EDS6-119 [FUJI]

E SERIESE ELECTROMAGNETIC FLOWMETER(INTEGRAL TYPE); Ë SERIESE电磁流量计(一体型)
EDS6-119
型号: EDS6-119
厂家: FUJI ELECTRIC    FUJI ELECTRIC
描述:

E SERIESE ELECTROMAGNETIC FLOWMETER(INTEGRAL TYPE)
Ë SERIESE电磁流量计(一体型)

文件: 总12页 (文件大小:200K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
E SERIESE ELECTROMAGNETIC FLOWMETER  
(INTEGRAL TYPE)  
DATA SHEET  
FME1, 2  
The electromagnetic flowmeter is an instrument to measure  
the volumetric flow rate of liquid simply by applying a mag-  
netic field from the outside utilizing the fact that an electric  
conductor which crosses a magnetic field at a certain velocity  
causes voltage to be induced in proportion to the velocity,  
which is known as Faraday’s law.  
This flowmeter is designed with the latest electronics tech-  
nology, realizing a compact and light-weight structure and  
measurement with high accuracy.  
FEATURES  
1. High accuracy  
When conductivity is above 5 µS/cm, flow rate of liquid  
can be measured regardless of density and viscosity. The  
measurement accuracy is as high as 0.6% of rate.  
2. Free power supply  
The flowmeter operates on power supply 100 to 230V AC,  
50/60Hz.  
• Mounting method :  
3. Grounding electrode  
Mounted via flange insertion type on oppo-  
site (with Guide rings)  
··· 3A to 100A  
Use of the grounding electrode of Hasteroy C in the flow-  
meter allows installation without an earth ring.  
Note 1) Guide ring : A ring-shaped guide used for  
centering the sensor when a wafer type  
is mounted on the piping.  
Note 2) Flange with meter size 3A or 6A can be  
used for 15A.  
or flange mounting  
··· 15A to 300A  
4. Change of settings.  
The setting of various parameters can be changed from  
the outside of the case cover. Application of the supplied  
magnetic stick to the outside glass surface enables the  
setting to change without opening the case cover.  
5. Stable measurement of flow rate  
• Fluid pressure :  
A digital filter for pulsating or noisy flow signal, flow rate  
output low cut, and damping function allows flow rate  
measurement to be stabilized.  
0 to 2000kPa or flange operating pressure,  
whichever is lower.  
• Meter size and measurement range  
6. Self-diagnosis function  
See the following table for the full scale of  
measurable flow rate.  
Since self-diagnosis function is provided for empty detec-  
tion, trouble, and maloperation, the flowmeter can be  
used with safety.  
Min.measurement range Max. measurement range  
Meter size  
[m3/h]  
[m3/h]  
7. Simultaneous display of instantaneous flow and total  
flow 2-stage display with LCD backlight which is visible in  
the dark.  
3A Note 3)  
6A Note 3)  
15A  
0 to 0.012  
0 to 0.06  
0 to 0.3  
0 to 0.24  
0 to 1.2  
0 to 6.0  
25A  
0 to 0.6  
0 to 12.0  
0 to 36.0  
0 to 60.0  
0 to 180.0  
0 to 240.0  
0 to 600.0  
0 to 1080  
0 to 1800  
0 to 2400  
40A  
0 to 1.8  
50A  
0 to 3.0  
80A  
0 to 9.0  
SPECIFICATIONS  
100A  
0 to 12.0  
0 to 30.0  
0 to 54.0  
0 to 90.0  
0 to 120.0  
Detector  
150A Note 4)  
200A Note 4)  
250A Note 4)  
300A Note 4)  
• Measurement item :  
General-use industrial water, waste water,  
and other liquids with conductivity of more  
than 5µs/cm.  
Wafer type or flange type  
• Structure :  
Note 3) Meter size 3A and 6A : Wafer type only  
Note 4) Meter size 150A or more : Flange type only  
EDS6-119  
Aug.3, 2001  
Date  
FME1, 2  
Fluid temperature :  
Fault diagnosis function :  
Various faults can be diagnosed by hard-  
ware check and process check.  
Zero point adjustment :  
–25 to +130˚C (PFA, TFE lining)  
[˚C]  
130  
Zero point is automatically calibrated with  
key operation.  
Low cut :  
0 to 10% FS settable  
Momentary output can be cut to 0% at  
