FC SERIES RATIO SETTER  
DATA SHEET  
PDG3  
The FC series Ratio Setter carries out ratio setting and com-  
putation for ratio control and sends a signal to a controller as  
its set value.  
This product is a ratio setter to be used in a process and it  
excels in the effect of monitoring due to adoption of a color  
LCD.  
Besides standard signals of 1 to 5 V DC, input signals from  
thermocouples and resistance bulbs can be handled at op-  
tion.  
FEATURES  
1. High visibility ensured with color graphic display  
A color LCD is adopted for graphic display of bar graph  
and trend screens,etc.  
2. Communication function (option)  
RS-485 (Modbus protocol) are available.  
3. Memory card (option)  
Memory card can save any data, for example process in-  
put, WAFER output, etc.  
Communication  
®
RS-485 (Modbus  
Transmission terminal  
)
PV  
SV  
indicator indicator  
SO  
indicator  
Signal name/terminal No.  
Signal name/terminal name  
Linearize  
Square root  
Filter  
Local mode output (LS)/DO7  
(KPV)  
(SO)  
Process variable input/PV1  
(Analog input)  
PV compensation signal  
(KPV)/AO3  
SOH  
R
SO=R(SV+B3) x  
(KPV–B1)+B2  
Computed value output (SO)/AO1  
B1  
B2  
B3  
SOL  
2
Squared computed value output  
(SO2)/AO2  
R
L
SO  
RSVH  
RSVL  
(SV)  
External set point value  
input/PV2  
(Analog input)  
Set point value output signel  
(SV)/AO4  
Input  
switch  
Remote reqest (R-REQ)/DO8  
R
Upper alarm output (H)/DO9  
Lower alarm output (L)/DO10  
Fault output (FLT-Do)/FLT  
KPV  
Alarm  
Remot acknowledge signal  
(R-ACK)/DI6  
R-mode  
Fault  
FLT lamp  
EDSX11-137b  
Date Dec. 24, 2003  
PDG3  
Allowable signal source resistance:  
100 or less (Zener barrier connection  
unallowable)  
SPECIFICATIONS  
1. Input Signals  
Performance under reference condition(23± 2˚C,  
55±10%RH, Power voltage and frequency variation ±1%,  
free from the effect of external noise) unless otherwise  
specified.  
Influence by signal source resistance:  
About 0.25 µV/Ω  
Influence by ambient temperature:  
±0.2% FS/10°C ±1°C or less.  
Influence by power supply fluctuation:  
±0.2% FS ±1˚C or less  
1-1 Analog input signal  
• Number of inputs  
8 inputs  
Burnout detection: Provided  
Isolation: Isolated from internal circuit.  
(3) Resistance bulb (option)  
Types and measurable ranges:  
* See Table 2.  
Input accuracy: ±0.2% FS ±1 digit  
Input accuracy guarantee range:  
-5% to 105% of input range  
• Inpute signal types  
: DC voltage, thermocouple (option), resistance bulb (op-  
tion)  
Two thermocouple inputs or two resistance bulb inputs  
are selectable.  
Allowable wiring resistance: 10or  
less per wire, provided wiring resis-  
tance must be equal among 3 wires (Ze-  
ner barrier connection unallowable)  
•Influence by ambient tempera-  
ture: ±0.2% FS/10˚C or less.  
Influence by power supply fluctuation:  
±0.2% FS or less  
Burnout detection: Provided  
(1) DC voltage • Input range: Selectable among 0 to 5 V  
DC, 1 to 5 V DC and 0 to 10 V DC  
Initial set before delivery : 1 to 5 V DC  
Input accuracy: ±0.1% of input span±1  
digit  
Scaling (Industrial data conversion) :  
Settable within a range from -32767 to  
32767  
4, 3, 2, 1 or 0 digit below decimal point  
is selectable.  
Initial set before delivery : 0.00% to  
100.00%  
Industrial unit: Settable in up to 8 char-  
acters  
Isolation: Isolated from internal circuit.  
[Note] FS: full span.  
• Sampling period  
: 100 ms  
Usable characters: Alphabets numerals,  
