IN-SITU ZIRCONIA OXYGEN ANALYZER  
<ZIRCOMAT-P>  
DATA SHEET  
ZFK, ZRM  
This oxygen analyzer is used to continuously measure  
oxygen concentration in combustible exhaust gas of industrial  
boilers or furnaces, and is ideally suited for combustion moni-  
toring and control.  
The detector (ZFK) used with the analyzer is directly  
inserted into the objects measured, eliminating the need for a  
sampling device and provides quick response.  
General-use detector  
High-temperature detector  
The converter (ZRM) features automatic calibration and  
blowdown functions. The adoption of liquid crystal display  
facilitates operation and setting in interactive mode.  
Besides the general-use type detector, corrosion resisting  
type and high temperature type are available for selection  
according to applications.  
FEATURES  
1. Output range easily set  
Output range can be easily set in 0.5% increments within  
the scope of 2 to 50%. When oxygen decreases, in-  
complete combustion level appears on the display (rich  
mode; output voltage of oxygen detector), instead of  
oxygen concentration.  
Converter  
2. Automatic calibration/blowdown function  
Automatic calibration and manual/auto blowdown func-  
tions are provided as standard functions. An external  
solenoid valve is required.  
SPECIFICATIONS  
3. Easily operated in interactive mode  
General  
Interactive mode is adopted to the liquid crystal display for  
Measuring object: Oxygen contained in noncombustible  
operation and parameter setting, facilitating use even for  
beginners.  
4. Combustion efficiency display function  
gas  
Measuring principle:  
Direct-insertion zirconia system  
Measuring range: 0 to 2 ……50 vol% O2 freely settable  
(in 0.5% steps)  
Combustion efficiency calculated from oxygen concent-  
ration and temperature of exhaust gas can be displayed as  
an optional function, which is useful to improve combus-  
tion efficiency.  
Repeatability:  
Linearity:  
Within ±0.5% of max. output signal  
±2% of full scale  
5. Sampling device is unnecessary  
Response time:  
Within 7sec for 90% response (from  
calibration gas inlet)  
100, 115, 220 or 230V AC, 50/60Hz  
Gas sampling devices such as a gas aspirator, a dehu-  
midifier, etc. are unnecessary because of use of direct-  
insertion type detector. The adoption of a flow guide tube  
utilizing the flow of the measured gas assures quick  
response (less than 7sec).  
Power supply:  
Power consumption:  
(approx.)  
15 + 50VA (at steady state of general-use  
detector)  
15 + 200VA (at start of general-use  
detector)  
Approx. 15min  
6. Selection of detector type according to applications  
Besides the general-use type detector used under  
temperatures of less than 600°C, a corrosion-proof de-  
tector for measuring incinerator exhaust gas, and a high  
temperature type detector using heat insulator for the  
ejector and insertion tube, capable of measuring  
temperatures up to 1590°C, are available for selection  
according to applications.  
Warmup time:  
Oxygen detector (ZFK2,5), ejector (ZTA)  
Measuring detector:  
For general-use: ZFK2  
For corrosive gas: ZFK5  
EDSX3-113c  
Date Nov. 30, 2001  
ZFK, ZRM  
Measured gas temperature:  
Repeatability:  
Linearity:  