flow rate below the set cutoff point.  
Note) Output low cut and total low cut are  
set at the same value.  
50  
0
0% signal lock :  
-25  
[˚C]  
-20  
10  
25  
60  
Display and output can be locked to 0%  
with status input.  
Ambient tempertaure  
Filter :  
A digital filter is included in the converter  
especially for pulsating or noisy flow sig-  
nals.  
Ambient temperature Fluid temperature allowable range  
Material :  
Empty detection :  
Lining  
Tefron(PFA, TFE)  
Absence of liquid is detected and status  
Signal electrode  
Earth electrode  
Earth ring Note 2)  
signal is outputted only when diameter is  
more than 10A and conductivity is more  
than 20µS/cm.  
Hasteroy C-4 equivalent  
Flow switch : 0 to 130% FS  
Status signal is outputted by setting high/  
low limit flow.  
Dumping time constant :  
1 to 99.999 sec  
Density setting :  
Housing case  
Flange Note 3)  
Aluminum alloy  
SUS316 equivalent  
Available from 0.01 to 5.00g/cm3, and the  
weight of the fluid can also be indicated.  
Note 1) Materials of fluid wetted parts should be selected  
in consideration of erosion due to measuring fluid.  
Refer to the table of material selection on the at-  
tached sheet.  
Converter case :  
Aluminum alloy  
Wiring connection port :  
Note 2) For earth ring attachments, see CODE SYMBOLS.  
Note 3) Flange type only  
1
G /2 (with water-proof gland)  
Finish color : Silver, Lid ....Beige  
Protection class :  
IP67  
Conveter  
Input/output signal :  
Grounding : D-class grounding (100or less)  
Current output; 4 to 20mA DC  
Load rasistance 0 to 600Ω  
Pulse output; open-collector  
Standard performance  
Accuracy rating of display and pulse output :  
Capacity; 16 to 30V DC, 0.22A or less  
ON voltage; 2V or less  
Max. 5kHz  
Status output; open-collector  
Capacity: 16 to 30V DC, 0.22A or less  
ON voltage; 2V or less  
Flow velocity  
0.7m/s or more  
0.7m/s or less  
Accuracy  
±0.5% of rate  
0.0035  
±
100 % of rate  
Qv  
Qv : Measuring flow velocity  
Status input; voltage input  
Capacity: 16 to 30V DC  
Accuracy rating of analog output :  
Internal resistance: 2kΩ  
Flow velocity  
0.7m/s or more  
0.7m/s or less  
Accuracy  
±0.6% of rate  
0.0035  
Pulse output : Total pulses are outputted by setting total  
constant. Pulse width 0.1 to 2000ms is  
settable.  
Span setting : Flow rate full scale(FS) can be set by set-  
ting flow rate unit and flow rate value.  
Display cubic volume unit ; m3, L, mL  
Display time unit ; /d, /h, /min, /s  
Flow direction change :  
±
100+0.1 % of rate  
Qv  
Qv : Measuring flow velocity  
Power consumption :  
14VA or less  
Operating condition :  
Flow direction can be reversed in flow di-  
rection mode.  
Ambient temperature;  
–20 to 60˚C (Detector : PFA, TFE lining)  
Ambient humidity; 95% RH or less  
Power voltage; 100 to 230V AC +10%,  
-15%  
Power frequency; 50/60Hz  
(Note)  
Flow display : Real unit flow display, % display or user  
unit display is possible. Max 6 disits.  
Total display : Totaled volume can be displayed by set-  
ting the unit of cubic volume.  
Displayed cubic volume unit ; m3, L, mL  
Total value is held when power failure  
occurs.  
If ambient humidity exceeds 95% RH, se-  
lect a submersible type in FMB model.  
2
Length of straight pipe for installing the electromagnetic flowmeter  
The length of the up-stream/down-stream straight pipe of the flowmeter should be long enough to ensure accurate measure-  
ments. See below.  
1-1) Upstream reducer pipe  
2-1) Downstream reducer pipe  
Flowmeter  
Flowmeter  
Flowing direction  
Flowing direction  
Downstream straight pipe unnecessary  
5D  
1-2) Upstream diffuser pipe  
2-2) Downstream diffuser pipe  
Flowmeter  
Flowmeter  
Flowing direction  
Flowing direction  