1-2 Digital input signal  
• Number of inputs  
: 10 inputs  
• Electrical specifications  
: No-voltage contact or transistor contact  
symbols such as +, , ,etc.  
*
Input accuracy guarantee range: 5% to  
105% of input range.  
Maximum continuous permissible volt-  
age: ±35 V  
Input resistance: 1 Mor more  
Influence by ambient temperature:  
±0.1% FS/10°C or less.  
Influence by power supply fluctuation:  
±0.1% FS or less.  
Isolation : Non-isolated from internal cir-  
cuit.  
ON/0 V, OFF/24 V, ON current/about 8  
mA  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
each digital input and output.  
• Contact rating : 30 V DC, 10 mA or more  
• Signal judgment  
: No-voltage contact  
In case of current input:  
Shunt resistor need to be connected to  
the analog input terminal.  
Contact resistance;  
200 or less at ON,  
100 kor more at OFF  
: Transistor contact  
1V max at ON.,  
leakage current 100µA max. at OFF  
(250 shunt resistor is optional item)  
(2) Thermocouple (option)  
Types and measurable ranges:  
* See Table 2.  
2. Output Signals  
Input accuracy: ±0.2% FS ±1 digit  
[Note]B type: ±5% between 0 to 400˚C  
S and R type: ±1%between 0 to 500˚C  
All type of TC: ±5% under–100˚C  
Reference junction compensation error:  
±1.0°C (provided measurable range is  
50°C and higher)  
Performance under reference condition(23± 2˚C,  
55±10%RH, Power voltage and frequency variation ±1%,  
free from the effect of external noise) unless otherwise  
specified.  
2-1 Analog output signal  
[Note]Reference junction compensa-  
tion resistor is connected at external  
input terminal in case of thermo-  
couple input is ordered.  
Input accuracy guarantee range: 5%  
to 105% of input range.  
(1) Auxiliary analog output  
• Number of outputs:  
: 4 outputs  
• Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V  
DC and 0 to 10 V DC  
Initial set before delivery: 1 to 5 V DC  
Input resistance: 1 Mor more  
2
• Output accuracy  
: ±0.1% FS  
• Load resistance  
: 15 kor more  
• Output guarantee range  
: 1 to 5 VDC : –12.5% to 112.5%  
4.Setting and Operation  
(1) Set point setting method  
• Setting key  
: Up key/down key  
• Setting speed : About 40 s/FS  
• Setting resolution  
: 0.05% FS/each key press  
: 0 to 5 VDC : 0% to 112.5%  
: 0 to 10VDC : 0% to 105%  
(2) Operation mode  
• Kinds of operation mode  
• Influence by power supply fluctuation  
: ±0.1% FS or less  
: R and L  
[Note] R: Remote mode (operation according to exter-  
nal set point)  
•Isolation  
: Non-isolated from internal circuit  
L: Local mode (operation according to the inter-  
nal set point)  
• Changeover : Balance bumpless changeover from Lo-  
cal to Remote  
2-2 Digital output signal  
• Number of outputs  
: 10 outputs  
• Electrical specifications  
: Transistor open collector  
Balanceless bumpless in other  
changeover  
1 V max. at ON, 10 µA max at OFF.  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
[Note] Balance bumpless changeover is a method  
where each setting value needs to be balanced  
by operator himself at the time of changeover.  
Balanceless bumpless changeover is a method  
where each setting value is automatically bal-  
anced by the ratio setter at the time of  
changeover.  
each digital input and output.  
• Output rating : 30 V DC, 100 mA max. (resistive load)  
2-3 Fault output signal (terminal symbol FLT)  
• Number of outputs  
(3) Security  
: 1 output  
• Electrical specifications  