±0.5% of full scale  
±1.0% of full scale  
Flow guide tube system; –20 to +600°C  
(for general-use, corrosive gas)  
Ejector system; –20 to +1590 °C (for  
high-temperature gas)  
Indication:  
Oxygen concentration; 3-digit LED  
Operation/setting display: 16-digit, 2-line  
LCD  
–20 to +800°C (for general-use)  
Mode display: 3pcs LED  
Measured gas pressure:  
Oxygen concentration output signal:  
4 to 20mA DC (allowable load resistance:  
–3 to +3kPa (–306 to +306mmH2O)  
Flow guide tube: With or without blow-down nozzle  
Flange; JIS5K 65A FF  
500or less)  
or 0 to 1V (output resistance: 100 or  
(JIS5K-80AFF for high particulate gas)  
Insertion length; 0.3, 0.5, 0.75, 1m  
(0.8m for high particulate gas)  
Ejector (general-use):  
less)  
Isolated output, linear  
Contact output signal:  
(1) Contact specification; 4 points, N.O. (1a), 250V AC, 2A  
(2) Contact function;  
Probe for guiding measured gas to de-  
tector  
• Under maintenance  
Flange; JIS10K 65A RF  
• Under blowdown  
Insertion length; 0.5, 0.75, 1, 1.5m  
(according to customer's specification)  
Ambient temperature:  
• Span calibrating gas  
• Zero calibration gas  
Following functions freely selected  
• High limit alarm  
–20 to +60°C for cable section  
–5 to +100°C for ejector section  
125°C or less at detector flange surface  
with power applied  
• Low limit alarm  
• High/low limit alarm  
• Fault (abnormal)  
Structure:  
Filter:  
Dust/rain-proof structure(IEC IP55  
equivalent)  
Alumina(filtering accuracy 50µm) and  
quartz paper  
Contact input signal:  
Auto. calibration start (auto. calibration  
starts when contact closes)  
Calibration disable (calibration disabled  
when contact closes)  
Contact specification; isolated, ON at  
1kor less  
Main materials of gas-contacting parts:  
General-use detector; Zirconia, SUS316,  
platinum  
Anticorrosive detector; Zirconia, tita-  
nium, platinum  
Flow guide tube; SUS304 or SUS316  
Ejector (general use);SUS316, SUS304  
Ejector; (for high temperature) SiC,  
SUS316, SUS304  
Calibration method:  
(a) Manual calibration with key operation  
(b) Auto. calibration (standard function)  
Calibration cycle; 00 day 00 hour to 90  
days 60 hours  
Calibration gas: • Range settings  
Zero gas; 0.010 to 50.000% O2  
Span gas: 8.000 to 23.000% O2  
• Recommended calibration gas concen-  
tration  
Calibration gas inlet:  
SUS316  
Reference air inlet (option):  
Rc1/8 or NPT1/8  
Detector mounting:  
Horizontal plane ± 45°, ambient sur-  
rounding air should be clean.  
Outer dimensions: (L x max. dia.) 210mm x 100mm  
(detector)  
Mass (approx.) {weight}:  
Zero gas; 0.25 to 2.0% O2  
Span gas; 20.6 to 21.0% O2  
(oxygen concentration in the  
air)  
Blowdown:  
A function for blowing out with com-  
pressed air dust that has deposited in the  
flow guide tube. Blowdown can be  
performed for a predetermined time and  
at predetermined intervals.  
Detector; 1.6kg  
Ejector; 15kg (insertion length 1m)  
Flow guide tube (general-use, 1m); 5kg  
Finish color:  
Ejector air inlet flow rate:  
5 to 10r/min  
Blowdown air inlet pressure:  
200 to 300kPa {2 to 3 kgf/cm2}  
Ejector exhaust gas processing:  
Within furnace, returned to flue  
Heater temperature drop alarm output (ejector):  
