Digital Controller  
COMPACT CONTROLLER M [CC-M]  
(PROGRAMMABLE CONTINUOUS OUTPUT TYPE)  
DATA SHEET  
PDA3  
The Compact Controller M (programmable continuous out-  
put type) is a multi-loop process controller.  
It accepts 1 to 5 V DC and signals from thermocouples and  
resistance bulb as input, and is provided with abundant con-  
trol and computation functions to allow configuring a flex-  
ible system with a high cost performance.  
FEATURES  
1. Multi-loop controller of up to 4 control outputs.  
CC-M has max.4 control outputs,that is real 4-loop multi-  
loop controller.  
[Note] In this data sheet, the term "loop" is used in the  
same meaning as the quantity of control output.  
2. Control and computation functions dependent on wafers  
Control and computation functions are implemented by  
combining function-software packages called "WAFERS."  
Since the WAFERS are built in the controller, optimum  
system can be programmed by using the front-panel keys  
and the PC based configurator.  
(1) PID control  
• Number of loops and PID  
: Selectable among the following  
3. High visibility ensured with color graphic display  
A color LCD is adopted for graphic display of multi-loop  
bar graph and trend screens,etc.  
1 loop (1 control output / 2PID)  
2 loops (2 control outputs / 4PID)  
4 loops (4 control outputs / 8PID)  
4. Communication function (option)  
• Proportional band (P)  
RS-485 (Modbus protocol or OPTO22 interface ) are  
available.  
5. Soft logic function (option)  
PLC function can be implemented by IEC61131-3 stan-  
dard programming language through the PC based con-  
figuration software.  
: 1.0 to 3276.7%, set at 3000.0% for de-  
livery  
• Integration time (I)  
: 0.1 to 3276.7 s, set at 3000.0 s for deliv-  
ery  
• Derivative time (D)  
: 0.0 to 900.0 s, set at 0.0 s for delivery  
(2) Programming function  
• Programming method  
: WAFER connection  
• Program capacity  
: 48 WAFERS x 4 loops (max. 192 WA-  
6. Back-up (option)  
If the controller becomes faulty, influence over the sys-  
tem can be evaded by changing the built-in backup opera-  
tion unit.  
7. Memory card (option)  
Memory card can save any data, for example process in-  
put, WAFER output, etc.  
FERS)  
A maximum of 48 WAFERS usable in 1  
loop  
• Kind of wafer : 100 kinds listed in Table 1  
(3) Computation cycle  
: 200 ms for 4-loop (8PID) control of sim-  
plicity PID  
SPECIFICATIONS  
1. Control and Computation Functions  
Control and computation functions are implemented by  
combining function-software packages called "WAFERS."  
Combination of WAFERS is called "WAFER connection."  
CC-M comprises 100 kinds of WAFERS.  
WAFER connection is made by operating the keys on the  
front panel or using the PC based configurator.  
(4) Alarm function  
• Method  
• Kinds  
: Alarm can be displayed and output  
through WAFER connection.  
: Each high/low of PV, SV and MV, PV  
change rate alarm, MV change rate  
alarm, high/low deviations.  
EDSX11-132e  
Date Dec. 24, 2003  
PDA3  
2. Input Signals  
Influence by signal source resistance:  
About 0.25 µV/Ω  
Influence by ambient temperature:  
±0.2% FS/10°C ±1°C or less.  
Influence by power supply fluctuation:  
±0.2% FS ±1˚C or less  
Performance under reference condition(23± 2˚C,  
55±10%RH, Power voltage and frequency variation ±1%,  
free from the effect of external noise) unless otherwise  
specified.  
2-1 Analog input signal  
• Number of inputs  
8 inputs  
Burnout detection: Provided  
Isolation: Isolated from internal circuit.  
(3) Resistance bulb (option)  
Types and measurable ranges:  
* See Table 2.  