• Method  
• Password  
: Setting of a password  
: Settable in 4 numerals (within 0000 to  
ffff)  
: Transistor open collector  
1 V max. at ON, 10 µA max at OFF.  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
each digital input and output.  
Initial set before delivery: 0000  
• Contents of security  
: Inhibition of parameter setting  
(4) Other setting items  
• Output rating : 30 V DC, 100 mA max. (resistive load)  
• Tag name  
: Settable in up to 8 characters  
Usable characters; alphabes, numerals,  
symboles such as +, – , ,etc.  
*
3. Display  
5.Power Supply  
• Voltage rating : 100 V to 240 V AC/24 V DC  
• Allowable range  
• Display unit : 16 Colors graphic liquid crystal display,  
with CFL back light and contrast adjust  
function.  
: 85 V to 264 V AC/20 V to 30 V DC  
• Contents of display  
• Frequency  
• Power consumption  
: 60 VA or less (100 V to 240 V AC)  
: 30 W or less (24 V DC)  
Power supply output voltage  
(terminal symbol VP and PC)  
: 20V to 30V DC,max. 40mA  
: 47 to 63 Hz  
: Menu  
: Loop panel  
Bar graph display, digital display, etc.  
: Trend screen (max. 8 screens)  
: Alarm and alarm historical screen  
: Analog input/output and digital input/  
output indication screen  
: WAFER connection screen  
: Parameter setting screen  
3
PDG3  
6. General performance and characteristics  
• Insulation resistance  
9. Self-Diagnosis  
• Control and computation circuit failure  
: 500 V DC, 50 Mor more.  
• Dielectric strength  
: Monitoring with watchdog timer  
• Input signal failure  
: Voltage/current input  
: 2,000 V AC for 1 minute between  
power terminal and ground terminal in  
case of 100 V to 240 V AC power supply  
: 500 V AC for 1 minute between power  
terminal and ground terminal in case of  
24 V DC power supply.  
: 500 V AC for 1 minute between signal  
communication terminals and ground  
terminal  
Monitoring of range over  
: Thermocouple and resistance bulb  
Monitoring of disconection  
• Behavior at failure  
: FLT is indicated, FLT lamp lights, and  
FLT output signal turns on.  
10. Structure  
• Enclosure  
• Finish color  
• Rush current : 60 A or less. (100 V AC to 240 V AC  
power supply)  
: Plastic (material: PC-ABS)  
: Front frame and enclosure both gray  
• Clock  
: Set and display year, month, day, hour,  
minute, second  
• Flame resistance  
: UL94V-0  
accuracy : ±100 ppm except of time lag  
shorter than 1 s / power ON / OFF ac-  
tion.  
• Protection  
: Front face; IP54 (display unit and opera-  
tion key)  
• External dimensions (W x H x D)  
• Memory backup  
: Protection by lithium battery.  
: 72 x 144 x 280 mm  
• Mass  
• Mounting method  
: Flush on indoor panel  
: 1.9 kg or less  
(expected battery life is about 2 years  
under room temperature)  
Parameter and program are stored non-  
volatile memory.  
Vertical mounting as standard  
Tilted mounting allowed within back-  
ward angle 0° to 45°.  
7. Operating and storage conditions  
• Operating temperature  
: 0 to 50˚C  
: 0 to 40°C in case of multiple mounting  
90° to 45°  
( Temperature change rate : Max. 10˚C / h)  
• Transport and storage temperature  
: -20 to 70˚C  
For panel cutout dimension, refer to  
Panel Cutout Dimensions  
( Temperature change rate : Max. 20˚C / h)  
• Operating humidity  
• External terminal  
: Compression terminal type  
: 5 to 90% RH, condensation unallowable  
• Transport and storage humidity  
: 5 to 95% RH, condensation unallowable  