Alarm output when below 100°C  
Mechanical thermostat  
Silver and SUS metallic color  
Blowdown cycle; 00 hour 00 minute to  
99 hours 60 minutes  
Blowdown time; 0 minute 00 second to  
9 minutes 60 seconds  
Output signal hold:  
Output signal is held during calibration  
and blowdown. The hold function can  
also be released.  
Transmission function (option):  
RS-485  
N.O. (1a) contact, 200V AC, 2A  
Transmission distance; Max. 500m total  
Number of units connected; Max. 8 units  
Half-duplex bit serial transmission, start-  
stop synchronization.  
Oxygen converter (ZRM)  
Measuring range: 0 to 2 ……50 vol% O2 freely settable  
(in 0.5% O2 steps)  
2
Remark: When connecting via an RS-  
232C interface, a RS232 RS  
485 converter should be used.  
Combustion efficiency display (option):  
This function calculates and displays  
combustion efficiency from oxygen  
concentration and measured gas temper-  
ature.  
Thermocouple (K or R) is required for  
temperature measurement.  
Rich mode display:  
When the detector output voltage ex-  
ceeds 200mV (0.0023%O2), the rich  
mode (fuel rich) is indicated in LCD  
where the LED showing the detector  
output voltage flickers.  
Self-diagnosis function:  
Provided for detector temperature fault,  
zero calibration fault, span calibration  
fault, calibration disable, and detector  
output fault.  
Ambient temperature:  
–10 to +50°C  
Ambient humidity: 90% RH or less  
Power supply:  
Construction:  
90 to 220 or 230 V AC, 50/60Hz  
Dust-proof, rainproof construction  
(corresponding to IP53 of IEC)  
Steel  
Material:  
Outer dimensions (H x W x D):  
220 X 193 X 89mm  
Mass {weight}:  
Approx. 3.5kg (excluding cable and de-  
tector)  
Finish color:  
Munsell 2.5Y8.4/1.2  
Mounting method: Mounted flush on panel or on pipe  
Electrical Safety:  
Overvoltage category  
; II power supply input  
; I relay interfaces  
(IEC1010-1)  
External overcurrent protective device  
; 10A  
Equipment interfaces are safety  
separated (SELV)  
The product conforms to the requirements of the  
Electromagnetic compatibility Directive 89/336/EEC as  
detailed within the technical construction file number  
TZ734575. The applicable standards used to demonstrate  
compliance are :  
EN 55011 : 1992 CLASSA Conducted and Radiated emissions  
EN 50082-1 : 1992  
Radiated immunity, ESD and FBT  
ZFK, ZRM  
3
ZFK, ZRM  
CODE SYMBOLS  
(Detector)  
(Ejector)  
1
2
3
4
5
6
7
8
4
5
6
7
8
9 10 11 12 13 14  
Description  
Z T A  
1
1
Description  
ZFK  
4
Measured gas temperature  
Application  
1
2
For high temperatures (+1590°C max.)  
General-use (+800°C max.)  
2
5
General use  
For corrosive gas (refuse incinerator)  
Insertion length [mm]  
Kinds  
B
C
D
E
500  
750  
1000  
1500  
R
Standard  
Cal. gas inlet  
For φ6mm tube  
For φ1/4 inch tube  
1
2
Power supply  
Power supply  
100/115VAC 50/60Hz  
200/220VAC 50/60Hz  
230VAC 50/60Hz (CE-marking approved)  
1
3
5
100V/115V AC 50/60Hz  
200V/220V AC 50/60Hz  
230VAC 50/60Hz  
1
3
5
Flow guide tube  
flange  
application  
None  
length  
(Converter)  
0 Y 0  
5 A 3  
5 A 5  
5 A 7  
5 A 1  
5 B 3  
5 B 5  
5 B 7  
5 B 1  
5 C 3  
5 C 5  
5 C 7  
5 C 1  
6 D 3  
6 D 5  
6 D 7  
6 D 1  
6 E 3  
1
2
3
4
5
6
7
8
9