• Inpute signal types:  
DC voltage, thermocouple (option), re-  
sistance bulb (option)  
Input accuracy: ±0.2% FS ±1 digit  
Input accuracy guarantee range:  
-5% to 105% of input range  
Allowable wiring resistance: 10or  
less per wire, provided wiring resis-  
tance must be equal among 3 wires (Ze-  
ner barrier connection unallowable)  
•Influence by ambient tempera-  
ture: ±0.2% FS/10˚C or less.  
Two thermocouple inputs or two resis-  
tance bulb inputs are selectable.  
(1) DC voltage • Input range: Selectable among 0 to 5 V  
DC, 1 to 5 V DC and 0 to 10 V DC  
Initial set before delivery : 1 to 5 V DC  
Input accuracy: ±0.1% of input span±1  
digit  
Scaling (Engineering data conversion) :  
Settable within a range from -32767 to  
32767  
Influence by power supply fluctuation:  
±0.2% FS or less  
Burnout detection: Provided  
4, 3, 2, 1 or 0 digit below decimal point  
is selectable.  
Isolation: Isolated from internal circuit.  
[Note] FS: full span.  
Initial set before delivery : 0.00% to  
100.00%  
Engineering unit: Settable in up to 8  
characters  
• Sampling period  
: 100 ms  
Usable characters: Alphabets numerals,  
2-2 Digital input signal  
• Number of inputs  
: 10 inputs  
• Electrical specifications  
: No-voltage contact or transistor contact  
symbols such as +, , ,etc.  
*
Input accuracy guarantee range: 5% to  
105% of input range.  
Maximum continuous permissible volt-  
age: ±35 V  
Input resistance: 1 Mor more  
Influence by ambient temperature:  
±0.1% FS/10°C or less.  
Influence by power supply fluctuation:  
±0.1% FS or less.  
Isolation : Non-isolated from internal cir-  
cuit.  
ON/0 V, OFF/24 V, ON current/about 8  
mA  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
each digital input and output.  
• Contact rating : 30 V DC, 10 mA or more  
• Signal judgment  
: No-voltage contact  
In case of current input:  
Shunt resistor need to be connected to  
the analog input terminal.  
Contact resistance;  
200 or less at ON,  
100 kor more at OFF  
: Transistor contact  
(250 shunt resistor is optional item)  
(2) Thermocouple (option)  
1V max at ON.,  
Types and measurable ranges:  
* See Table 2.  
leakage current 100µA max. at OFF  
Input accuracy: ±0.2% FS ±1 digit  
[Note]B type: ±5% between 0 to 400˚C  
S and R type: ±1%between 0 to 500˚C  
All type of TC: ±5% under–100˚C  
Reference junction compensation error:  
±1.0°C (provided measurable range is  
50°C and higher)  
[Note]Reference junction compensa-  
tion resistor is connected at external  
input terminal in case of thermo-  
couple input is ordered.  
3. Output Signals  
Performance under reference condition(23± 2˚C,  
55±10%RH, Power voltage and frequency variation ±1%,  
free from the effect of external noise) unless otherwise  
specified.  
3-1 Analog output signal  
(1) Control output  
• Number of outputs  
: Selectable among 1, 2 and 4 outputs  
• Output signal : 4 to 20 mA DC  
• Output accuracy  
Input accuracy guarantee range: 5%  
to 105% of input range.  
