R3S-DC8S [MSYSTEM]
Remote I/O R3 Series DISCRETE OUTPUT MODULE;型号: | R3S-DC8S |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DISCRETE OUTPUT MODULE 输出元件 |
文件: | 总5页 (文件大小:149K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3S-DC8
Output: Separable tension clamp terminal (applicable wire
Remote I/O R3 Series
size: 0.2 to 1.5 mm , stripped length 10 mm)
2
Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output 1 to output 2 to output 3 to output 4 to
output 5 to output 6 to output 7 to output 8 to internal bus
or internal power
DISCRETE OUTPUT MODULE
(Do 8 points (relay), tension clamp terminal block)
27.5 (1.08)
Output hold setting: Setting for communication error with
side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating
conditions.
130 (5.12)
120 (4.72)
mm (inch)
Output status indicator:
1 to 8: Red LED; turns on with the output ON.
9 to 16: Unused
MODEL: R3S–DC8[1][2]
OUTPUT SPECIFICATIONS
Output: Relay contact, 8 points
ORDERING INFORMATION
• Code number: R3S-DC8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-DC8W/CE/Q)
Common: 1 point 1 common (8 terminals)
Maximum load current: 2.0 A per point
Relay driving power: 24 V DC ±10 %, ≥ 60 mA
Maximum outputs applicable at once: No limit (at 24 V DC)
Contact rating: 250 V AC @ 2 A (cos ø = 1)
30 V DC @ 2 A (resistive load)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
8: 8
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @ 1 mA
Mechanical life: 2 × 10 cycles (300 cycle/min.)
7
[1] COMMUNICATION MODE
S: Single
When driving an inductive load, external protection is
recommended.
W: Dual
ON delay: ≤ 10 msec.
OFF delay: ≤ 10 msec.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 190 g (0.42 lb)
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
R3S-DC8 SPECIFICATIONS
ES-8941 Rev.3 Page 1/5
https://www.m-system.co.jp/
MODEL: R3S-DC8
PERFORMANCE
Data allocation: 1
Current consumption: Approx. 60 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 1 to output 2 to output 3 to output 4 to output 5 to
output 6 to output 7 to output 8 to internal bus or internal
power)
2000 V AC @ 1 minute (power input to FG;
isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (output)
Pollution Degree 2
Output to internal bus or internal power: Basic insulation
(250 V)
RoHS Directive
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
• Output Hold
If both are in error, the module holds the signal and stands
by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs OFF signals and
stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is
established and normal data is received.
R3S-DC8 SPECIFICATIONS
ES-8941 Rev.3 Page 2/5
https://www.m-system.co.jp/
MODEL: R3S-DC8
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Output Status Indicator LEDs
ERR LED
1
SW3
4
3
2
1
Output
Hold
ON
20
EXTERNAL DIMENSIONS unit: mm [inch]
120 (4.72)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
1
20
R3S-DC8 SPECIFICATIONS
ES-8941 Rev.3 Page 3/5
https://www.m-system.co.jp/
MODEL: R3S-DC8
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
ERR INDICATOR
RUN
LED
DIP SW
Output
Circuit
LED
LED
Ry
Ry
Ry
Ry
Ry
Ry
Ry
Ry
1
INTERNAL BUS A
Communication
Circuit
1
2
3
4
5
6
7
8
9
Do 1
*INTERNAL BUS B
COM 1
Do 2
2
3
4
5
6
7
8
COM 2
Do 3
INTERNAL POWER
COM 3
Do 4
COM 4
Do 5
Control
Circuit
10 COM 5
11 Do 6
12 COM 6
13 Do 7
14 COM 7
15 Do 8
16 COM 8
17 +24V
18 +24V
19 0V
24V DC
20 0V
Numbers in italic indicate LED No.s assigned to the front panel LEDs.
*For dual redundant communication.
■ Output Connection Examples
ࠉ
1 point 1 common Do 1
1
2
COM 1
-
+
+
-
Do 8 15
COM 8 16
-
+
+
-
R3S-DC8 SPECIFICATIONS
ES-8941 Rev.3 Page 4/5
https://www.m-system.co.jp/
MODEL: R3S-DC8
OUTPUT TERMINAL ASSIGNMENT
PIN No.
1
FUNCTION
Do1
2
COM1
Do2
3
4
COM2
Do3
5
6
COM3
Do4
7
8
COM4
Do5
9
10
11
12
13
14
15
16
17
18
19
20
COM5
Do6
COM6
Do7
COM7
Do8
COM8
+24V
+24V
0V
0V
Specifications are subject to change without notice.
R3S-DC8 SPECIFICATIONS
ES-8941 Rev.3 Page 5/5
https://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明