SUS304 general use  
SUS304 general use  
SUS304 general use  
SUS304 general use  
SUS316 for corrosive gas  
SUS316 for corrosive gas  
SUS316 for corrosive gas  
SUS316 for corrosive gas  
SUS316 with blow-down nozzle 300mm  
SUS316 with blow-down nozzle 500mm  
SUS316 with blow-down nozzle 750mm  
SUS316 with blow-down nozzle 1000mm  
300mm  
500mm  
750mm  
1000mm  
300mm  
500mm  
750mm  
1000mm  
Description  
Z R M 1  
1 1 -  
Output signal  
4 to 20mA DC  
0 to 1V DC  
B
E
Optional functions  
Y
A
B
C
None  
Serial communication (RS-485)  
Combustion efficiency display  
Transmission function + Combustion  
efficiency display  
Power supply  
SUS316 for high particulate  
SUS316 for high particulate  
SUS316 for high particulate  
SUS316 for high particulate  
300mm  
500mm  
750mm  
1000mm  
1
5
90 to 220V AC 50/60Hz  
230VAC 50/60Hz (CE marking approved)  
Mounting method  
Panel mounting  
Pipe mounting  
1
2
SUS316 for high particulate with 300mm  
cover  
6 E 5  
6 E 7  
6 E 1  
Z Z Z  
SUS316 for high particulate with 500mm  
Note: Specify the detector type.  
(ZFK 2 or 5, R-type or K-type thermo-  
couple)  
cover  
SUS316 for high particulate with 750mm  
cover  
SUS316 for high particulate with 1000mm  
(Exclusive-special cable)  
cover  
Others  
1
2
3
4
5
6
7
8
9
Description  
Connectable devices  
For ZRM  
Z R Z M  
1 -  
Protection cover  
Without  
With  
Y
A
M
Types  
For R thermocouple  
Reference air inlet  
Non  
R
Y
A
B
Rc1/8  
NPT1/8  
Conduit length  
None  
None  
None  
None  
None  
None  
None  
None  
None  
None  
None  
None  
6m  
Cable length  
6m  
YA  
YB  
YC  
YD  
YE  
YF  
YG  
YH  
YJ  
10m  
15m  
20m  
30m  
40m  
50m  
60m  
70m  
80m  
90m  
100m  
6m  
Non-standard spec.  
Other non-standard items  
Z
( Replacement Detector element)  
4
5
6
7
8
9 10 11 12 13  
0 Y 0 Y Y  
Description  
ZFK  
4
YK  
YL  
Application  
2
5
General use (TC516041)  
For corrosive gas (refer to incinerator)  
(TC516042)  
YM  
AA  
BB  
CC  
DD  
10m  
15m  
20m  
10m  
15m  
20m  
Kinds  
Standard  
R
Cal. gas inlet  
Polypropylene joint for φ6 tube  
Brass joint for φ1/4 inch tube  
Cable end treatment  
None  
One side (detector side)  
Both sides  
6
7
0
1
2
Power supply  
1
3
5
100/115VAC 50/60Hz  
200/220VAC 50/60Hz  
230VAC 50/60Hz  
Note: For connection between detector and  
converter, the conduit to be used should  
be rainproof flexible type.  
4
CONFIGURATION  
Flow guide tube system  
Reduction valve  
Rc1/4  
(unnecessary when supply air pressure is  
Solenoid valve  
(not supplied)  
200 to 300kPa {2 to 3kgf/cm2}  
(upper side blow port should be selected)  
Blow-down, 200 to 300kPa {2 to 3kgf/cm2}  
Supply air  
Rainproof cover  
15ASGP  
tube equivalent  
(not supplied)  
or 10/ 8 PTFE pipe  
or copper pipe  
15ASGP  
tube equivalent  
(not supplied)  
Flow guide tube  
Detector  
ZFK2  
ZFK5  
Gas temperature.  
600°C max.  
1
2
3
4
5
6
Rainproof flexible conduit.  
20m max.  
Bule  
Black  
Red Yellow  
White White  
AC power  
supply  
Sample gas outlet  
4-core  
cable  
Converter (ZRM)  
2-core  
cable  
Analog  
output  
Auxiliary  
input  
Zirconia Thermocouple Maintenance Blow-down  
Gas temperature.  
600°C max.  
signal  
signal  
contact  
contact  