5D  
Downstream straight pipe unnecessary  
1-3) Various upstream valves  
Flowing direction  
2-3) Various downstream valves  
Flowmeter  
Flowmeter  
Flowing direction  
Note)  
10D  
2 to 3D  
Note) "5D" with sluice valve fully open  
1-4) Upstream 90° bend  
2-4) Downstream 90° bend  
Flowmeter  
Flowmeter  
Flowing  
direction  
Flowing direction  
5D  
2 to 3D  
1-5) Upstream T-pipe  
2-5) Downstream T-pipe  
Flowmeter  
Flowmeter  
Flowing  
direction  
Flowing direction  
5D  
2 to 3D  
Minimum length of straight pipe between up-stream/down-stream joints and flowmeter.  
Note 1) D=diameter of measuring pipe.  
Note 2) Do not put any objects, which affect magnetic field, electromotive force and flow velocity profile, in the measuring pipe.  
Note 3) Use a straight pipe (2D to 3D) on the down-steam side, if the drift to the up-stream side is affected by installing valves,  
etc.  
3
FME1, 2  
Mounting posture of electromagnetic flowmeter  
The flowmeter can be installed vertically, horizontally, or at other angle. When installing, be sure to observe the following points.  
q The measuring pipe should always fill with fluid which flows in the piping.  
Fluid may not fill up the pipe.  
Air are apt to from.  
I
.  
H
N
Fluid may not  
fill up the pipe.  
Good  
.  
N
HF
.
Good  
Example of mounting posture  
Pump  
w The signal electrode should be at a level with the ground. And also signal electrode and ground electrode should always keep  
contact with fluid. If the signal electrode or the ground electrode is upper position against the fluid, correct measurements  
cannot be expected due to air bubbles on the fluid.  
Signal electrode  
Ground electrode  
Ground  
Ground  
< Good >  
< Good >  
Ground electrode  
Signal electrode  
Signal electrode  
Ground  
electrode  
Ground  
Ground  
< No good >  
< No good >  
Position of electrode  
How to connect the grounding cable contacting with measuring liquid.  
Since the electromagnetic flowmeter is provided with a ground electrode, flow rate of liquid can be measured without an earth  
ring. However, if stray potential exists in a pipeline, the potential in the pipeline may fluctuate.  
In this case, the earth ring (option) of the same material as signal electrode and ground electrode should be mounted on the  
upstream and downstream sides of the flowmeter to connect to the grounding terminal.  
For liquid that contains attachments or deposits, take the liquid contacting ground from the optional earth rings and metallic pipe  
(without lining).  
Grounding connection  
In case of metallic  
pipe without linging  
Without earth ring  
With earth ring  
4
CODE SYMBOLS  
Integral type electromagnetic flowmeter (wafer type)  
1
2
3
4
5
6
7
8
9
10 11 12 13  
14  
FME 1  
1 - H 0 A 0 -  
Description  
Meter size (5th code)  
S
A
C
D
T
E
F
G
3A  
6A  
15A  
25A  
40A  
50A  
80A  
100A  
Lining material (6th code)  
T
P
TFE (adhesive Tefron) : applied for meter size 15A to 100A  
PFA (mold Tefron) : applied for meter size 3A to 6A  
Earth ring material (7th code)  
0
None  
H
Hasteroy C  
Electrode matertal (9th code)  
Hasteroy C  
H
0
Flange (10th code)  
None  
Guide ring (11th code)  
1
7
For JIS 10K  
For JIS 75M (Meter size 80A, 100A only)  
Wiring connection port size (12th code)  
A
0
G1/2(PF1/2) female screw with water-proof gland  
(13th code)  
None  
Optional specifications (14th code)  
None  
Stainless tag plate  
Parameter setting  
Parameter setting and stainless tag plate  
Y
A
B
C
Note 1) Items with the asterisk mark will be manufactured as order.  
5
FME1, 2  
Integral type electromagnetic flowmeter (flange type)  
1
2
3
4
5
6
7
8
9
10 11 12 13  
14  
FME 2  
T
1 - H 1 0 A 0 -  
Description  
Meter size (5th code)  
C
D
T
E
F
