TPS4000-24 [TDK]
AC-DC电源;型号: | TPS4000-24 |
厂家: | TDK ELECTRONICS |
描述: | AC-DC电源 |
文件: | 总5页 (文件大小:1752K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
TPS4000 Series
https://product.tdk.com/en/power/tps
www.emea.lambda.tdk.com/tps
4080W 3-Phase Input Industrial Power Supplies
The TPS series industrial AC-DC power supplies offer output power up to 4,080W in a 2U high package with 3 phase supply input. Features include voltage
and current programming, remote on/off, remote sense, a standby supply, PMBus™ communication, built in ORing FET and wide operating temperature
range of -40°C to +70°C. The TPS4000 is also designed to meet MIL-STD-461F/G RE102 EMI and MIL-STD-810F vibration and shock.
Features
Benefits
• 400/440/480Vacꢀ(Nominal)ꢀ3ꢀPhaseꢀDeltaꢀorꢀWye
• Fully Regulated, Wide Range Voltage Adjustment
• Voltage and Current Programming
•ꢀ-40°Cꢀ(startꢀup)ꢀtoꢀ+70°Cꢀoperation
•ꢀ92%ꢀTypicalꢀEfficiency
• Global Use
• Versatile Application
• Flexible Control and Adjustment
• Suitable for Rugged Environments
• Less Energy Used
• PMBus™ Communication
• Remote Output Programming and Monitoring
• Suitable for N + 1 Redundancy
• Built in ORing FET for parallel operation
Model Selector
Nominal Output
Voltage
Adjustment
Max
Current
(A)ꢀ
Max
Power
(W)ꢀ
Max Current
at Nominal Voltage
(A)ꢀ
Max Power
at Nominal Voltage
(V)
Model
ꢀ ꢀ
Range
(V)ꢀ
(V)ꢀ
TPS4000-24ꢀ
24ꢀ
19.2ꢀ-ꢀ28.5ꢀ
166ꢀ
4000ꢀ
170ꢀ
4080
TPS4000-48
48
38.4 - 58
83.3
4000
85
4080
*Wider range adjustment as stated on the UL safety files are possible, although some parameters might not meet some of the listed specifications.
Related Products
Type
Part Number
Description
EMCꢀfilterꢀ
RTMN-5020ꢀ
Highꢀattenuationꢀ20Aꢀ500Vacꢀ3-phaseꢀinputꢀtwoꢀstageꢀfilterꢀ
ꢀ
Specification
Model
TPS4000
Input
ꢀ InputꢀVoltageꢀrangeꢀ
ꢀ InputꢀFrequencyꢀ
ꢀ
ꢀ
ꢀ
Vꢀ
Hzꢀ
Aꢀ
Aꢀ
W
mAꢀ
-ꢀ
350ꢀ-ꢀ528,ꢀDeltaꢀorꢀWyeꢀ3ꢀphaseꢀ(Note:ꢀSafetyꢀcertifiedꢀforꢀ400-480Vacꢀonly)ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
47ꢀ-ꢀ63ꢀ(Note:ꢀSafetyꢀcertifiedꢀforꢀ50ꢀtoꢀ60Hzꢀonly)ꢀ
8ꢀperꢀphaseꢀ(steadyꢀstate)ꢀ
ꢀ
ꢀ
ꢀ InputꢀCurrentꢀ(AtꢀnominalꢀVin)ꢀ
ꢀ
ꢀ InrushꢀCurrentꢀatꢀ400-480Vacꢀ(ColdꢀStart)ꢀ
<25ꢀperꢀphaseꢀ(excludingꢀinitialꢀfilterꢀcapacitorꢀchargingꢀ<2ms)ꢀ
ꢀ
Dropped Phase Power
1600. Not recommended for long term operation