Heater  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
Flow guide tube  
for high particulate  
Blue Yellow Red White  
Black White  
4 to 20mA DC  
(0 to 1V)  
6mm or 4 inch tube  
for calibration gas  
(not supplied)  
Cell/thermocouple output  
Heater power supply  
Sample gas outlet  
AC power  
supply  
Serial  
communication  
Calibrating gas  
contact  
Contact input  
NC  
21  
SG  
25  
FG  
26  
N
L
15  
16  
17  
18  
19  
20  
22  
23  
24  
27  
28  
PE  
Gas temperature.  
600°C max.  
AC power supply  
Flow guide for high  
particulate with cover  
AC power  
supply  
RS-485  
Reduction  
valve (ZBD6)  
Solenoid valve  
(not supplied)  
Joint  
Standrad gas  
for zero point  
(ZBM)  
Flowmeter  
(ZBD4)  
(1 to 1.5R/min)  
Reduction valve (unnecessary when supply air pressure is  
50 to 100kPa {0.5 to 1kgf/cm2}  
*2  
Ref. air  
*1 Air supply  
to Detector  
Reduction vale  
(ZBD6)  
Solenoid valve  
(not supplied)  
(0.2 to 0.5R/min)  
*1 Standard gas for  
span point (ZBM)  
*1 Sandard gas or instrumentation air can be used in plase of span gas.  
Note  
*2 Instrument quality air or bottled air is available as reference air instead of ambient air.  
5
ZFK, ZRM  
Ejector system  
Flowmeter  
(ZBD)  
Reduction valve  
(unnecessary when supply air pressure is  
Ejector (ZTA)  
Ejector (5 to 10R/min)  
200 to 300kPa {2 to 3kgf/cm2} )  
Joint  
Supply air  
Power supply  
1
2
4
5
Gas temperature.  
1590°C max.  
Copper pipe 6/ 4mm  
Heater temperature drop  
Alarm  
Solenoid valve  
(not supplied)  
Copper pipe  
10/ 8mm  
Copper pipe  
10/ 6mm  
Detector (ZFK2)  
1
2
3
4
5
6
Bule  
Black  
Red Yellow  
White White  
Rainproof flexible conduit.  
4-core  
cable  
AC power  
supply  
2-core  
cable  
Converter (ZRM)  
Analog  
output  
Auxiliary  
input  
Zirconia Thermocouple Maintenance Blow-down  
signal signal contact contact  
Heater  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
Blue Yellow Red White  
Black White  
4 to 20mA DC  
(0 to 1V)  
Cell / thermocouple output  
Heater power supply  
AC power  
supply  
Serial  
communication  
Calibrating gas  
contact  
Contact input  
NC  
21  
SG  
25  
FG  
26  
N
L
6mm or 4 inch tube  
for calibration gas  
(not supplied)  
15  
16  
17  
18  
19  
20  
22  
23  
24  
27  
28  
PE  
AC power supply  
AC power  
supply  
RS-485  
Reduction  
vale (ZBD6)  
(1 to 1.5R/min)  
joint  
Solenoid valve  
(not supplied)  
Standrad gas  
for zero point  
(ZBM)  
Flowmeter  
(ZBD4)  
Reduction valve (unnecessary when supply air pressure is  
50 to 100kPa {0.5 to 1kgf/cm2}  
*2  
Ref. air  
*1 Air supply  
to Detector  
Reduction vale  
(ZBD6)  
(0.2 to 0.5R/min)  
Solenoid valve  
(not supplied)  
*1 Standard gas for  
span point (ZBM)  
Note: *1 Standard gas or instrumentation air can be used in place of span gas.  
*2 Instrument quality air or bottled air is available as reference air instead of ambient air.  
6
CAUTIONS  
SCOPE OF DELIVERY  
If combustible gas (CO, H2 etc.) exists in the measured  
gas, error will occur due to burning at the sensor section.  
The inclusion of corrosive gas (Si vapor, alkaline metal, P,  
Pb etc.) will shorten the life of the sensor.  
Detector:  
Converter:  
Ejector:  
Detector main unit x 1, Viton O ring x 2,  