: ±0.2% FS  
Input resistance: 1 Mor more  
Allowable signal source resistance:  
100 or less (Zener barrier connection  
unallowable)  
• Load resistance  
: 600 or less  
2
• Output accuracy guarantee range  
: 2 to 22 mA DC  
5.Setting and Operation  
(1) Set point setting method  
• Influence by ambient temperature  
: ±0.2% FS/10˚C or less  
• Influence by power supply fluctuation  
: ±0.2% FS or less  
• Setting key  
• Setting speed : About 40 s/FS  
• Setting resolution  
: Up key/down key  
: 0.05% FS/each key press  
• Isolation  
(2) Auxiliary analog output  
• Number of outputs:  
: Non-isolated from internal circuit  
(2) Control output operation method  
• Operation key : Up key, down key and high-speed key  
• Operation speed  
: 4 outputs  
: About 40 s/FS (usual),  
• Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V  
DC and 0 to 10 V DC  
about 8 s/FS (high speed)  
(3) Operation mode  
Initial set before delivery: 1 to 5 V DC  
• Output accuracy  
• Kinds of operation mode  
: C, A, and M  
: ±0.1% FS  
[Note] C : Cascade mode (operation according to  
remote set point)  
• Load resistance  
: 15 kor more  
A : Auto mode (operation according to the  
local set point)  
M : Manual mode (control output to be  
manually operated by operator)  
• Changeover : Balance bumpless changeover from  
Auto to Cascade  
• Output guarantee range  
: 1 to 5 VDC : –12.5% to 112.5%  
: 0 to 5 VDC : 0% to 112.5%  
: 0 to 10VDC : 0% to 105%  
• Influence by power supply fluctuation  
: ±0.1% FS or less  
Balanceless bumpless in other Auto to  
Cascade  
•Isolation  
: Non-isolated from internal circuit  
Balanceless bumpless in other  
changeover  
3-2 Digital output signal  
• Number of outputs  
: 10 outputs  
• Electrical specifications  
: Transistor open collector  
[Note] Balance bumpless changeover is a  
method where each setting value  
needs to be balanced by operator him-  
self at the time of changeover.  
Balanceless bumpless changeover is a  
method where each setting value is au-  
tomatically balanced by the controller at  
the time of changeover.  
1 V max. at ON, 10 µA max at OFF.  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
each digital input and output.  
• Output rating : 30 V DC, 100 mA max. (resistive load)  
(4) Security  
• Method  
• Password  
: Setting of a password  
: Settable in 4 numerals (within 0000 to  
ffff)  
3-3 Fault output signal (terminal symbol FLT)  
• Number of outputs  
: 1 output  
Initial set before delivery: 0000  
• Electrical specifications  
• Contents of security  
: Inhibition of parameter setting  
(5) Other setting items  
: Transistor open collector  
1 V max. at ON, 10 µA max at OFF.  
Isolated from the internal circuit by  
photocoupler. Not isolated between  
each digital input and output.  
• Tag name  
: Settable in up to 8 characters  
Usable characters; alphabes, numerals,  
symboles such as +, – , ,etc.  
*
• Output rating : 30 V DC, 100 mA max. (resistive load)  
6.Power Supply  
• Voltage rating : 100 V to 240 V AC/24 V DC  
• Allowable range  
4. Display  
• Display unit : 16 Colors graphic liquid crystal display,  
with CFL back light and contrast adjust  
function.  
: 85 V to 264 V AC/20 V to 30 V DC  
• Frequency  
• Power consumption  
: 60 VA or less (100 V to 240 V AC)  
: 30 W or less (24 V DC)  
Power supply output voltage  
(terminal symbol VP and PC)  
: 20V to 30V DC,max. 40mA  
: 47 to 63 Hz  
• Contents of display  
: Menu  
: Loop panel (1, 2, 4 and 8 loops)  
Bar graph display, digital display, etc.  
[Note] The term "loop" hereby indicates  
the number of control blocks. It does  
not mean the number of control out  
puts.  
: Tuning screen  
: Trend screen (max. 8 screens)  
: Alarm and alarm historical screen  
: Analog input/output and digital input/  
output indication screen  
: WAFER connection screen  
: Parameter setting screen  
3
PDA3  
10. Self-Diagnosis  
• Control and computation circuit failure  
7. General performance and characteristics  
• Insulation resistance  
: 500 V DC, 50 Mor more.  