ꢀ LeakageꢀCurrentꢀ
ꢀ
ꢀ
<3ꢀ
ꢀ
ꢀ
ꢀ PowerꢀFactorꢀ(400-480Vac)ꢀ
Harmonic Compliance
ꢀ HoldꢀUpꢀTimeꢀ(typ)ꢀ
ꢀ Efficiencyꢀ(Typical)ꢀ
ꢀ Conductedꢀ&ꢀRadiatedꢀEMIꢀ
ꢀ Immunityꢀ
0.92ꢀtypicalꢀatꢀratedꢀload,ꢀnominalꢀVinꢀ
ꢀ
ꢀ
ꢀ
ꢀ
-
Not applicable
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
msꢀ
-ꢀ
>10ꢀatꢀ80%ꢀofꢀratedꢀcurrent,ꢀnominalꢀinput/outputꢀvoltageꢀ ꢀ
92%ꢀ
EN55032-AꢀConductedꢀandꢀradiatedꢀ(Inꢀendꢀsystem)ꢀ
ꢀ
ꢀ
-ꢀ
ꢀ
-ꢀ
EN61000,ꢀseeꢀimmunityꢀtable.ꢀMIL-STD-461F/GꢀCS101,ꢀCS114ꢀ(ArmyꢀGround),ꢀCS115,ꢀCS116ꢀ
ꢀ
ꢀ LineꢀDipꢀ
-ꢀ
SEMIꢀF47-0706ꢀatꢀ480Vacꢀnominalꢀ(CriteriaꢀB)ꢀ
ꢀ
ꢀ
ꢀ SafetyꢀCertificationsꢀandꢀMarkingsꢀ
-ꢀ
IEC/UL/CSA/EN62368-1,ꢀ60950-1,ꢀCEꢀandꢀUKCAꢀMarks
1
TPS4000 Series
Immunity
Test
ESD
Standard
Test Level
Criteria
B
Notes
EN61000-4-2
±8 kV air discharge,
±4 kV contact discharge
See test report
Radiated Susceptibility
EN61000-4-3
3 V/m from 80-1000 MHz
A
B
See test report
See test report
See test report
See test report
Seeꢀtestꢀreport
Seeꢀtestꢀreport
ꢀ ꢀ
ꢀ
(80%ꢀAMꢀatꢀ1kHz)ꢀ
Electrical Fast Transient Burst
Surge
EN61000-4-4
Power line pulses of ± 1 kV;
I/O line pulses of ± 0.5 kV
EN61000-4-5
3±2kV common mode,
B
±1kV differential mode
Conducted Susceptibility
EN61000-4-6
3 Vrms, 150 kHz - 80 MHz
A
ꢀ ꢀ
ꢀ
1ꢀkHzꢀ80%ꢀAMꢀ
ꢀ Magneticꢀfieldsꢀ
ꢀ ꢀ
EN61000-4-8ꢀ
ꢀ
Inductiveꢀloopꢀatꢀ50ꢀHz,ꢀ
Aꢀ
toꢀ30.0ꢀampsꢀ(rms)ꢀperꢀmeterꢀ&ꢀ300.0ꢀampsꢀ(rms)ꢀperꢀmeterꢀ
VoltageꢀDipsꢀofꢀ30%ꢀandꢀ>95%;ꢀInterruptionsꢀofꢀ>95%.ꢀ
ꢀ VoltageꢀDipsꢀandꢀInputꢀInterruptionsꢀ EN61000-4-11ꢀ
Bꢀ/ꢀCꢀ
Specification
Model
TPS4000
Output
ꢀ LineꢀRegulationꢀ
ꢀ LoadꢀRegulationꢀ
ꢀ TotalꢀRegulationꢀ
ꢀ WarmꢀUpꢀDriftꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
%ꢀ
<0.25ꢀ
<0.5ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
%ꢀ
%ꢀ
<1.75ꢀ
<0.2ꢀ
%ꢀ
ꢀ TemperatureꢀStabilityꢀ
ꢀ TemperatureꢀCoefficientꢀ
ꢀ Rippleꢀ&ꢀNoiseꢀ(pk-pk)ꢀMaximumꢀ
Minimum Load
-ꢀ
0.05%ꢀofꢀratedꢀVoutꢀforꢀ8hrsꢀafterꢀ30minꢀwarmupꢀ
200ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ppm/°Cꢀ
ꢀ
ꢀ
mVꢀ
A
%ꢀ
%ꢀ
-
24Vꢀmodel:ꢀ240mV,ꢀ48Vꢀmodel:ꢀ480mVꢀ
None
ꢀ OvercurrentꢀProtectionꢀ
ꢀ OvervoltageꢀProtectionꢀ
Overtemperature Protection
Fan Fail
ꢀ
ꢀ
Adjustableꢀ(70-105%ꢀofꢀmaximumꢀratedꢀcurrent).ꢀConstantꢀcurrentꢀstyle.ꢀꢀ
ꢀ
ꢀ
115%ꢀofꢀoutputꢀvoltageꢀsetꢀpointꢀ(tracking).ꢀꢀCycleꢀACꢀorꢀuseꢀtheꢀremoteꢀon/offꢀtoꢀresetꢀ