mounting screw (M5mm x 16) x 6,  
thermal sticker x 1, flow guide tube (as  
specified) x 1, ceramic filter x 1, rainproof  
cover (as specified) x 1  
Converter main unit x 1, mounting  
bracket set, (according to specification) x  
1
Accessories (AC250V 500mA T fuse x 2,  
AC250V 3.15A T fuse x 2)  
Ejector main unit x 1, insertion tube x 1,  
M16mm nut, and washer x 4, packing x 1  
When the measured gas temperature is high (+300°C or  
higher), the flange should be separated from the furnace  
wall in order to bring the detector flange surface  
temperature below the specified value +125°C). The flow  
guide should be attached in the direction in which the gas  
flow to the detector decreases.  
When much dust is included in the gas, the flow guide  
tube should be attached at an inclination so that the flow  
goes from below to above. And the flow guide should be  
attached in the direction in which the gas flow to the  
detector decreases.  
Items to be prepared separately:  
(1) Standard gas for calibration  
Type ZBM NSH4-01 (up to 5% O2 range)  
Type ZBM NSJ4-01 (over 5% O2 range)  
(2) Reduction valve for standard gas (type ZBD61003)  
(3) Flowmeter  
In the case of a refuse incinerator, automatic blow down  
of the flow guide should not be performed (to prevent  
corrosion of the flow guide tube due to drainage). Blow-  
down should be performed manually when change in the  
indication has become very little with the furnace stopped.  
Type; ZBD42203, 0.2 to 2r/min (for calibrating gas)  
Type; ZBD42403, 1 to 10r/min (for ejector)  
DEVICE CONFIGURATION  
The device to be combined differ according to the conditions of the gas to be measured. Select the devices to be combined  
with reference to the following table.  
Measured gas  
DUST  
Device configuration  
Detector type Converter  
Temperature Gas Flow  
Application  
Protection  
cover  
Note  
Ejector  
type  
type  
Less than 0.2g/mm3  
Less than 10g/Nm3  
600°C or  
5 to 20m/s  
5 to 20m/s  
5
5
General-use  
(boiler)  
Fuel; gas, oil  
Fuel: coal  
ZFK2R  
ZFK2R  
4-  
4-  
A
C
ZRM  
ZRM  
less  
with blow down  
Less than 1g/Nm3  
Less than 10g/Nm3  
600°C or  
5
5
For corrosive  
gas (refuse  
incinerator)  
Included low moisture ZFK5R  
Included low moisture ZFK5R  
with blow down  
4-  
4-  
B
C
ZRM  
ZRM  
less  
Less than 25g/Nm3 no  
Less than 25g/Nm3 yes  
6
6
Included low moisture ZFK5R  
with blow down  
4-  
4-  
D
E
ZRM  
ZRM  
ZRM  
ZRM  
Included high moisture ZFK5R  
with blow down  
Less than 1g/Nm3  
Less than 1g/Nm3  
ZTA2  
ZTA1  
800°C or  
less  
Less than  
1m/s  
General-use  
(boiler)  
SUS316 tube  
with blow down  
SIC tube  
ZFK2R  
4-OYO  
4-OYO  
1590°C or  
less  
Less than  
1m/s  
ZFK2R  
with blow down  
Note (1) Dust volume is approximate value.  
(2) Instrument quality air or bottled air is available as reference air by selecting detector with reference air inlet.  
7
ZFK, ZRM  
OUTLINE DIAGRAM (Unit:mm)  
Detector (ZFK2)  
80  
67  
Proof cover (to order)  
Approx. 65  
Approx. 130  
Approx. 118  
45.4  
36  
5
26  
Filter  
EXTERNAL CONNECTION DIAGRAM  
Element output  
Heater  
Thermocouple  
A
1
3
2
4
5
6
Black / White/ red / White/ yellow / blue  
2-core wire  
4-core wire  