15A  
25A  
40A  
50A  
80A  
G
H
J
K
L
100A  
150A  
200A  
250A  
300A  
Lining material (6th code)  
TFE (adhesive Tefron)  
T
Earth ring material (7th code)  
0
None  
H
Hasteroy C  
Electrode matertal (9th code)  
Hasteroy C  
H
1
Flange (10th code)  
For JIS 10K  
Guide ring (11th code)  
None  
0
Wiring connection port size (12th code)  
A
0
G1/2(PF1/2) female screw with water-proof gland  
(13th code)  
None  
Optional specifications (14th code)  
None  
Stainless tag plate  
Parameter setting  
Parameter setting and stainless tag plate  
Y
A
B
C
Note 1) Items with the asterisk mark will be manufactured as order.  
6
OUTLINE DIAGRAM (Unit: mm)  
(Wafer type)  
G1/  
2
Wire lead-in port  
199  
120  
73  
Water-proof gland  
B
W1  
< Stainless tag plate >  
Option  
75  
Meter size  
3A,6A 15A  
25A  
40A  
50A  
80A  
100A  
W1  
69  
75  
62  
281  
3
69  
75  
62  
281  
3
91  
95  
104  
112  
82  
119  
130  
90  
103  
163  
110  
377  
9
133  
190  
130  
417  
10  
B
F
73  
H
292  
4.5  
301  
6
337  
6.5  
Mass ( Kg )  
7
FME1, 2  
OUTLINE DIAGRAM (Unit: mm)  
(Flange type)  
G1/  
2
Wire lead-in port  
199  
120  
73  
Water-proof gland  
N-øB  
W1  
0
T
(Note)  
W2-3  
< Stainless tag plate >  
Option  
Meter size  
15A  
25A  
40A  
50A  
80A  
100A  
W1  
66.5  
200  
95  
87  
200  
125  
90  
100  
200  
140  
105  
4-19  
20  
116  
200  
155  
120  
4-19  
20  
100  
200  
185  
150  
8-19  
20  
130  
250  
210  
175  
8-19  
22  
W2 (Note)  
øD  
øC  
70  
N-øB  
4-15  
14  
4-19  
18  
JIS 10K  
Flange  
T
20  
øG  
52  
70  
85  
100  
337  
90  
130  
377  
110  
19  
155  
417  
130  
20  
H
281  
62  
292  
73  
301  
82  
F
5.5  
6.5  
8.5  
11  
Mass ( Kg )  
(Note) W2 are dimensions after positioning to piping.  
The lining flare sections are not glued before positioning to piping.  
(There are about 30mm protruding of each side.)  
8
OUTLINE DIAGRAM (Unit: mm)  
G1/  
2
Wire lead-in port  
199  
120  
73  
Water-proof gland  
N-øB  
W1  
W2  
T
(None)  
< Stainless tag plate >  
150A 200A 250A 300A  
Meter size  
W1  
170  
195  
250  
250  
Option  
0
0
0
0
W2 (Note)  
øD  
300 -3 350  
450 -5 500  
-3  
-5  
280  
240  
330  
290  
400  
355  
445  
400  
øC  
N-øB  
8-23 12-23 12-25 16-25  
JIS 10K  
Flange  
T
25  
212  
461  
148  
33  
28  
268  
523  
179  
55  
30  
320  
579  
207  
81  
31  
370  
665  
250  
86  
øG  
20  
H
F
Mass ( Kg )  
(Note) W2 are dimensions after positioning to piping.  
The lining flare sections are not glued before positioning to piping.  
(There are about 30mm protruding of each side.)  
9
FME1, 2  
EXTERNAL CONNECTION DIAGRAM  
HOW TO CONNECT CABLE  
1. Press the terminal spring by inserting a minus driver  
(small) through the opening at top.  
V9 V8 P7 G2 X1  
+
N
L
2. Insert terminated cable into the cable lead-in port as  
shown below.  
3. When the driver is removed, the cable is fixed (connected)  
by the spring force in the terminal.  
Total pulse  
output  
Power supply  
Current output  
Minus driver (small)  
10 15mm  
Status output  
Status input  
Cable  
Note) Cable should be securely fixed with the supplied  
water-proof gland.  
FLOW RATE – FLOW VELOCITY CONVERSION DIAGRAM  
3 4 5 6 810-2  
2
3
4 5 6 810-1  
2
3
4 5 6 8 1  
2
3
4 5 6 8 10  
2
3
4 5 6 8 102  
2
3 4 5 6 8  
L/s  
10  
8
6
5
4
3
2
1
0.8  
0.7  
0.5  
m3/ h  
L/min  
10-2  
2
3
4 5 6 810-1  
4 5 6 8 1  
2
3
4 5 6 8 1  
2
3
4 5 6 8 10  
2
3
4 5 6 8102  
4 5 6 8103  
2
3
4 5 6 8103  
4 5 6 8104  
2
3
2
3
2
3
4 5 6 8 10  
2
3
4 5 6 8102  
Flow rate  
2
3
2
3
2
3
4 5  
SCOPE OF DELIVERY  
Main unit (mounting bolt and packing should be prepared  
separately).  
Spare parts (guide rings (note) / for wafer type).  
Note) Not supplied for 80A and 100A JIS 10K.  
