R8-NC3-R/Q [MSYSTEM]
Remote I/O R8 Series POWER/NETWORK MODULE;型号: | R8-NC3-R/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R8 Series POWER/NETWORK MODULE |
文件: | 总5页 (文件大小:306K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R8-NC3
Remote I/O R8 Series
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
POWER/NETWORK MODULE
(CC-Link Ver.2.00; for 64-point analog signals)
Functions & Features
• Free combination of analog and discrete I/O
• Space-saving
PACKAGE INCLUDES...
• Protective cover
Typical Applications
GENERAL SPECIFICATIONS
Connection
• Remote I/O for DCS and PLC
•Power input: Tension clamp (Front Twin connection)
Applicable wire size: 0.2 - 2.5 mm
2
Stripped length: 10 mm
•CC-Link: Tension clamp (Front Twin connection)
Applicable wire size: 0.2 - 1.5 mm
2
Stripped length: 10 mm
•Internal bus, intenal power, exc. supply: Via connector
Max. number of I/O modules: 16
(Max. consumption current of I/O modules: 1.6 A)
Isolation: CC-Link to internal bus or internal power or power
input to exc. supply to FE1
MODEL: R8–NC3–R[1]
Status indicators: Power, Run, Error, SD, RD
Data allocation: Mode 1, 2
ORDERING INFORMATION
• Code number: R8-NC3-R[1]
Specify a code from below for [1].
(e.g. R8-NC3-R/Q)
CC-Link COMMUNICATION
Protocol: CC-Link. Conforms to Version 2.00
Device type: Remote device station
• Specify the specification for option code /Q
(e.g. /C01)
Required nodes: 4 (112 I/O points, 16 words) × m (m =
Cyclic expansion setting)
Network cable: CC-Link cable designated by Mitsubishi
Electric
I/O TYPE
NC3: CC-Link
Cyclic expansion: 2, 4 (Function selected with DIP SW)
Station address setting: Rotary switch; 1 to 64
Baud rate setting: Rotary switch
POWER INPUT
DC power
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps
Terminating resistor: Built-in (DIP Switch, default: disable)
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
INSTALLATION
Power consumption
[1] OPTIONS
blank: none
•DC: Approx. 12 W 24 V DC (@ internal power max. current
1.6 A) )
/Q: With options (specify the specification)
Internal power supply (power supply for I/O module):
• DC power supply: 5 V DC
• Current capacity: 1.6 A
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Excitation supply output (excitation for I/O module)
•DC: 24 V DC ±10 %
•Operational current: 10 A
/C02: Polyurethane coating
(From power supply (exitation supply) connector, via
connector for internal bus, supplied to each I/O module.
Power output current consumption must be under
R8-NC3 SPECIFICATIONS
ES-9726 Rev.5 Page 1/5
http://www.m-system.co.jp/
MODEL: R8-NC3
operational current.)
Operating temperature: 0 to 55°C (32 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 180 g (0.40 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(CC-Link to internal bus or internal power or power input to
exc. supply to FE1)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
EXTERNAL VIEW
FRONT VIEW
TOP VIEW
Status Indicator LED
Station Address Setting
Rotary SW
DA
DG
Baud Rate Setting
Rotary SW
DB
SLD
FE
Internal Bus Connector
CC-Link Connector
Function Setting
DIP SW
Connector for
Power Supply and
Excitation Supply
8
7
6
5
4
3
2
1
Terminator
DIP SW
On
Miniature Jack Connector for Configuration
■ STATUS INDICATOR LED
ID
COLOR FUNCTION
ON when the internal 5V power is in normal
status.
Green ON with normal communication *1
Red ON when abnormal data is received.
Power Green
Run
Error
SD
Green ON with data transmitting
Green ON with data receiving
RD
*1. Run LED turns off when no command is received from
the master device.
R8-NC3 SPECIFICATIONS
ES-9726 Rev.5 Page 2/5
http://www.m-system.co.jp/
MODEL: R8-NC3
CONNECTION DIAGRAMS
■ MASTER CONNECTION
MASTER UNIT
R8-NC3
R8-NC3
TERMINATOR
blue
*1
DA
DB
DA
DB
DA
white
yellow
DB
DG
SLD
FE
DG
SLD
FG
DG
SLD
FE
*1. Turn on the terminator DIP switch to activate the internal terminating resistor.
■ POWER SUPPLY, EXCITATION SUPPLY CONNECTOR TERMINAL ASSIGNMENT
Printed-circuit board connector (Phoenix Contact)
Unit side connector: MSTBV2,5/5-GF-5,08AU
Cable side connector: TFKC2,5/5-STF-5,08AU
PIN
ID
FUNCTION
1
2
3
4
5
No.
1
24V Power supply 24V DC
2
0V
+
Power supply 0V DC
3
Excitation supply 24V DC
Excitation supply 0V DC
4
−
5
FE1 Grounding
■ NETWORK CONNECTOR ASSIGNMENT
Printed-circuit board connector (Phoenix Contact)
Unit side connector:
MC1,5/5-GF-3,5
Cable side connector: TFMC1,5/5-STF-3,5
PIN
ID
FUNCTION
DA
1
2
3
4
5
No.
1
DA
DG
DB
2
DG
DB
3
4
SLD Shield
FE
Functional earth
5
R8-NC3 SPECIFICATIONS
ES-9726 Rev.5 Page 3/5
http://www.m-system.co.jp/
MODEL: R8-NC3
EXTERNAL DIMENSIONS unit: mm (inch)
■UNIT
50 (1.97)
[3 (.12)]
55 (2.17)
[4 (.16)]
DIN RAIL
(35 mm wide)
■PROTECTIVE COVER
5 (.20)
50 (1.97)
R8-NC3 SPECIFICATIONS
ES-9726 Rev.5 Page 4/5
http://www.m-system.co.jp/
MODEL: R8-NC3
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.
STATUS
INDICATOR
ROTARY SW
DIP SW
Isolation
Control
Circuit
Comm.
Circuit
DA
DG
DB
INTERNAL BUS
TO OTHER
CC-Link
DEVICES
SLD
FE
JACK
PC CONFIGURATION JACK
+24V
Power
Circuit
(No isolation)
INTERNAL
POWER (5V)
POWER
0V
+
EXC. SUPPLY (24V)
EXC. SUPPLY
−
FE1
Specifications are subject to change without notice.
R8-NC3 SPECIFICATIONS
ES-9726 Rev.5 Page 5/5
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明