Exclusive-special cable  
6-  
6
Ref. air inlet (to order)  
NPT1/8 or Rc1/8  
Calibration gas inlet (to order)  
SUS316 for 6/ 4 PTEF tube or 1/4 inch tube.  
Exclusive  
cable gland  
Flow guide tube  
155  
130  
Approx. L  
12  
Approx. 20  
67  
Gas inlet  
Z F K 2 R  
4 - 5 A 3  
5
7
1
6-M5  
Gas outlet  
detector side  
3
1
Cord 11th  
L (m)  
MASS  
5
7
Z
8–15  
MTG. holes  
1.0  
0.5 0.75  
0.3  
Oxygen detector  
L=  
(to order)  
4.1  
2.7 3.3  
4.8  
Approx.(kg)  
Flow guide tube (with blow-down nozzle)  
155  
Approx. L  
18  
Approx. 20  
130  
3
67  
Gas inlet  
6-M5  
detector side  
Z F K 2 R  
4 - 5 C 3  
5
7
1
Gas outlet  
Oxygen detector  
Blow down air inlet  
815  
MTG. holes  
Select an upper port to  
avoid the condensation  
in the piping  
4-Rc1/4  
with plug int.thd.  
3
1
Cord 11th  
5
7
Z
0.5 0.75 1.0  
5.7  
L (m)  
Mass  
0.3  
L=  
(to order)  
3.0 3.8  
4.8  
Approx.(kg)  
8
Flow guide tube (for high particulate)  
4 - Rc 1/4  
with plug int thd.  
Blow down air inlet  
Select an upper port to  
avoid the condensation  
in the piping  
8 - 19  
MTG. hole  
29.5  
Flange: JIS 5K80A FF  
ZFK MTG. position  
Packing  
Z F K 2 R  
4 - 6 D 3  
5
7
1
Gas outlet  
30  
3
1
Cord 11th  
5
7
Z
0.5 0.75 1.0  
8.3  
L (m)  
Mass  
0.3  
L=  
(to order)  
4.5 5.6  
7.0  
Approx.(kg)  
Gas flow  
Tube (50A SCH40)  
Flow guide tube (for high particulate with cover)  
4 - Rc 1/4  
with plug int thd.  
Blow down air inlet  
Select an upper port to  
avoid the condensation  
in the piping  
8 - 19  
MTG. holes  
Flange: JIS 5K80A FF  
ZFK MTG. position  
Packing  
Z F K 2 R  
4 - 6 E 3  
5
7
1
Gas outlet  
30  
3
1
0.5 0.75 1.0  
Cord 11th  
5
7
Z
L (m)  
Mass  
0.3  
L=  
(to order)  
7.1 9.0  
13.6  
11.4  
Approx.(kg)  
Gas flow  
(38)  
Tube (50A SCH40)  
Protection tube (65A SCH40)  
9
ZFK, ZRM  
Detector (ZFK5)  
80  
67  
Proof cover (to order)  
Approx. 65  
Approx. 130  
Approx. 118  
45.4  
36  
5
26  
Filter  
EXTERNAL CONNECTION DIAGRAM  
Element output  
Heater  
Thermocouple  
1
3
2
4
5
6
Black / White/ red / White/ yellow / blue  
2-core wire  
4-core wire  
Exclusive-special cable  
Ref. air inlet (to order)  
NPT1/8 or Rc1/8  
6-  
6
Exclusive cable gland  
Calibration gas inlet (to order)  
SUS316 for 6/ 4 PTEF tube or 1/4 inch tube.  
Flow guide tube  
155  
130  
Approx. 40  
12  
3
Approx. L  
67  
Gas inlet  
Z F K 5 R  
4 - 5 B 3  
5
7
1
6-M5  
detector side  
Gas outlet  
3
1
Cord 11th  
L (m)  
5
7
Z
8- 15  
MTG. holes  
1.0  
0.3 0.5  
0.75  
Oxygen detector  
L=  
(to order)  
MASS  
Approx.(kg)  
3.3  
4.5 6.1  
7.6  
Flow guide tube (with blow - down nozzle)  
155  
Approx. 20  
18  
Approx. L  
130  
3
67  
Gas inlet  
6-M5  
detector side  
Z F K 5 R  
4 - 5 C 3  
5
7
1
Gas outlet  
Blow down air inlet  
8- 15  
MTG. holes  
Oxygen detector  
Select an upper port to  
avoid the condensation  
in the piping  
3
1
Cord 11th  
L (m)  
5
7
Z
4- Rc 1/4  
with plug int. thd.  
1.0  
0.3 0.5  
0.75  
L=  
(to order)  
MASS  
Approx.(kg)  
3.3  
4.2 5.7  
7.4  
10  
Flow guide tube (for high particulate)  
4 - Rc 1/4  
with plug int thd.  
Blow down air inlet  
Select an upper port to  
avoid the condensation  
in the piping  
8 - 19  
MTG. hole  
Flange: JIS 5K80A FF  