Magnetic stick  
ITEMS SPECIFIED AT ORDERING  
1. Type, specification code.  
2. Flow measurement range and mesurement fluid.  
3. When ordering “with stainless tag plate,” specify Tag No.  
(up to 16 alphanumeric characters) as needed.  
4. When ordering “with parameter setting,” complete and  
send the attached parameter designation table.  
10  
If you want the instrument with certain parameters factory set as you desire, specify them in the following parameter designation  
tables 1 and 2.  
Company :  
Name :  
Sector :  
Telephone No. :  
Measured fluid :  
<Parameter designation table 1>  
Put check marks into which precede items to modify for.  
Standard set value  
Item selection or  
value designation  
Setting item  
Range  
Item to select  
Example  
020.0s  
(Note 1)  
Damping  
5.0s  
1.0 to 99.0s  
.
[s]  
LCD  
1st line  
indication  
Real scale  
indication  
<1st line, 2nd line>  
<Designation of 1st line indication> According to selection of left item,  
Select an item from the following. designate necessary item and value.  
Real scale indication  
Volume unit: mL, L, m3  
Mass unit: g, kg  
q Real scale indication  
Volume unit: mL, L, m3  
Mass unit: g, kg  
Unit: m3/h  
Time unit: /s, /min, /h  
Arbitrary real scale indication Unit factor: 0.00001 to  
9999999  
Time unit: /s, /min, /h  
w Arbitrary real scale unit  
Unit factor: 0.00001 to  
9999999  
Unit name: Arbitrary value  
of 4 characters  
1000000  
*Value converted the units into L  
Unit name:  
None.  
e Percent indication (%)  
Percent indication  
t/h  
1000000  
t
Total real scale indication Volume unit: mL, L, m3  
Mass unit: g, kg  
r Total real scale indication  
Volume unit: mL, L, m3  
Mass unit: g, kg  
Arbitrary total real scale Unit factor: 0.00001 to  
indication  
9999999  
t Arbitrary total real scale unit  
Unit factor: 0.00001 to  
9999999  
Unit name: Arbitrary value  
of 4 charactes  
*Value converted the units into L  
Unit name:  
TAG No. indication  
Bar graph indication  
Non-display  
<Designation of 2nd line indication> According to selection of left item,  
Select an item from the following. designate necessary item and value.  
None  
None  
None  
y TAG No. indication  
u Bar graph indication  
(Percent indication can also  
be indicated simultaneously  
in 1% step)  
LCD  
2nd line  
indication  
Total realscale  
indication  
Unit: m3  
Real scale indication  
Volume unit: mL, L, m3  
Mass unit: g, kg  
i
Non-display  
Time unit: /s, /min, /h  
Arbitrary real scale indication Unit factor:0.00001 to  
9999999  
1000000  
t/h  
*Value converted the units into L  
Unit name:  
Percent indication  
None.  
Total real scale indication Volume unit: mL, L, m3  
Mass unit: g, kg  
Arbitrary total real scale Unit factor: 0.00001 to  
indication  
9999999  
Value converted the units into L  
1000000  
t
*
Unit name:  
TAG No. indication  
Bar graph indication  
Non-display  
None  
None  
None  
Range  
By table-1  
(Note 5)  
0.5 to 10 m/s  
converted to flow velocity.  
Volume unit  
Time unit: /s, /min,  
/h, /d  
:
mL, L, m3 Must be designated in 4 significant digits. 100.0  
Value:  
Instantaneous  
output  
low-cut point  
Total  
None.  
0.0%  
0.0% to 10.0%  
FORWARD  
.
None.  
Value:  
%
3.5%  
FORWARD  
/REVERSE (Note4) FORWARD/REVERSE  
FORWARD  
direction  
FORWARD/REVERSE  
Volume unit:  
Total constant 1m3  
(Note 2)  
Value: 0.001 to 1000  
Unit : mL, L, m3  
mL, L, m3  
(total value  
per pulse)  
Total  
30ms  
0.1 to 2000ms  
None.  
.
[ms]  
50.0[ms]  
pulse width  
(Note 3)  
Filter  
off  
on  
off  
on  
off  
None.  
11  
FME1, 2  
<Parameter designation table 2>  
Standard set value  
Item selection or  
value designation  
Setting item  
Range  
Item to select  