• Dielectric strength  
: Monitoring with watchdog timer  
• Input signal failure  
: Voltage/current input  
: 2,000 V AC for 1 minute between  
power terminal and ground terminal in  
case of 100 V to 240 V AC power supply  
: 500 V AC for 1 minute between power  
terminal and ground terminal in case of  
24 V DC power supply.  
: 500 V AC for 1 minute between signal  
communication terminals and ground  
terminal  
Monitoring of range over  
: Thermocouple and resistance bulb  
Monitoring of disconnection  
• Control output signal failure  
: Monitoring of disconnection by read  
back check  
• Behavior at failure  
: FLT is indicated, FLT lamp lights, FLT  
output signal turns on, control stops and  
control output is held.  
: 60 A or less. (100 V AC to 240 V AC  
power supply)  
• Rush current  
• Clock  
: Set and display year, month, day, hour,  
minute, second  
11. Structure  
• Enclosure  
• Finish color  
• Flame resistance  
: UL94V-0  
• Protection  
accuracy : ±100 ppm except of time lag  
shorter than 1 s / power ON / OFF ac-  
tion.  
: Plastic (material: PC-ABS)  
: Front frame and enclosure both gray  
• Memory backup  
: Protection by lithium battery.  
: Front face; IP54 (display unit and opera-  
tion key)  
(expected battery life is about 2 years  
under room temperature)  
• External dimensions (W x H x D)  
Parameter and program are stored non-  
volatile memory.  
: 72 x 144 x 280 mm  
• Mass  
• Mounting method  
: Flush on indoor panel  
: 1.9 kg or less  
8. Operating and storage conditions  
Vertical mounting as standard  
Tilted mounting allowed within back-  
ward angle 0° to 45°.  
• Operating temperature  
: 0 to 50˚C  
: 0 to 40°C in case of multiple mounting  
( Temperature change rate  
: Max. 10˚C / h)  
• Transport and storage temperature  
: -20 to 70˚C  
90° to 45°  
( Temprature change rate  
: Max. 20˚C / h)  
• Operating humidity  
For panel cutout dimension, refer to  
Panel Cutout Dimensions  
: 5 to 90% RH, condensation unallowable  
• Transport and storage humidity  
: 5 to 95% RH, condensation unallowable  
• External terminal  
: Compression terminal type  
12. Backup Function (option)  
• Method : With backup operation unit  
• Number of control outputs  
: 1, 2 or 4 outputs selectable.  
• Operating continuous vibration  
: 4.9 m/s2 or less  
• Transport and storage shock  
: Fall of 60cm max. in packed status  
• Indication  
: Control output indication of each loop  
(mA indication)  
9. Power Failure and restart Function  
• Permissible duration of momentary power failure  
: 20 ms at 90V AC (100 V to 240 V AC  
only)  
• Indicator  
: 21-segment LED  
• Indication changeover  
: Changeable to each loop by loop selec-  
In the case of 24V DC, it is recom-  
mended to avoid power failure problem  
that system power supply unit with  
permissible duration of momentary  
power failure of 20ms or more (PXJ, for  
example) is used.  
tion key  
Loop No. indicated by 1-digit LED  
• Operation key : Control output up, control output down,  
loop selection  
• Operation resolution  
: 5%  
• Behavior at power failure detection  
: Control stops at detection of power fail-  
ure.  
• Backup changeover  
: Changeover has been made by the HM  
(Hard Manual) switch. However,  
changeover cannot be made when the  
backup operation unit is faulty.  
: In all loops, changeover to the HM  
mode is blanceless and bumpless.  
• Power recovery mode  
: Selectable initial start and continuous  
start  
4
14. Soft logic function (option)  
[Note] The both of soft logic function and WAFER is not  
available to operate one time.  
13. Communications (option)  
13-1 RS485 interface-1  
Communication behavior  
: Slave  
Programming method  
: Based on IEC 61131-3  
• Communication protocol  
: Modbus® protocol  
available language;  
Ladder diagram (LD)  
• Physical specification  
: EIA RS-485  
• Communication method  
: Half-duplex, bit serial  
: Start-stop synchronizing  
• Connection form  
: Multi-drop  
• Communication speed  
Sequential function chart (SFC)  
Function block diagram (FBD)  
: Programming is to be carried out using  
the PC based configuration software.  