Internal thermostat. Automatic reset
-
Blocked or fan failure detection. Cycle AC input or use PMBus to reset
Compensates for a total of 1V cable drop
Remote Sense
-
ꢀ RemoteꢀOn/Offꢀ
Voltage Programming
Overcurrent Programming
ꢀ DCꢀGoodꢀ
ꢀ
-ꢀ
-
Enableꢀorꢀinhibitꢀ(selectable)ꢀ
ꢀ
ꢀ
0 - 5V external voltage adjusts the output from Vout max to Vout min
0 - 5V external voltage adjusts the current limit from Iout max to Iout min
OpenꢀCollector,ꢀONꢀwhenꢀoutputꢀisꢀaboveꢀ90%ꢀofꢀoutputꢀsetꢀpointꢀ(tracking)ꢀ
-
ꢀ
ꢀ
ꢀ
-ꢀ
-ꢀ
-ꢀ
-
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ ACꢀFailꢀ
OpenꢀCollector,ꢀONꢀwhenꢀACꢀinputꢀisꢀaboveꢀ340Vac,ꢀtheꢀloadꢀisꢀ>30%ꢀandꢀunitꢀisꢀenabledꢀ
Openꢀcollector,ꢀOFFꢀduringꢀnormalꢀoperation,ꢀactiveꢀlowꢀduringꢀdroppedꢀphaseꢀstate.ꢀꢀLoadꢀ>30%ꢀ
11.2 - 12.5V, 0.3A
ꢀ DroppedꢀPhaseꢀWarningꢀ
Standby Voltage
ꢀ Indicatorsꢀ
ꢀ
ꢀ
-ꢀ
-ꢀ
-
GreenꢀLEDsꢀindicatesꢀDCꢀisꢀOKꢀandꢀACꢀisꢀON.ꢀBlinkingꢀred/greenꢀduringꢀdroppedꢀphaseꢀ(Loadꢀ>30%)ꢀ ꢀ
Singleꢀwireꢀcurrentꢀshare,ꢀupꢀtoꢀ8ꢀunits.ꢀꢀ(InternalꢀORingꢀMOSFETsꢀareꢀfitted).ꢀDerateꢀtoꢀ90%ꢀoutputꢀpowerꢀꢀ
Possible, see installation manual
ꢀ ParallelꢀOperationꢀ
Series Operation
2
TPS4000 Series
Specification
Model
TPS4000
Environmental
ꢀ OperatingꢀTemperatureꢀ(-40°Cꢀstart-up)ꢀꢀ
°Cꢀ
-10ꢀtoꢀ+70,ꢀderateꢀlinearlyꢀfromꢀ100%ꢀtoꢀ80%ꢀloadꢀfromꢀ50ꢀtoꢀ60,ꢀandꢀfromꢀ80%ꢀtoꢀ55%ꢀatꢀ70
ꢀ ꢀ
Storage Temperature
ꢀ
ꢀ
(Atꢀ-40°Cꢀaꢀ10ꢀminꢀwarmꢀupꢀatꢀ80%ꢀloadꢀisꢀrequiredꢀtoꢀmeetꢀspecification)
°C
-40 to +85
ꢀ Humidityꢀ(nonꢀcondensing)ꢀ
Pollution Degree
ꢀ
%RHꢀ
10ꢀ-ꢀ95%RH
-
-
PD 2
Cooling
Internal variable speed fan
Altitude
m
4,000
ꢀ WithstandꢀVoltageꢀ(Forꢀ1ꢀminute)ꢀ
ꢀ IsolationꢀResistanceꢀ
ꢀ Vibrationꢀ(Operating)ꢀ
Shock
ꢀ
ꢀ
ꢀ
Vacꢀ
MΩꢀ
-ꢀ
InputꢀtoꢀGroundꢀ2,000Vac,ꢀInputꢀtoꢀOutputꢀ3,000Vac,ꢀOutputꢀtoꢀGroundꢀ500Vdcꢀ ꢀ
ꢀ
ꢀ
>100ꢀatꢀ25°C,ꢀ70%RHꢀ&ꢀ500VDCꢀꢀ
ꢀ
DesignedꢀtoꢀmeetꢀMIL-STD-810F,ꢀMethodꢀ514.5,ꢀProcꢀI,ꢀCategoryꢀ1,ꢀ10ꢀ
ꢀ
-
Designed to meet MIL-STD-810F, Method 516.5, Procedure I, IV & VI
Other
ꢀ Weightꢀ(Typ)ꢀ
ꢀ
ꢀ
ꢀ
gꢀ
mmꢀ
Inchesꢀ
-
4,000ꢀ
ꢀ
ꢀ
ꢀ Sizeꢀ(WxHxD)ꢀ
107ꢀxꢀ84.4ꢀxꢀ335ꢀ(excludingꢀoutputꢀbusbars)ꢀ
4.21ꢀxꢀ3.33ꢀxꢀ13.2ꢀ(excludingꢀoutputꢀbusbars)ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ Sizeꢀ(WxHxD)ꢀ
Mating Connectors