Example  
(Note 1)  
Empty detection off  
function  
on  
off  
on  
off  
Alarm output value  
3.6mA  
4mA  
24.8mA  
Upper/Lower Upper limit value Upper limit value: 0 to 130%  
Upper limit alarm  
Alarm output value  
3.6mA  
Upper limit  
value:  
limit alarm  
: 130%  
4mA  
24.8mA  
Upper limit value:  
120.0%  
Lower limit  
value:  
Lower limit value Lower limit value: 0 to 130%  
: 0%  
Lower limit alarm  
Upper/Lower limit alarm  
.
%
0.0%  
Lower limit value:  
.
%
Specific gravity 1.000g/cm3  
0.01 5g/cm3  
Up to 16 alphanumerics  
None  
None  
g/cm3  
0.95g/cm3  
F-100  
TAG-NO  
Blank unless  
designated  
STANDARD  
Flow  
STANDARD  
OPPOSITE  
STANDARD  
OPPOSITE  
None  
direction  
(Note 1) Standard set value refers to parameter set value as factory set in case parameter setting is not designated.  
(Note 2) Designate so that the number of total pulse outputs will be below 5kHz at the maximum flow rate (to meet the following equation).  
Range [m3/h] / (total constant [m3] × 3600) 5000  
(Note 3) Designate the total pulse width so as to hold: (Total constant [m3]) × 3600/range [m3/h] total pulse width [ms]/500  
(Note 4) When selecting FORWARD/REVERSE from the total direction, total pulse is only outputted in the FORWARD direction.  
(Note 5) Factory-set range before shipment (unless specified).  
Table-1  
Meter size Range [m3/h] Meter size Range [m3/h] Meter size Range [m3/h]  
3A  
0.05  
0.2  
1.2  
3.5  
40A  
50A  
80A  
100A  
14.0  
14.0  
35.0  
55.0  
150A  
200A  
250A  
300A  
120.0  
220.0  
350.0  
350.0  
6A  
15A  
25A  
(Material selection table of electrode/earth ring)  
Material of  
Measurable liquid  
electrode/earth ring  
Unmeasurable liquid  
SUS316  
Water and waste water, weak acid, weak alkali  
Inorganic acid, organic acid, chloride or alike  
Example: 25% acetic acid or less, hydroiodic acid,  
butyric acid, aqueous ammonia or alike  
Hastelloy C-4 or  
equivalent  
Suitable for intermediate oxidation and reduction  
and can be used for various fields.  
Chloride, high-temperature strong acids  
(nitric acid, hydrochloric acid, sulfuric acid),  
ferric chloride or alike  
Example: Sea water, formic acid, acetic acid, aqueous  
ammonia, normal-temperature nitric acid and sulfuric  
acid or alike  
Titanium  
Tantalum  
Resistant to sea water, most oxidative acids, chloride, Reductive acids such as hydrochloric acid,  
sulfide and alkali.  
sulfuric acid, phosphoric acid, oxalic acid  
Example: Sea water, saline water, aqueous ammonia,  
chlorine water, polyelectrolyte, acetic acid, ferric  
chloride or alike  
Resistant to most chemicals.  
(particularly, strong acids)  
Sodium hydroxide, potassium hydroxide,  
hydroflouric acid, fuming sulfuric acid or  
alike  
Example: Hydrochloric acid, sulfuric acid, nitric acid,  
aqua regia, ferric chloride, hypochlorous acid, sodium  
hypochlorite, PAC (Polyaluminum chloride) or alike  
Platinum-iridium (Pt-Ir)  
Resistant to almost chemicals.  
Aqua regia  
(Note): The electrode/earth ring for E-series electromagnetic flowmeter use Hastelloy C-4 or equivalent.  
If other material except Hastelloy C-4 is required, select a model that uses other material from the integral type  
electromagnetic flowmeter (FMA series) of Fuji Electric.  
Caution on Safety  
*Before using this product, be sure to read its instruction manual in advance.  
Head Office  
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan  
http://www.fesys.co.jp/eng  
Sales Div.  
International Sales Dept.  
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan  
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187  
http: //www.fic-net.jp/eng  
Printed in Japan  
Information in this catalog is subject to change without notice.  