ZFK MTG. position  
Packing  
Z F K 5 R  
4 - 6 D 3  
5
7
1
Gas outlet  
30  
3
1
Cord 11th  
L (m)  
5
7
Z
0.3 0.5 0.75  
1.0  
L=  
(to order)  
MASS  
Approx.(kg)  
4.5 5.6 7.0 8.3  
Gas flow  
Tube (50A SCH40)  
Flow guide tube (for high particulate with cover)  
4 - Rc 1/4  
with plug int thd.  
Blow down air inlet  
Select an upper port to  
avoid the condensation  
in the piping  
8 - 19  
MTG. holes  
Flange: JIS 5K80A FF  
ZFK MTG. position  
Packing  
Z F K 5 R  
4 - 6 E 3  
5
7
1
Gas outlet  
30  
3
1
Cord 11th  
L (m)  
5
7
Z
0.3 0.5 0.75  
1.0  
L=  
MASS  
Approx.(kg)  
(to order)  
7.1 9.0 11.4 13.6  
Gas flow  
(38)  
Tube (50A SCH40)  
Protection tube (65A SCH40)  
11  
ZFK, ZRM  
Converter (ZRM)  
Panel flush mounting  
Pipe mounting  
88.6  
18  
204  
193  
2B pipe for mounting  
60.5 0.5mm)  
(
Cable gland  
35  
194  
9
EXTERNAL CONNECTION DIAGRAM  
4-core Cable  
2-core Cable  
5
2
6
3
4
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14  
37  
55  
28  
176  
A.OUT  
AUX.IN  
Zr.SIG  
T.C  
MENT  
BLOW  
HEAT  
Wiring port, 3- 23.  
with rubber bushing  
Blow  
contact  
Output  
signal  
Maintenance  
contact  
Heater power  
supply  
Element  
input  
Thermo-  
couple  
Auxiliary  
input  
15 16 17 18 19 20 21 22 23 24 25 26 27 28  
P E  
N
L
D11 D12 DI  
COM  
Contact input  
FG  
DXA DXB  
Serial  
G
ZV COM SV  
SG  
POWER  
Power supply  
Calibrating gas  
contact  
communication  
Note (1) : The numbers 1 through 6 denote detector terminal No. for exclusive - special cables.  
(2) : M3 terminal screws are used for the terminal block.  
Ejector (ZTA)  
4-M16 bolt  
190  
Approx. L  
170  
P
Gas inlet  
40  
L [mm]  
500 750 1000 1500  
Detector  
(ZFK2)  
Viewed from P direction  
140  
35  
50  
45  
40  
Blow -down air inlet  
(Rc1/4)  
(JIS 10K65ARF)  
Ejector air inlet  
(Rc1/4)  
Cable gland  
(A15C)  
EXTERNAL CONNECTION DAIAGRAM  
1
2
3
4
5
AC  
power supply  
Ejector air  
outlet  
Heater temp.drop alam  
Caution on Safety  
(Rc1/4)  
*Before using this product, be sure to read its instruction manual in advance.  
Head Office  
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan  
http://www.fesys.co.jp/eng  
Sales Div.  
International Sales Dept.  
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan  
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187  
http: //www.fic-net.jp/eng  
Printed in Japan  
Information in this catalog is subject to change without notice.  

相关型号:

EDSX3-119B

IN-SITU ZIRCONIA OXYGEN ANALYZER < ZIRCOMAT-C >
FUJI

EDSX3-137D

IN-SITU ZIRCONIA OXYGEN ANALYZER
FUJI

EDSX5-71

FCX – AX SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-72

FFCCXX – –AAX SSEERRIIEESS REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-73

FCX – AX SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-74

FCX – AX SERIES SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-75

FCX – C SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-76A

FCX – C SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-77

FCX –AX SERIES PRESSURE TRANSMITTER Hydroseal® Diaphragm Version
FUJI

EDSX5-79J

ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-80K

PRESSURE TRANSMITTER
FUJI

EDSX5-82K

SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI