R3-NF3-R/Q [MSYSTEM]
Remote I/O R3 Series T-Link INTERFACE MODULE;型号: | R3-NF3-R/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series T-Link INTERFACE MODULE |
文件: | 总7页 (文件大小:193K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-NF3
0.2 to 2.5 mm , stripped length 7 mm)
2
Remote I/O R3 Series
Internal bus: Via the Installation Base
(model: R3-BSx)
T-Link INTERFACE MODULE
(Fuji Electric T-Link capsule equivalent)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
27.5
(1.08)
Screw terminal: Nickel-plated steel
Isolation: T-Link to internal bus or internal power to power
input to RUN contact output to FG
Input error data setting: Input value setting at input module
error with side DIP SW
130
(5.12)
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
I/O Points setting: Set with the front DIP switch
Data setting: Set with the front DIP switch
I/O Module Status setting: Set with the front DIP switch
I/O Type setting: Set with the front DIP switch
Analog Data Type setting: Set with the front DIP switch
RUN indicator: Bi-color (green/red) LED; Green ON in normal
communication; Red blinks when receiving data (Function
selected with DIP SW)
109
(4.29)
mm (inch)
MODEL: R3–NF3–[1][2]
ORDERING INFORMATION
• Code number: R3-NF3-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NF3-M2/Q)
ERR indicator: Bi-color (green/red) LED; Green ON in
communication errors or minor failure, blinks at errors in the
internal circuits; Red blinks when transmitting data
(Function selected with DIP SW)
• Specify the specification for option code /Q
(e.g. /C01)
■ RUN CONTACT OUTPUT
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
[1] POWER INPUT
N: No power supply
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)*
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When
7
DC Power
driving an inductive load, external contact protection and
noise quenching recommended.
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
T-Link SPECIFICATIONS
Node address: Rotary switch; 00 – 99
Configuration: Multi-drop
[2] OPTIONS
blank: none
Communication: Half-duplex
Baud rate: 500 kbps
/Q: With options (specify the specification)
Transmission media/distance:
KPEV-SB, 0.75 mm
2
× 1 pair, 700 m
× 1 pair, 1000 m
T-KPEV-SB, 1.25 mm
2
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
INSTALLATION
Power consumption
•AC: ≤ 22 VA
/C02: Polyurethane coating
/C03: Rubber coating
•DC: ≤ 9 W
Current consumption (no power supply): 120 mA
Output current (power supply): 230 mA continuous at 20 V
DC; 380 mA for 10 minutes
GENERAL SPECIFICATIONS
Connection
T-Link: Euro type connector terminal (applicable wire size:
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 1/7
http://www.m-system.co.jp/
MODEL: R3-NF3
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (T-Link to
internal bus or internal power to power input to RUN contact
output to FG)
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Node Address Setting
Rotary SW (MSB)
SA1
SA2
RUN LED
ERR LED
Node Address Setting
Rotary SW (LSB)
DIP SW
SW3
ON
SW2
SW1
RT+
RT–
SD
T2
Network
SW6
Configuration Jack
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
8:KS7
7:KS6
6:KS5
5:KS4
4:KS3
3:KS2
2:KS1
1:KS0
T1
Euro Type
Connector Terminal
1
2
3
4
ON
ON
5
6
ON
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 2/7
http://www.m-system.co.jp/
MODEL: R3-NF3
TRANSMISSION DATA DESCRIPTIONS
The DIP SW in the front of the module species I/O points, I/O type and with or without of I/O module status data setting.
I/O DATA is assigned data allocation setting from module 1 orderly.
The data of I/O module out of the setting area is invalid.
When there is I/O module status data, use the data area of the last 2 words of the input data area as the status data. When the
status data and I/O data overlap, the status data takes precedence.
For example, when the number of I/O points is “16” and SW1 and SW2 are set as shown below.
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
4
4
4
1
1
1
1
Then the I/O data are assigned as in the gures below:
■ IN THE CASE OF NO I/O MODULE STATUS (KS3: OFF)
• I/O TYPE: INPUT ONLY or OUTPUT ONLY
• I/O TYPE: INPUT / OUTPUT MIXED
The side DIP SW (SW1, 2) determine data allocation of mod-
ule (number of data) per module.