Programming and editing are not al-  
lowed on the controller  
: 19.2 kbps  
Number of steps  
: 2k steps of ladder  
• Communication distance  
: Max. 500 m in total  
Computation cycle  
: 200 ms / 2k steps of ladder  
• Number of connectable units  
: Max. 31 units  
: Fixed to 8 bits  
: Odd / Even / None  
: 1 or 2  
15. Memory Card Interface (option)  
Specification : Compact Flash® (Based on CFA)  
Compatible memory card  
• Data length  
• Parity  
• Stop bit  
: Isolated from internal circuit  
: 100 (optional item)  
: 5 V flash memory card  
Capacity 4, 20 and 32 MB  
• Isolation  
• Terminator  
Application  
Saving period : 1s to 2h  
Data storage capacity  
: Process data logging (32 points or less)  
• Communication items  
: Parameters and process value.  
• RS232C / RS485 signal converter (optional item)  
: Code symbol: PDZT0001  
Memory card  
capacity  
Data storge  
4MB  
about 180 thousand data  
about 900 thousand data  
about 1.35 million data  
13-2 RS485 interface-2  
Communication behavior  
: Master  
20MB  
32MB  
: I/O extension  
Analog input / output : Max.4  
Digital input / output : Max.32  
Usage  
[Note] The data of max. 16 points (4 screens)  
can be storaged at storage time as 1 s.  
:
• Format method  
Communication protocol  
: OPTO22 interface  
Physical specification  
: EIA RS485  
Communication method  
: Half-duplex, bit serial  
: Start-stop synchronizing  
Communication speed  
: Dependent on this controller  
: Readout by PC using PCMCIA card slot  
• Data readout  
• Recommended memory card  
: Made by Sandisk corporation  
Sandisk compact Flash memory card is  
standardized and on the market.  
: 57.6 kbps  
Communication distance  
: Max.50m in total  
Number of connectable units  
: Max.31 units  
[Note] Number of units is limited depend  
on the number of I/O points.  
: Isolated from internal circuit  
: 100 (optional item)  
Isolation  
Terminator  
Communication item  
: Parameters, process values,etc.  
• Connectable slave unit  
: SNAP I/O series (OPTO22 corpora-  
tion)  
5
PDA3  
16. Standards under Conformity  
(1) General safety  
WAFER name  
Linearize  
Kinds  
Outline  
7
Carries out segmented-line  
approximation with 15-segmented-  
line function.  
Time schedule control by step or  
polygonal line approximation with  
7 segments.  
: IEC 1010-1 (1990)  
EN 61010-1 (1993)  
Program control  
4
(2) EMC  
: Emission EN 50081-2 (1994)  
Immunity EN 50082-2 (1995)  
Flip-flop  
Pulse width integration  
1
1
RS flip-flop.  
Adds the change of input at each  
basic cycle to the previous  
integration value.  
17. Configuration Software  
17-1 Programming loader software  
(code symbol : PDZP2001)  
Selector  
1
Compares two input values,and  
provides High output(Large one),  
Low output(Small one),and result  
of judgement on large/small.  
Selects input or output via a switch  
function.Analog hold circuit also  
provided.  
Outputs on-delay,off-delay timer  
signal via start of input signal  
according to timer setting.  
Carries out absolute value processing  
on input and outputs the result.Also  
judges the sign(Positive,negative)of  
input value and outputs the result.  
This software is installed on the CD-ROM form instruction  
manual (PDZQ2001) supplied with the main unit.  
Communication cable (PDZL1001) is optionally available.  
WAFER connection can be entered, edited, uploaded and  
downloaded.  
Changeover  
Timer  
1
1
1
Operation parameter can be entered, edited, uploaded  
and downloaded.  
Absolute value/sign  
inversion  
17-2 Soft logic configurator (optional item)  
(code symbol : ZOZ C-KDS-WD2A)  
*
Programming method  
Square root extraction  
Lead,lag  
1
3
Extracts square root of input value  
and outputs the result.Low input  
cutoff function equipped.  
