing has been  
removed from the common memory, the operations “Hold  
output” and “Clear Output” are selectable.  
MESSAGE TRANSMISSION  
The module supports the FL-net defined functions listed in  
the following table. Only the server function is supported.  
Server function allows the module to build a response frame  
to a request message.  
Client function allows the module to transmit a request  
message and to receive its response frame.  
MESSAGE TYPE  
Byte block read  
Byte block write  
Word block read  
Word block write  
Network parameter read  
Network parameter write  
Stop command  
SERVER  
No  
CLIENT  
No  
No  
No  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
No  
No  
Start command  
No  
Prole read  
No  
Transparent mode  
Log data read  
No  
Yes  
Yes  
Yes  
No  
Log data clear  
No  
Message echoback  
No  
PC REQUIREMENTS (provided by the user)  
The following PC environment is required to run the R3-NFLBLD program.  
Operating system: Windows 7 (32-bit/64-bit) or Windows 10 (32-bit/64-bit)  
Screen area: 1024 by 768 pixels  
LAN card: Required to connect to Ethernet  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 3/6  
https://www.m-system.co.jp/  
MODEL: R3-GFL1  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
LNK LED  
Main  
Configuration Jack  
MAIN  
HER LED  
(unused)  
PER LED  
CFG LED  
RUN/CFG Selector  
SW1  
I/O  
8
7
6
5
4
10BASE-T/100BASE-TX  
RJ-45 Connector  
ETHERNET  
I/O Configuration Jack  
RX  
TX  
RX LED  
TX LED  
3
2
1
Module  
Allocation  
ON  
RUN Contact  
Output  
TRANSMISSION DATA DESCRIPTIONS  
Use the DIP SW located at the side of the module to specify module allocation.  
1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 8 modules (128 words  
input, 128 words output) transmission is available. R3-GFL1 seems as if max. 8 I/O modules are mounted to 8 slots via FL-net.  
The input of the module is processed as follows.  
[FL-net Communication] --> [R3-GFL1 Module] --> [R3 Base] --> [R3 Communication Module]  
The data set with output tab of R3-NFLBLD to input is transmitted to R3 communication module. Output is reversed. The data  
set with transmitting area 1 and transmitting area 2 is transmitted to FL-net.  
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot,  
an internal bus error occurs. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the  
data for more than 16 modules.  
WHEN R3-GFL1 IS MOUNTED ON SLOT NO. 2 (4 modules)  
Real I/O modules are mounted on Slots No. 1 and 2, however, the network module (R3-NE1) recognizes that each of Slots No. 1  
to 5 is occupied. That is, R3-NE1 recognizes R3-SV4 mounted on Slot No.1 as it is and recognizes R3-GFL1 mounted on Slot  
No.2 as divided into four modules and occupying Slots No. 2 to 5.  
SLOT  
REAL MODULE VERTUAL MODULE NO. OF WORDS  
R3-BS08  
Slot No.1  
Slot No.2  
Slot No.3  
Slot No.4  
Slot No.5  
Slot No.6  
Slot No.7  
Slot No.8  
R3-SV4  
R3-GFL1  
No module  
No module  
No module  
No module  
R3-NE1  
R3-SV4  
R3-GFL1 (1/4)  
R3-GFL1 (2/4)  
R3-GFL1 (3/4)  
R3-GFL1 (4/4)  
No module  
R3-NE1  
4Words  
16Words  
16Words  
16Words  
16Words  
----  
R3-  
R3-  
R3-  
R3-  
SV4 GFL1  
NE1 PS1  
1
2
3
4
5
6
7
8
----  
R3-PS1  
R3-PS1  
----  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 4/6  
https://www.m-system.co.jp/  
MODEL: R3-GFL1  
I/O DATA DESCRIPTIONS  
■ MODULE STATUS, SOURCE NODE ERROR  
Shows each module’s availability and error status.  
15  
0
Module 1 (Slot 1)  
Module 2 (Slot 2)  
Module 3 (Slot 3)  
Module 8 (Slot 8)  
■ ANALOG DATA  
16-bit binary data.  
15  
0
EXTERNAL DIMENSIONS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 5/6  
https://www.m-system.co.jp/  
MODEL: R3-GFL1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
LED  
JACK  
JACK  
RJ45  
I/O CONFIGURATION JACK  
MAIN CONFIGURATION JACK  
10BASE-T/100BASE-TX  
Main  
Control  
Circuit  
I/O  
Communication  
Circuit  
INTERNAL BUS  
Control  
Circuit  
DIP SW  
T1  
T2  
INTERNAL POWER  
RUN CONTACT OUTPUT  
SYSTEM CONFIGURATION EXAMPLES  
128 channels PC recorder software  
(Model: MSR128-V6)  
RS-232-C  
RS-232-C/RS-485 Converter  
(Model: R2K-1)  
CO  
NF  
IG  
RUN  
B
RA  
TE  
ER  
R.1  
ER  
R.2  
RS-485  
R3- R3- R3-  
GFL1 NM1 PS1  
Hub  
Ethernet  
FL-net  
Compatible PLC  
R3- R3- R3- R3-  
SV4 DA16 NFL1 PS1  
Specifications are subject to change without notice.  
R3-GFL1 SPECIFICATIONS  
ES-8461 Rev.13 Page 6/6  
https://www.m-system.co.jp/  

相关型号:

R3-GFL1S/Q

Remote I/O R3 Series FL-net INTERFACE MODULE
MSYSTEM

R3-GGLMP

Remote I/O R3 Series INTERFACE I/O MODULE
MSYSTEM

R3-GGLMP/CE

Remote I/O R3 Series INTERFACE I/O MODULE
MSYSTEM

R3-GGLMP/Q

Remote I/O R3 Series INTERFACE I/O MODULE
MSYSTEM

R3-GM1

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-GM1S

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-GM1S/CE

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-GM1S/Q

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-LC2

Remote I/O R3 Series STRAIN GAUGE INPUT MODULE
MSYSTEM

R3-LC2S

Remote I/O R3 Series STRAIN GAUGE INPUT MODULE
MSYSTEM

R3-LC2S/Q

Remote I/O R3 Series STRAIN GAUGE INPUT MODULE
MSYSTEM

R3-LC2W

Remote I/O R3 Series STRAIN GAUGE INPUT MODULE
MSYSTEM