RM4UA31MW [SCHNEIDER]

DPDT, Momentary, 0.005A (Coil), 240VDC (Coil), 1200mW (Coil), AC/DC Input, DIN Rail/Panel Mount,;
RM4UA31MW
型号: RM4UA31MW
厂家: SCHNEIDER ELECTRIC    SCHNEIDER ELECTRIC
描述:

DPDT, Momentary, 0.005A (Coil), 240VDC (Coil), 1200mW (Coil), AC/DC Input, DIN Rail/Panel Mount,

光电二极管 继电器
文件: 总11页 (文件大小:162K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Product datasheet  
RM4UA31MW  
Characteristics  
voltage measurement relay RM4-U - range  
0.05..5 V - 24..240 V AC DC  
Commercial status  
Discontinued: 31 December 2016  
End-of-service: 31 December 2016  
RM4UA31MW has not been replaced. Please contact your  
customer care centre for more information.  
Main  
Range of product  
Product or component type  
Relay type  
Zelio Control  
Industrial measurement and control relays  
Voltage measurement relay  
RM4U  
Relay name  
Relay monitored parameters  
Time delay  
Overvoltage or undervoltage detection  
Adjustable 0.05...30 s  
Power consumption in VA  
Measurement range  
1.5…3.3 VA AC  
0.05...0.5 V voltage AC 50/60 Hz  
0.3...3 V voltage AC 50/60 Hz  
0.5...5 V voltage AC 50/60 Hz  
0.05...0.5 V voltage DC  
0.3...3 V voltage DC  
0.5...5 V voltage DC  
Complementary  
Maximum switching voltage  
440 V AC  
[Us] rated supply voltage  
24...240 V AC 50/60 Hz +/- 5 %  
24...240 V DC  
Maximum power consumption in W  
Output contacts  
1.2 W DC  
2 C/O  
Internal input resistance  
71000 Ohm  
43000 Ohm  
6600 Ohm  
Permissible continuous overload  
Permissible non repetitive overload  
80 V  
20 V  
60 V  
100 A for <= 1 s  
25 A for <= 1 s  
80 A for <= 1 s  
Setting accuracy of the switching  
threshold  
+/-5 %  
Switching threshold drift  
<= 0.06 % per degree centigrade depending permissible ambient air temperature  
<= 0.5 % within the supply voltage range (0.85...1.1 Un)  
Setting accuracy of time delay  
Time delay drift  
10 P  
<= 0.07 % per degree centigrade depending on the rated operational temperature  
<= 0.5 % within the supply voltage range (0.85...1.1 Un)  
Oct 16, 2019  
1
Hysteresis  
5…30 % adjustable of voltage threshold setting  
Quality labels  
CE  
Overvoltage category  
[Ui] rated insulation voltage  
Operating voltage tolerance  
Supply disconnection value  
Operating position  
III conforming to IEC 60664-1  
500 V conforming to IEC  
0.85...1.1 Uc  
> 0.1 Uc  
Any position without  
Connections - terminals  
Screw terminals, 2 x 1.5 mm²flexible with cable end  
Screw terminals, 2 x 2.5 mm²flexible without cable end  
Tightening torque  
0.6…1.1 N.m  
30000000 cycles  
8 A  
Mechanical durability  
[Ith] conventional free air thermal  
current  
[Ie] rated operational current  
2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/1991  
2 A at 70 °C 24 V DC-13 conforming to VDE 0660  
3 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/1991  
3 A at 70 °C 115 V AC-15 conforming to VDE 0660  
3 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/1991  
3 A at 70 °C 24 V AC-15 conforming to VDE 0660  
3 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/1991  
3 A at 70 °C 250 V AC-15 conforming to VDE 0660  
0.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/1991  
0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660  
0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991  
0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660  
Switching capacity in mA  
Switching voltage  
Contacts material  
Width  
10 mA at 12 V  
250 V AC  
90/10 silver nickel contacts  
22.5 mm  
Net weight  
0.08 kg  
Compatibility code  
RM4  
Environment  
Electromagnetic compatibility  
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2  
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2  
Standards  
EN/IEC 60255-6  
Product certifications  
GL  
UL  
CSA  
Directives  
73/23/EEC - low voltage directive  
89/336/EEC - electromagnetic compatibility  
Ambient air temperature for storage  
Ambient air temperature for operation  
Relative humidity  
-40…85 °C  
-20…65 °C  
15…85 % 3K3 conforming to IEC 60721-3-3  
0.35 ms (f= 10…55 Hz) conforming to IEC 60068-2-6  
15 gn for 11 ms conforming to IEC 60068-2-27  
Vibration resistance  