Signal: Housing, JST PHDR-20VS, Crimp terminals, SPHD-001T-P0.5
PMBusꢀshuntꢀjumper:ꢀSamtecꢀ2SN-BK-Gꢀ
ꢀ ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
MTBF - Telcordia SR-332 issue 3
Warranty
hrs
yrs
250,000 hours Method 1, Ground Benign, 25C, nominal input
3 years
PMBus Functions
Output Voltage Monitoring
Output Current Monitoring
Internal Temperature Monitoring
Remote On/Off Programming
Remote Voltage Programming
Remote Overcurrent Programming
Fault Clearing
Reading Manufacturing Related Data
Notes
Seeꢀwebsiteꢀforꢀdetailedꢀspecifications,ꢀtestꢀmethodsꢀandꢀinstallationꢀmanualꢀ
ꢀ
Derating Curve
3
TPS4000 Series
Outline Drawing
4
TPS4000 Series
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +33 1 60 12 71 65
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
tla.powersolutions@tdk.com
www.us.lambda.tdk.com
tlf.fr.powersolutions@tdk.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
tlf.it.powersolutions@tdk.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
tlf.nl.powersolutions@tdk.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
tlg.powersolutions@tdk.com
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
tlc.powersolutions@tdk.com
www.lambda.tdk.com.cn
Austria Sales Office
Tel: +43 2256 655 84
tlg.at.powersolutions@tdk.com
TDK-Lambda Singapore Pte Ltd.
Tel: +65 6251 7211
tls.marketing@tdk.com
www.sg.lambda.tdk.com
www.emea.lambda.tdk.com/at
Switzerland Sales Office
Tel: +41 44 850 53 53
tlg.ch.powersolutions@tdk.com
www.emea.lambda.tdk.com/ch
TDK India Private Limited, Power Supply Division
Tel: +91 80 4039-0660
mathew.philip@tdk.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
tlg.dk.powersolutions@tdk.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
tlu.powersolutions@tdk.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
tli.powersolutions@tdk.com
www.emea.lambda.tdk.com/il-en
For Additional Information, please visit
https://product.tdk.com/en/power/
TPS4000_260734 April 7th, 2023 V3
5
TPS4000 Series
相关型号:
TPS40000DGQRG4
Low Input (2.25V-5.5V) 300 kHz Frequency, Synchronous Buck Controller, Source Only 10-MSOP-PowerPAD -40 to 85
TI
TPS40001DGQR
2.25 to 5.5V input, 300kHz, synchronous buck controller with Predictive Gate Drive™ Technology 10-HVSSOP -40 to 85
TI
©2020 ICPDF网 联系我们和版权申明