• Operating continuous vibration  
: 4.9 m/s2 or less  
11. Communications (option)  
11-1 RS485 interface-1  
Communication behavior  
: Slave  
• Transport and storage shock  
: Fall of 60cm max. in packed status  
• Communication protocol  
: Modbus® protocol  
• Physical specification  
: EIA RS-485  
• Communication method  
: Half-duplex, bit serial  
: Start-stop synchronizing  
• Connection form  
: Multi-drop  
• Communication speed  
: 19.2 kbps  
• Communication distance  
: Max. 500 m in total  
• Number of connectable units  
8. Power Failure and restart Function  
• Permissible duration of momentary power failure  
: 20 ms at 90V AC (100 V to 240 V AC  
only)  
[Note] In case of 24 V DC, system power supply unit  
(model: PXJ) is recommended to avoid power  
failure problem.  
• Behavior at power failure detection  
: Control stops at detection of power fail-  
ure.  
• Power recovery mode  
: Selectable initial start and continuous  
start  
: Max. 31 units  
• Data length  
• Parity  
• Stop bit  
: Fixed to 8 bits  
: Odd / Even / None  
: 1 or 2  
• Isolation  
• Terminator  
: Isolated from internal circuit  
: 100 (optional item)  
• Communication items  
: Parameters and process value.  
• RS232C / RS485 signal converter (optional item)  
: Code symbol: PDZT0001  
4
12. Memory Card Interface (option)  
• Specification : Compact Flash® (Based on CFA)  
• Compatible memory card  
: 5 V flash memory card  
Capacity 4, 20 and 32 MB  
• Application  
: Process data logging (32 points or less)  
• Saving period : 1s to 2h  
• Data storage capacity  
Memory card  
capacity  
Data storge  
4MB  
about 180 thousand data  
about 900 thousand data  
about 1.35 million data  
20MB  
32MB  
[Note] The data of max. 16 points (4 screens) can be  
storaged at storage time as 1 s.  
• Format method  
: Dependent on this setter  
• Data readout : Readout by PC using PCMCIA card slot  
• Recommended memory card  
: Made by Sandisk corporation  
Sandisk compact Flash memory card is  
standardized and on the market.  
13. Standards under Conformity  
(1) General safety  
: IEC 1010-1 (1990)  
EN 61010-1 (1993)  
(2) EMC  
: Emission EN 50081-2 (1994)  
Immunity EN 50082-2 (1995)  
5
PDG3  
Table 1  
List of WAFERS  
WAFER name  
Kinds  
Outline  
WAFER name  
Kinds  
Outline  
Bit concatevate  
8
Outputs digital data as word data to  
an external expansion I/O.  
Slices the digital data acquired as  
word data from an external  
expansion I/O into each bit.  
Encodes an input signal into  
a binary code.  
Generates a sawtooth wave with  
a slope entered for each  
cycle time.  
Converts BCD data into binary data  
and binary data into BCD data.  
Carries out AND,OR,NOT,XOR  
and a combination of these logical  
operations.  
Carries out a combination of  
addition,subtraction,multiplication  
and division.  
Carries out temperature and  
pressure compensation through use  
of differential pressure,compensated  
pressure,proper temperature.  
Carries out segmented-line  
approximation with 15-segmented-  
line function.  
Pulse No.counter  
1
Detects rise of pulse and counts the  
number of pulses.  
Integrates the input signal and  
converts it to number of pulses  
for output.  
Bit slicing  
1
Pulse No.output  
1
Encoder  
1
1
Decoder  
1
2
1
Decodes 2-bit pure binary input and  
outputs it to 4 terminals.  
Sawtooth wave generator  
Running average  
Sample & hold  
Calculates ranning average of input  
data and outputs the result.  
Holds the input value according to  
sample signal(0/1)and continues  
the output.  
Usable for dead time compensation  
control etc.Data sampling can be  
done in 1 sec or 1 min units.  
Outputs ON-OFF signal with  
hysteresis.  
BCD  
5
6
Logical operation  
Dead time  
6
Arithmetic operation  
8
1
ON-OFF  
1
1
1
Alarm  
Compares the input and set value  
and outputs the judgment result.  
Performs output processing in time  
proportional PID control.  
Temperature/pressure  
compensation  
Palse width modurator  
A variety of applications are possible through combination of WAFERS.  
Linearize  
7
Flip-flop  
Pulse width integration  
1
1
RS flip-flop.  
Adds the change of input at each  
basic cycle to the previous  
integration value.  
Selector  
1
Compares two input values,and  
provides High output(Large one),  
Low output(Small one),and result  
of judgement on large/small.  
Selects input or output via a switch  
function.Analog hold circuit also  
provided.  
Outputs on-delay,off-delay timer  
signal via start of input signal  
according to timer setting.  
Carries out absolute value processing  
on input and outputs the result.Also  
judges the sign(Positive,negative)of  
input value and outputs the result.  
Extracts square root of input value  
and outputs the result.Low input  
cutoff function equipped.  
Carries out lead/lag operation on the  
input and outputs the results.  
Used as analog filter function and  
for various compensations.  
Limits the input within the range of  
high/low limit settings,and outputs  
the result.Also outputs high/low  
limit alarm signal.  
Outputs signal which changes...in  
ramp from toward target value at  
the set full scale time.There are two  
of these wafers...in minute unit and  
hour unit.  
Changeover  
Timer  
1
1
1
Absolute value/sign  
inversion  
Square root extraction  
Lead,lag  
1
3
Limiter  
1
2
Ramp function  
Analog averaging  
Analog integration  
1
1
Carries out sequential integration on  
input data,calculates the average  
value at each averaging time,  
and otuputs the result.  
Integrates the value obtained by  
multiplying the input data by  
a proportional constant,and outputs  
the result.  
Pulse generation  
Dead band  
1
1
Outputs a pulse at the set time  
interval.  
Adds dead band compensation to  
the input and outputs the result.  
6
Table 2  
SCOPE OF DELIVERY  
List of Thermocouple and Resistance Bulb Measurable  
range  
Ratio setter, panel mounting bracket, instruction manual  
(depend on code symbols)  
Input signal  
Input type code Input range code Measurable range˚C  
Thermocouple  
J
01  
00  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
00  
01  
02  
03  
04  
05  
06  
07  
0.0~400.0  
0.0~800.0  
0.0~400.0  
0.0~800.0  
0.0~1200.0  
0.0~1600.0  
0.0~1800.0  
Optional Items  
J
Available  
Item  
Type  
Specificatio  
unit  
K
Terminator  
PDZR2001  
For compression terminal  
1
K
for communication (100 )  
Shunt resistor (250 )  
K
PDZS2001  
For compression terminal  
1
1
1
1
1
R
Communication cable (Note1)  
B
For compression terminal, PDZK4xx1  
from PD* to PD*  
With compression  
T
-
200.0  
~
200.0  
400.0  
terminal at both ends  
With M3.5 solderless  
terminal on PLC side  
9-pin connector on PC side  
T
-
150.0~  
For compression terminal, PDZK5xx1  
from PD* to PLC  
E
0.0~800.0  
200.0 800.0  
E
-
~
For compression terminal, PDZK6xx1  
from PD* to PC  
S
0.0~1600.0  
0.0~1300.0  
N
Communication converter PDZT0001  
RS232C / RS485  
signal converter  
Instruction manual in  
book form  
U
-200.0~400.0  
WRe5-26  
PL2  
0.0~2300.0  
0.0~1300.0  
0.0~150.0  
0.0~300.0  
0.0~500.0  
0.0~600.0  
-50.0~100.0  
Ratio Setter  
Instruction Manual  
PDZX3G01  
PDZQ2001  
PDZA1001  
1
Resistance bulb Pt100  
00  
in book form (in English)  
Instruction Manual on  
CD-ROM (in English)  
Mounting bracket  
Instruction manual on  
CD-ROM  
1
1
Improved mounting  
bracket  
-
100.0  
200.0~600.0  
200.0~850.0  
~200.0  
(Note 1) These cables are used for Modbus  
Length needs to be specified.  
.
-
-
Block diagram of electrical isolation  
Solid line shows  
isolation from the  
other units or circuits.  
Power  
supply  
Power supply  
unit  
DI1 to DI10  
DI / DO  
unit  
Ground  
PV1  
DO1 to DO10  
Ground  
TC or RTD  
input unit  
AI1 to AI6  
AI / AO  
unit  
TC or RTD  
input unit  
PV2  
AO1 to AO4  
RS485  
(Modbus)  
Communication unit  
7
PDG3  
CODE SYMBOLS  
1 2 3 4 5 6 7 8  
P D G 3 1 -  
9 10111213 1415  
- Y Y  
Y
Description  
Number of loops <5th digit code>  
1
1 loop  
External terminal <6th digit code>  
Compression terminal  
2
Input signal <7th digit code>  
1 to 5 V DC  
Thermocouple  
A
C
D
Note 1  
Note 2  
Note 2  
Resistance bulb Pt100  
Power supply voltage <9th digit code>  
A
B
100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz  
24V DC (Usable range 20 to 30V DC)  
Operation mode <10th digit code>  
Remote-Local changeable type  
R
Communicatioin / Memory card interface <12th digit code>  
(Slave)  
Without  
Without  
RS485  
RS485  
(Master)  
Without  
Without  
Without  
Without  
(memory card interface) Note 3 Note 4  
Without  
With  
Y
M
C
Without  
With  
Note 5  
Note 5  
U
Instruction manual <13th digit code>  
Without  
Y
D
With Instruction manual on CD-ROM (in Japanese and English)  
Note 1) For current input, a shunt resistor is used for conversion into voltage.  
Shunt resistor is optional item.  
Note 2) Thermocouple and resistance bulb input are opitons.  
Allowable up to 2 points.  
Note 3) Communication cable and terminator are optional items.  
Note 4) Recommended maker: Sandisk corporation.  
Note 5) Slave interface is Modbus protocol.  
Note 6) Input signal and measurable range initial set before delibvery is as follows.  
For specification of voltage input, scale is 0.00 to 100.00%  
For specification of thermocouple, K, 0.0 to 400.0˚C.  
For specification of resistance bulb is 0.0 to 150.0˚C.  
8
OUTLINE DIAGRAM (Unit : mm)  
Terminal cover  
Panel thickness 8mm or less  
Mounting bracket  
Panel  
72  
21.6  
280  
Mounting bracket  
Note) The distance between other instruments and low end of PDG shall be more than 100mm.  
MOUNTING BRACKET  
50  
205  
PANEL CUTOUT DIMENSIONS  
For mounting  
one unit  
For mounting  
multiple "n" units  
Number of  
units n  
2
+1  
0
68 +0.7  
(72.2n-4)  
0
9
PDG3  
EXTERNAL CONNECTION DIAGRAM  
1
2
3
4
5
6
7
8
AI1  
SC  
AI2  
AI3  
SC  
AI4  
AI5  
SC  
AI6  
SC  
VP  
PC  
DI9  
DI10  
DO9  
DO10  
22  
23  
24  
25  
26  
27  
28  
29  
30  
MI+2  
MI-2  
MI+3  
MI-3  
MI+4  
MI-4  
DO6  
DO7  
DO8  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
MI+1  
MI-1  
AO1  
SC  
AO2  
AO3  
SC  
Voltage  
input  
VPD  
AO4  
FLT  
9
10  
11  
12  
13  
14  
15  
16  
31 DIO-COM  
32  
33  
DO1  
DO2  
DO3  
DO4  
DO5  
DI1  
VPD  
PCD  
(+)  
()  
DI6  
DI7  
24 V external  
Power supply  
34 DIO-COM  
35  
36  
37  
38  
39  
40  
41  
42  
DI8  