The number of input points and the number of output points
are assigned half numbers of KS0 to 1 respectively.
The rst half of the data area is the input area and the second
half is the output area.
The number of data set by SW1 and SW2 is assigned to trans-
mission data in order from slot 1.
Please set the input module in slot 1 and 2, and output mod-
ule after slot 3.
15
0
Begin
Address +0
15
0
Begin
Slot 1
Slot 2
Slot 3
Address +0
+2
+4
Slot 1
Slot 2
Slot 3
+2
+4
Input
(8 points)
+6
+6
+8
+8
+10
+12
+14
+10
+12
+14
Slot 4
Slot 5
Slot 6
Slot 7
Output
(8 points)
Slot 4
Slot 5
Slot 6
Slot 7
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 3/7
http://www.m-system.co.jp/
MODEL: R3-NF3
■ WITH INPUT / OUTPUT MODULE STATUS (KS3: ON)
• I/O TYPE: INPUT ONLY
• I/O TYPE: INPUT / OUTPUT MIXED
Status data is assigned to the last 2 words of the area.
Slot 6 and 7 are invalid.
Status data is assigned to the last 2 words of the area.
Data in the 3rd and 4th words of slot 2 are invalid.
15
0
15
0
Begin
Begin
+0
+2
+0
+2
Address
Address
Slot 1
Slot
Slot
1
2
Input
(8 points
+4
+4
Slot 2
Module
Status
Error
+6
+6
Status
+8
+8
Slot
3
Slot 3
+10
+12
+14
+10
+12
+14
Output
(8 points
Slot
Slot
4
5
Slot
4
5
6
7
Slot
Slot
Slot
Module Status
Error Status
• I/O TYPE: OUTPUT
Status data cannot be assigned because there is no input data.
For output only, operate without status area.
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot turns to
“1,” and the unmounted slot to “0.”
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”
R3-TSx, R3-RSx, R3-US4 (T/C, RTD input): Input burnout
R3-DA16A: Power input in error or disconnected
R3-YSx: Output current error (e.g. load unconnected)
R3-PC16A: External power supply in error or disconnected
Every module which input is less than -15% or more than +115%
R3-US4 (voltage input): out of -10 to +110% input.
MODULE STATUS, ERROR STATUS
Shows each module's availability and error status.
15
0
Module 1
Module 2
Module 3
:
Module 16
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 4/7
http://www.m-system.co.jp/
MODEL: R3-NF3
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.
15
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.
For example, 135.4°F is converted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.
15
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.
15
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
0
0
+0
+1
Lower 16 bits
Higher 16 bits
15
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 5/7
http://www.m-system.co.jp/
MODEL: R3-NF3
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
15
0
+0
+1
Lower 16 bits
Higher 16 bits
0
■ ANALOG 16 BITS BCD DATA
The display range is -7999 to +7999. Change data within display range with configurator software (model: R3CON).
■ ANALOG 32 BITS BCD DATA
The display range is -1500 to +11500. Data allocation of module is doubled as usual. Pay attention I/O type.
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
15
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
0 : OFF
1 : ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
10 (.39)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
6–M3
SCREW
1
4
2
5
3
TERMINAL
COVER
6
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 6/7
http://www.m-system.co.jp/
MODEL: R3-NF3
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
LED Rotary SW
Isolation
RT+
RT–
SD
T2
Control
Circuit
Communication
Circuit
Close to terminate.*
INTERNAL BUS
Shielded Twisted-pair
Cable
To Other
T-Link
Devices
Term. Resist.
DIP SW
–
+
T1
INTERNAL POWER
RUN +
RUN –
U (+)
1
4
2
3
6
RUN CONTACT OUTPUT
5
**
**
POWER INPUT
V (–)
**
FG
JACK
CONFIGURATION JACK
* When the module is at an end of the transmission line via twisted-pair calbe
(= when there is no cross wiring), close across the RT+ and RT– terminals with the
jumper included in the product package. Remove the jumper for all other locations.
**Not provided with ‘No Power Supply’ type module.
Caution: FG terminal is NOT a protective conductor terminal.
Specifications are subject to change without notice.
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 7/7
http://www.m-system.co.jp/