R3Y-YS4W/CE [MSYSTEM]
Remote I/O R3 Series DC CURRENT OUTPUT MODULE;型号: | R3Y-YS4W/CE |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DC CURRENT OUTPUT MODULE 输出元件 |
文件: | 总4页 (文件大小:118K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3Y-YS4
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8370)
Remote I/O R3 Series
DC CURRENT OUTPUT MODULE
(4 points, isolated, connector type)
RELATED PRODUCTS
• Connector terminal block (model: CNT)
27.5 [1.08]
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Connection
130
[5.12]
Internal bus: Via the Installation Base (model: R3-BSx)
Output: 40-pin connector (Fujitsu FCN-365P040-AU)
Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output 1 to output 2 to output 3 to output 4 to
internal bus or internal power
110
[4.33]
mm [inch]
Output hold function: Setting for communication error with
side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with output abnormality;
MODEL: R3Y–YS4[1][2]
ORDERING INFORMATION
• Code number: R3Y-YS4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3Y-YS4W/H/CE/Q)
Green in normal operating conditions.
• Specify the specification for option code /Q
(e.g. /C01/SET)
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
NO. OF CHANNELS
4: 4
Load resistance: 300 Ω max. (600 Ω max. with Option /H)
INSTALLATION
[1] COMMUNICATION MODE
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
S: Single
W: Dual
[2] OPTIONS (multiple selections)
Load Resistance
blank: ≤ 300 Ω
PERFORMANCE
Conversion accuracy: ±0.05 %
/H: ≤ 600Ω
Standards & Approvals
blank: Without CE
Data range: 0 – 10000 of the output range
Data allocation: 4
/CE: CE marking
Current consumption: 180 mA (260 mA with Option /H)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output 1 to
output 2 to output 3 to output 4 to internal bus or internal
power)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
R3Y-YS4 SPECIFICATIONS
ES-8961 Rev.10 Page 1/4
https://www.m-system.co.jp/
MODEL: R3Y-YS4
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
•Output Hold
If both are in error, the module holds the signal and stands
by until one of the communications recovers.
•Output OFF
If both are in error, the module outputs -15 % and stands by
until one of the communications recovers.
At the startup, it outputs -15 % until the communication is
established and normal data is received.
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
ERR LED
• Pin Assignment
B A
20 20
Output Connector
SW3
4
3
2
1
Output
Hold
B
A
1
1
R3Y-YS4 SPECIFICATIONS
ES-8961 Rev.10 Page 2/4
https://www.m-system.co.jp/
MODEL: R3Y-YS4
EXTERNAL DIMENSIONS unit: mm [inch]
27.5 [1.08]
110 [4.33]
POSITIONING
GUIDE
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Output Circuit
INTERNAL BUS A
Communication
Circuit
+
–
+
–
+
–
+
–
20A/20B
18A/18B
16A/16B
14A/14B
10A/10B
8A/8B
INTERNAL BUS B*
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
Output Circuit
Control
Circuit
INTERNAL POWER
Output Circuit
Output Circuit
6A/6B
4A/4B
*For dual redundant communication.
• Unused Output Channels
Close across the unused output terminals as shown below.
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
20A/20B 16A/16B 10A/10B
18A/18B 14A/14B 8A/8B
6A/6B
4A/4B
Unused channels left open are equal to the wire breakdown,
which turns the red ERR LED on and sets a burnout flag at the
PLC or the host device.
Unused channels can be specified and set so on the PC Configu-
rator Software (model: R3CON) without needing to short at the
field terminals.
R3Y-YS4 SPECIFICATIONS
ES-8961 Rev.10 Page 3/4
https://www.m-system.co.jp/
MODEL: R3Y-YS4
OUTPUT CONNECTOR (40-pin)
PIN NO.
ASSIGNMENT
PIN NO.
ASSIGNMENT
1A
2A
3A
NC
NC
NC
1B
2B
3B
NC
NC
NC
4A
5A
6A
– OUT4
NC
4B
5B
6B
– OUT4
NC
+ OUT4
+ OUT4
7A
8A
9A
NC
– OUT3
NC
7B
8B
9B
NC
– OUT3
NC
10A
11A
12A
+ OUT3
NC
10B
11B
12B
+ OUT3
NC
NC
NC
13A
14A
15A
NC
– OUT2
NC
13B
14B
15B
NC
– OUT2
NC
16A
17A
18A
+ OUT2
NC
16B
17B
18B
+ OUT2
NC
– OUT1
– OUT1
19A
20A
NC
19B
20B
NC
+ OUT1
+ OUT1
Specifications are subject to change without notice.
R3Y-YS4 SPECIFICATIONS
ES-8961 Rev.10 Page 4/4
https://www.m-system.co.jp/