R5T-DV4W/Q [MSYSTEM]
Remote I/O R5 Series;型号: | R5T-DV4W/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R5 Series |
文件: | 总3页 (文件大小:117K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R5T-DC4
steel
Remote I/O R5 Series
Isolation: Do1 or Do2 to Do3 or Do4 to internal bus or
internal power
DISCRETE OUTPUT MODULE
(screw terminal block; relay contact output, 4 points)
18 (.71)
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
Output status indicator: Red LED; turns on with the outputs
ON.
90
(3.54)
OUTPUT SPECIFICATIONS
Output: Relay contact, 4 points
137
(5.39)
Common: Every 2 points
mm (inch)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
MODEL: R5T–DC4[1][2]
ORDERING INFORMATION
Code number: R5T-DC4[1][2]
Mechanical life: 2 × 10 cycles (rate 300/min.)
7
When driving an inductive load, external contact protection
and noise quenching recommended.
Specify a code from below for each of [1] and [2].
(e.g. R5T-DC4W/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 110 g (0.24 lb)
NO. OF CHANNELS
4: 4-point outputs
[1] COMMUNICATION MODE
S: Single
PERFORMANCE
Data allocation: 1
W: Dual
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (Do 1 or Do 2 to
Do 3 or Do 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R5-BS)
Output: M3.5 screw terminal block (torque 0.8 N·m)
Internal power: Via the base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless
R5T-DC4 SPECIFICATIONS
ES-6129 Rev.9 Page 1/3
https://www.m-system.co.jp/
MODEL: R5T-DC4
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (output)
Pollution Degree 2
Output to internal bus or internal power – Basic insulation
(300 V)
RoHS Directive
FUNCTIONS
Output hold function:
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
If both are in error, the module holds the signal and stands
by until one of the communications recovers.
At the startup, it outputs OFF until the communication is
established and normal data is received.
EXTERNAL VIEW
FRONT VIEW
SIDE VIEW
RUN LED
RUN
1
1 2 3 4 5 6 7 8
Status Indicator LED
2
3
4
DO NOT USE
4
5
6
1
2
3
R5T-DC4 SPECIFICATIONS
ES-6129 Rev.9 Page 2/3
https://www.m-system.co.jp/
MODEL: R5T-DC4
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
LOCKING CLAMP
18 (.71)
38.5 (1.52)
98.5 (3.88)
TERMINAL COVER
8.2 (.32)
6–M3.5
TERMINAL
SCREWS
4
5
2
6
3
7.2 (.28)
POSITIONING GUIDE
1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN OUTPUT STATUS
LED INDICATOR LED
•
• • • •
Isolation
Isolation
INTERNAL BUS A
1
2
Communication
Circuit
1
2
3
4
5
6
Do 1
*INTERNAL BUS B
Do 2
Control
Circuit
COM1
Do 3
3
4
INTERNAL POWER
Do 4
COM2
*For dual redundant communication.
Note: Italic typed numbers correspond to the LEDs on the front panel.
Specifications are subject to change without notice.
R5T-DC4 SPECIFICATIONS
ES-6129 Rev.9 Page 3/3
https://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明