Shock resistance  
IP degree of protection  
IP20 (terminals) conforming to IEC 60529  
IP50 (casing) conforming to IEC 60529  
Pollution degree  
3 conforming to IEC 60664-1  
Dielectric test voltage  
2.5 kV  
4.8 kV  
Non-dissipating shock wave  
Resistance to electrostatic discharge  
6 kV contact conforming to IEC 61000-4-2 level 3  
8 kV air conforming to IEC 61000-4-2 level 3  
Resistance to electromagnetic fields  
Resistance to fast transients  
10 V/m conforming to IEC 61000-4-3 level 3  
2 kV conforming to IEC 61000-4-4 level 3  
2 kV: level 3 conforming to IEC 61000-4-5  
Protection against electric shocks  
Disturbance radiated/conducted  
CISPR 22 - class A  
CISPR 11 group 1 - class A  
2
Contractual warranty  
Warranty  
18 months  
3
Product datasheet  
RM4UA31MW  
Dimensions Drawings  
Voltage Measurement Relays  
Dimensions  
4
Product datasheet  
RM4UA31MW  
Mounting and Clearance  
Voltage Measurement Relays  
Rail mounting  
Screw fixing  
5
Product datasheet  
RM4UA31MW  
Connections and Schema  
Voltage Measurement Relays  
RM4UA01 and RM4UA02 Wiring Diagram  
A1-A2  
Supply voltage  
B1, B2, B3V,oCltages to be measured (see table below)  
Connection and current values to be measured  
RM4UA•1  
RM4UA•2  
B1-C  
B2-C  
B3-C  
B1-C  
B2-C  
B3-C  
0.05…0.5 V  
0.3…3 V  
0.5…5 V  
1…10 V  
5…50 V  
10…100 V  
RM4UA03 Wiring Diagram  
A1-A2  
Supply voltage  
B2, B3, CVoltages to be measured (see table below)  
Connection and current values to be measured  
B2-C  
B3-C  
30…300 V  
50…500 V  
RM4UA31 and RM4UA32 Wiring Diagram  
A1-A2  
Supply voltage  
B1, B2, B3V,oCltages to be measured (see table below)  
Connection and current values to be measured  
RM4UA•1  
B1-C  
B2-C  
B3-C  
B1-C  
0.05…0.5 V  
0.3…3 V  
0.5…5 V  
1…10 V  
RM4UA•2  
6
Connection and current values to be measured  
B2-C  
B3-C  
5…50 V  
10…100 V  
RM4UA33 Wiring Diagram  
A1-A2  
Supply voltage  
B2, B3, CVoltages to be measured (see table below)  
Connection and current values to be measured  
B2-C  
B3-C  
30…300 V  
50…500 V  
7
Product datasheet  
RM4UA31MW  
Connections and Schema  
Voltage Measurement Relays  
Application Scheme  
Example: overspeed monitoring (undervoltage function)  
(1)  
(2)  
Tachogenerator  
Overspeed  
8
Product datasheet  
RM4UA31MW  
Performance Curves  
Electrical Durability and Load Limit Curves  
AC Load  
Curve 1: Electrical durability of contacts on resistive load in millions of operating cycles  
X
Y
Current broken in A  
Millions of operating cycles  
Curve 2: Reduction factor k for inductive loads (applies to values taken from durability Curve 1)  
X
Y
Power factor on breaking (cos φ)  
Reduction factor K  
DC Load  
Load limit curve  
X
Y
1
2
3
Current in A  
Voltage in V  
L/R = 20 ms  
L/R with load protection diode  
Resistive load  
9
Product datasheet  
RM4UA31MW  
Technical Description  
Function Diagram  
Overvoltage Control  
Function “>”  
Legend  
t Time delay  
U A1-A2 Supply voltage  
US1 Setting voltage threshold  
US2 Voltage measured  
15-18, 15-16; 25-28, 25-26 Output relays connections  
Relay status: black color = energized.  
10  
Product datasheet  
RM4UA31MW  
Technical Description  
Function Diagram  
Undervoltage Control  
Function “<”  
Legend  
t Time delay  
U A1-A2 Supply voltage  
US1 Setting voltage threshold  
US2 Voltage measured  
15-18, 15-16; 25-28, 25-26 Output relays connections  
Relay status: black color = energized.  
11  

相关型号:

RM4UA33MW

Power/Signal Relay, DPDT, Momentary, 0.01A (Coil), 12VDC (Coil), 120mW (Coil), 250VDC (Contact), DC Input, Panel Mount
SCHNEIDER

RM4V1

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4WK

暂无描述
SANKEN

RM4Y

SILICON RECTIFIER DIODES
EIC

RM4Y

Rectifier Diodes
SANKEN

RM4YV

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YV1

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YV3

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YVO

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YW

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YWK

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN

RM4YWS

Rectifier Diode, 1 Phase, 1 Element, 3A, Silicon,
SANKEN