: Based on IEC 61131-3  
[Note] The program made by this software cannot be  
changed by the controller function key.  
Carries out lead/lag operation on the  
input and outputs the results.  
Used as analog filter function and  
for various compensations.  
Limits the input within the range of  
high/low limit settings,and outputs  
the result.Also outputs high/low  
limit alarm signal.  
Outputs signal which changes...in  
ramp from toward target value at  
the set full scale time.There are two  
of these wafers...in minute unit and  
hour unit.  
17-3 Recommended personal computer system  
Hardware  
: DOS/V machine, Pentium100MHz or  
higher  
Free hard disk capacity 40MB or more,  
memory capacity 32MB or more  
Limiter  
1
2
Ramp function  
Operating system  
: Windows 98 SE/2000/XP English ver-  
sion  
Analog averaging  
Analog integration  
1
1
Carries out sequential integration on  
input data,calculates the average  
value at each averaging time,  
and otuputs the result.  
Integrates the value obtained by  
multiplying the input data by  
a proportional constant,and outputs  
the result.  
Outputs a pulse at the set time  
interval.  
Adds dead band compensation to  
the input and outputs the result.  
Detects rise of pulse and counts the  
number of pulses.  
Integrates the input signal and  
converts it to number of pulses  
for output.  
Decodes 2-bit pure binary input and  
outputs it to 4 terminals.  
Calculates ranning average of input  
data and outputs the result.  
Holds the input value according to  
sample signal(0/1)and continues  
the output.  
Usable for dead time compensation  
control etc.Data sampling can be  
done in 1 sec or 1 min units.  
Outputs ON-OFF signal with  
hysteresis.  
17-4 Cable (code symbol : PDZL1001)  
Using the configuration software, the configuration file is  
downloaded via RS232C transmission cable.  
Table 1  
Pulse generation  
Dead band  
1
1
1
1
List of WAFERS  
WAFER name  
Kinds  
Outline  
Primary PID  
9
Carries out computation on the  
primary loop.  
Pulse No.counter  
Pulse No.output  
Secondary PID  
Gain schedule  
5
2
Carries out computation on the  
secondary loop.  
Outputs the PID parameter  
corresponding to input 1 according  
to the gain schedule table.  
Outputs digital data as word data to  
an external expansion I/O.  
Slices the digital data acquired as  
word data from an external  
expansion I/O into each bit.  
Encodes an input signal into  
a binary code.  
Decoder  
1
2
1
Bit concatevate  
Bit slicing  
8
1
Running average  
Sample & hold  
Encoder  
1
1
Dead time  
6
Sawtooth wave generator  
Generates a sawtooth wave with  
a slope entered for each  
cycle time.  
ON-OFF  
1
1
1
8
BCD  
5
6
Converts BCD data into binary data  
and binary data into BCD data.  
Carries out AND, OR, NOT, XOR  
and a combination of these logical  
operations.  
Alarm  
Compares the input and set value  
and outputs the judgment result.  
Performs output processing in time  
proportional PID control.  
Indicate input data on the front  
display (using 3 bar-graph display)  
Logical operation  
Palse width modurator  
Indicator  
Arithmetic operation  
8
1
Carries out a combination of  
addition, subtraction, multiplication  
and division.  
Carries out temperature and  
pressure compensation through use  
of differential pressure, compensated  
pressure, proper temperature.  
A variety of applications are possible through combination of WAFERS.  