OPT+  
OPT-  
COM  
I+2  
Io2  
Rcj2  
I-2  
58 DIO-COM  
59  
60  
PCD  
(+)  
17 MOD+  
18 MOD-  
19  
20  
21  
DI2  
DI3  
PCD  
(+)  
RS-485  
(Modbus  
()  
(COM)  
b
)
Rcj  
Process  
variable  
input 2  
COM  
VPD  
PCD  
61 DIO-COM  
A
62  
63  
64  
65  
66  
67  
DI4  
DI5  
I+1  
Io1  
Rcj1  
I-1  
24 V  
()  
Power  
supply  
for DIO  
B
(+)  
Resistance  
Voltage Thermo-  
b
Rcj  
bulb  
input  
input  
couple  
input  
Process  
variable  
input 1  
A
()  
B
Resistance  
Voltage Thermo-  
bulb  
input  
couple  
input  
input  
G
N/L/+  
Power source 100 to 240V AC  
Power source 24V DC  
~
+
INPUT/OUTPUT TERMINAL FUNCTION (when preset WAFER)  
Input signal name  
PV input  
Input terminal  
I+1I-1  
I+2I-2  
AI1  
Output signal name  
Output terminal  
AO1  
Computed value output (SO)  
Squared computed value (SO2)  
PV compensation signal (KPV)  
Set value output signal (SV)  
Don't use  
External AMV input  
AO2  
Universal analog input  
Universal analog input  
Universal analog input  
Universal analog input  
Universal analog input  
Universal analog input  
Universal digital input  
Universal digital input  
Universal digital input  
Universal digital input  
Universal digital input  
Universal digital input  
Universal digital input  
Remote acknowledge signal (R-ACK)  
Universal digital input  
Universal digital input  
AO3  
AI2  
AO4  
Analog  
MI+1MI-1  
MI+2MI-2  
MI+3MI-3  
MI+4MI-4  
DO1  
AI3  
Don't use  
AI4  
Don't use  
AI5  
Don't use  
AI6  
Universal digital output  
Universal digital output  
Universal digital output  
Universal digital output  
Universal digital output  
Universal digital output  
Local mode output (LS)  
Remote request (R-REQ)  
Upper alarm output (H)  
Lower alame output (L)  
Fault output (FLT-DO)  
Don't use  
DI1  
DO2  
DI2  
DO3  
DI3  
DO4  
DI4  
DO5  
DI5  
DO6  
DI6  
Digital  
DO7  
DI7  
DO8  
DI8  
DO9  
DI9  
DO10  
DI10  
FLT  
OPT+  
Don't use  
OPT-  
10  
11  
PDG3  
[Note] Windows is the registered trade mark of Microsoft corporation.  
[Note] Modbus is the registered trade mark of Gould Modicon.  
[Note] Compact Flash is the registered trade mark of Sandisk corporation.  
Caution on Safety  
*Before using this product, be sure to read its instruction manual in advance.  
Head Office  
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan  
http://www.fesys.co.jp/eng  
Sales Div.  
International Sales Dept.  
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan  
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187  
http: //www.fic-net.jp/eng  
Printed in Japan  
Information in this catalog is subject to change without notice.  

相关型号:

EDSX11-138B

FC SERIES ELECTRONIC INDICATOR
FUJI

EDSX11-140A

Digital Controller COMPACT CONTROLLER M [CC-M] (PROGRAMMABLE STEP OUTPUT TYPE)
FUJI

EDSX3-113C

IN-SITU ZIRCONIA OXYGEN ANALYZER ">
FUJI

EDSX3-119B

IN-SITU ZIRCONIA OXYGEN ANALYZER < ZIRCOMAT-C >
FUJI

EDSX3-137D

IN-SITU ZIRCONIA OXYGEN ANALYZER
FUJI

EDSX5-71

FCX – AX SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-72

FFCCXX – –AAX SSEERRIIEESS REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-73

FCX – AX SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-74

FCX – AX SERIES SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI

EDSX5-75

FCX – C SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-76A

FCX – C SERIES PRESSURE TRANSMITTER
FUJI

EDSX5-77

FCX –AX SERIES PRESSURE TRANSMITTER Hydroseal® Diaphragm Version
FUJI