下载:  下载PDF数据表文档文件
MODEL: R5T-DC4  
steel  
Remote I/O R5 Series  
Isolation: Do1 or Do2 to Do3 or Do4 to internal bus or  
internal power  
DISCRETE OUTPUT MODULE  
(screw terminal block; relay contact output, 4 points)  
18 (.71)  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
Output status indicator: Red LED; turns on with the outputs  
ON.  
90  
(3.54)  
OUTPUT SPECIFICATIONS  
Output: Relay contact, 4 points  
137  
(5.39)  
Common: Every 2 points  
mm (inch)  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
MODEL: R5T–DC4[1][2]  
ORDERING INFORMATION  
Code number: R5T-DC4[1][2]  
Mechanical life: 2 × 10 cycles (rate 300/min.)  
7
When driving an inductive load, external contact protection  
and noise quenching recommended.  
Specify a code from below for each of [1] and [2].  
(e.g. R5T-DC4W/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 110 g (0.24 lb)  
NO. OF CHANNELS  
4: 4-point outputs  
[1] COMMUNICATION MODE  
S: Single  
PERFORMANCE  
Data allocation: 1  
W: Dual  
Response time: ≤ 0.1 sec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (Do 1 or Do 2 to  
Do 3 or Do 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R5-BS)  
Output: M3.5 screw terminal block (torque 0.8 N·m)  
Internal power: Via the base (model: R5-BS)  
Screw terminal: Nickel-plated steel (standard) or stainless  
R5T-DC4 SPECIFICATIONS  
ES-6129 Rev.9 Page 1/3  
https://www.m-system.co.jp/  
MODEL: R5T-DC4  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1, EN 61010-2-201  
Measurement Category II (output)  
Pollution Degree 2  
Output to internal bus or internal power – Basic insulation  
(300 V)  
RoHS Directive  
FUNCTIONS  
Output hold function:  
In normal conditions, the module outputs the signal from  
the preferred bus A.  
When an error is detected, the output is switched to the  
data from the bus B.  
If both are in error, the module holds the signal and stands  
by until one of the communications recovers.  
At the startup, it outputs OFF until the communication is  
established and normal data is received.  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
RUN  
1
1 2 3 4 5 6 7 8  
Status Indicator LED  
2
3
4
DO NOT USE  
4
5
6
1
2
3
R5T-DC4 SPECIFICATIONS  
ES-6129 Rev.9 Page 2/3  
https://www.m-system.co.jp/  
MODEL: R5T-DC4  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
LOCKING CLAMP  
18 (.71)  
38.5 (1.52)  
98.5 (3.88)  
TERMINAL COVER  
8.2 (.32)  
6–M3.5  
TERMINAL  
SCREWS  
4
5
2
6
3
7.2 (.28)  
POSITIONING GUIDE  
1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN OUTPUT STATUS  
LED INDICATOR LED  
• • • •  
Isolation  
Isolation  
INTERNAL BUS A  
1
2
Communication  
Circuit  
1
2
3
4
5
6
Do 1  
*INTERNAL BUS B  
Do 2  
Control  
Circuit  
COM1  
Do 3  
3
4
INTERNAL POWER  
Do 4  
COM2  
*For dual redundant communication.  
Note: Italic typed numbers correspond to the LEDs on the front panel.  
Specifications are subject to change without notice.  
R5T-DC4 SPECIFICATIONS  
ES-6129 Rev.9 Page 3/3  
https://www.m-system.co.jp/  

相关型号:

R5T-PA22S

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PA22S/Q

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PA22W

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PA22W/Q

Remote I/O R5 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R5T-PC22S

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22S/Q

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22W

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PC22W/Q

Remote I/O R5 Series PULSE OUTPUT MODULE
MSYSTEM

R5T-PT1S

Remote I/O R5 Series
MSYSTEM

R5T-PT1S/Q

Remote I/O R5 Series
MSYSTEM

R5T-PT1W

Remote I/O R5 Series
MSYSTEM

R5T-PT1W/Q

Remote I/O R5 Series
MSYSTEM