Temperature/pressure  
compensation  
6
Table 2  
SCOPE OF DELIVERY  
List of Thermocouple and Resistance Bulb Measurable  
range  
Controller, panel mounting bracket, instruction manual  
(depend on code symbols)  
Input signal  
Input type code Input range code Measurable range˚C  
Thermocouple  
J
01  
00  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
00  
01  
02  
03  
04  
05  
06  
07  
0.0~400.0  
0.0~800.0  
0.0~400.0  
0.0~800.0  
0.0~1200.0  
0.0~1600.0  
0.0~1800.0  
Optional Items  
J
Available  
Item  
Type  
Specification  
K
unit  
Terminator  
for communication (100 )  
PDZR2001  
For compression terminal  
1
K
K
Shunt resistor (250 )  
PDZS2001  
For compression terminal  
1
1
R
Communication cable for PDZL1001  
configuration software  
Commonly usable cable  
for configuration software  
(3m length)  
B
T
-
200.0  
~
200.0  
400.0  
Communication cable (Note1)  
For compression terminal, PDZK4xx1  
from PDA to PDA  
T
-
150.0~  
With compression  
terminal at both ends  
1
1
1
1
1
E
0.0~800.0  
200.0 800.0  
E
-
~
For compression terminal, PDZK5xx1  
from PDA to PLC  
With M3.5 solderless  
terminal on PLC side  
S
0.0~1600.0  
0.0~1300.0  
For compression terminal, PDZK6xx1  
from PDA to PC  
9-pin connector on PC side  
N
U
-200.0~400.0  
Communication converter PDZT0001  
RS232C / RS485  
signal converter  
WRe5-26  
PL2  
0.0~2300.0  
0.0~1300.0  
0.0~150.0  
0.0~300.0  
0.0~500.0  
0.0~600.0  
-50.0~100.0  
Compact Controller M  
(CC-M) Instruction Manual  
in book form (in English)  
PDZX5001  
PDZX4001  
PDZQ2001  
Instruction manual in  
book form  
Resistance bulb Pt100  
00  
Compact Controller M  
(CC-M) Introductory Guide  
in book form (in English)  
Instruction manual in  
book form  
1
1
1
Instruction Manual on  
CD-ROM (in English)  
(Note2)  
Instruction manual on  
CD-ROM  
-
100.0  
200.0~600.0  
200.0~850.0  
~200.0  
Mounting bracket (Note3) PDZA1001  
Improved mounting  
bracket  
-
-
(Note 1) These cables are used for Modbus  
Length needs to be specified.  
.
(Note 2) The instruction manual, introductory guide and programming loader  
software (PDZP2001) are included.  
(Note 3) This is the improved mounting bracket adopted from PDA-2.  
Refer to the outline diagram for shape and dimensions.  
Block diagram of electrical isolation  
Solid line shows  
isolation from the  
other units or circuits.  
Power  
supply  
Power supply  
unit  
DI1 to DI10  
DI / DO  
unit  
Ground  
PV1  
DO1 to DO10  
Ground  
TC or RTD  
input unit  
AI1 to AI6  
AI / AO  
unit  
MI1 to MI14  
AO1 to AO4  
RS485 (OPTO22)  
TC or RTD  
input unit  
PV2  
RS485  
(Modbus)  
Communication unit  
7
PDA3  
CODE SYMBOLS  
1 2 3 4 5 6 7 8  
P D A 1 -  
9 10111213 1415  
-
Description  
Controller function <4th digit code>  
Programmable type  
3
Note 1  
Note 2  
Number of control loops <5th digit code>  
1 loop (1 control output)  
2 loops (2 control outputs)  
1
2
4
4 loops (4 control outputs)  
External terminal <6th digit code>  
Compression terminal  
2
Input signal <7th digit code>  
1 to 5 V DC  
Thermocouple  
A
C
D
Note 3  
Note 4  
Note 4  
Resistance bulb Pt100  
Power supply voltage <9th digit code>  
A
B
100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz  
24V DC (Usable range 20 to 30V DC)  
Operation mode <10th digit code>  
C
Cascade-Auto-Manual changeable type  
Backup operation unit <11th digit code>  
Without  
Y
A
B
C
D
E
F
For 1 control output, 100 to 240 V AC  
For 2 control outputs, 100 to 240 V AC  
For 4 control outputs, 100 to 240 V AC  
For 1 control output, 24 V DC  
For 2 control outputs, 24 V DC  
For 4 control outputs, 24 V DC  
Communicatioin / Memory card interface <12th digit code>  
(Slave)  
Without  
Without  
RS485  
RS485  
RS485  
RS485  
(Master)  
Without  
Without  
Without  
RS485  
(memory card interface) Note5 Note6  
Without  
With  
Y
M
C
D
U
R
Without  
Without  
With  
Note7  
Note7  
Note7  
Note7  
Without  
RS485  
With  
Instruction manual <13th digit code>  
Without  
Y
D
Instruction manual on CD-ROM (in Japanese and English) Note11  
Programming method <14th digit code>  
WAFER connection method  
Soft logic method  
1
2
Note 8  
Factory configuration<15th digit code>  
Without WAFER connection  
With up to 48 WAFER connection  
With more than 49 WAFER connection  
0
8
9
Note 9  
Note10  
Note10  
Note 1) Control and computation function could be done by WAFER connection or soft logic function.  