相关型号:

EDS6-120

E SERIESE ELECTROMAGNETIC FLOWMETER(SEPARATE TYPE)
FUJI

EDS6-121A

VORTEX FLOWMETER (Eggs DELTA)
FUJI

EDS6-122A

VORTEX FLOWMETER (DELTA FLOWPET)
FUJI

EDS6-123I

ULTRASONIC FLOWMETER M-Flow ">PW>
FUJI

EDS6-125

OPTICAL DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER
FUJI

EDS6-126

OPTICAL DIFFERENTIAL PRESSURE TRANSMITTER REMOTE SEAL TYPE
FUJI

EDS6-128C

EQUALIZING VALVE, OVAL FLANGE
FUJI

EDS6-132F

HYBRID ULTRASONIC FLOWMETER (PULSE">(Pulse Doppler method Transit Time method)
FUJI

EDS6-141D

ULTRASONIC FLOWMETER(2-Path System type)
FUJI

EDS6-33B

FCX SERIES DIFFERENTIAL PRESSURE TRANSMITTER
FUJI

EDS6-34F

FCX SERIES REMOTE SEAL TYPE DIFFERENTIAL PRESSURE TRANSMITTER
FUJI

EDS6-35D

FCX SERIES FLOW TRANSMITTER
FUJI