Note 2) Control loop means the number of control output.  
Note 3) For current input, a shunt resistor is used for conversion into voltage.  
Shunt resistor is optional item.  
Note 4) Thermocouple and resistance bulb input are opitons.  
Allowable up to 2 points.  
Note 5) Communication cable and terminator are optional items.  
Note 6) Recommended maker: Sandisk corporation.  
Note 7) Slave interface is Modbus protocol and master interface is OPTO22 interface  
Note 8) Programming method conforming with IEC61131-3.  
.
Optional items Soft logic configurator is necessary for programming.  
The both of Soft logic function and WAFER is not available to operate one time.  
Note 9) In this case, WAFER connection programming should be made by user.  
Connection tool (Programming loader) is optional item.  
When set "2" on the 14th digit code, "0" should be set on the 15th digit code.  
Note 10) WAFER connection specification sheets need to be prepared and submitted by user to Fuji.  
Input signal and measurable range initial set before delibvery is as follows.  
For specification of voltage input, scale is 0.00 to 100.00%  
For specification of thermocouple, K, 0.0 to 400.0˚C.  
For specification of resistance bulb is 0.0 to 150.0˚C.  
Note 11) Programming Loader (PDZP2001) is included in the CD-ROM.  
Communication cable (PDZL1001) is optionally available.  
This instruction manual is recorded in PDF format file. To read this manual,  
Adobe Acrobat Reader is required. Setup program of Acrobat Reader is also  
recorded on this CD-ROM.  
8
FUNCTIONAL DIAGRAM  
RS485 (Modbus  
)
PC /  
PLC  
Communication  
Control and computation  
(option)  
WAFER region  
Loop 4  
Loop 3  
Loop 2  
Loop 1  
max.4  
loops  
Control output  
Analog input  
Memory  
card  
(option)  
Compression  
terminal  
Thermocople /  
Resistance bulb  
(option)  
1st  
PID  
Analog  
output  
2nd  
PID  
Digital  
input  
Digital  
output  
or  
Soft logic function  
(Based on IEC 61131-3)  
Communication  
(option)  
PC  
RS485 (OPTO22  
)
interface  
OPTO22  
SNAP I/O  
Configuration software  
Back up operation unit  
(option)  
9
PDA3  
OUTLINE DIAGRAM (Unit : mm)  
Terminal cover  
Panel thickness 8 mm or less  
Cover bracket  
Panel  
72  
21.6  
280  
Mounting bracket  
Note) The distance between other instruments and low end of PDA shall be more than 100mm.  
10  
MOUNTING BRACKET  
50  
205  
PANEL CUTOUT DIMENSIONS  
For mounting  
one unit  
For mounting  
multiple nunits  
Number of  
n
2
n ; Q'TY  
+1  
0
+0.7  
0
(72.2n-4)  
68  
11  
PDA3  
EXTERNAL CONNECTION DIAGRAM  
Manipulated  
output  
Manipulated  
1
2
3
4
5
6
7
8
AI1  
SC  
AI2  
AI3  
SC  
AI4  
AI5  
SC  
AI6  
SC  
VP  
PC  
DI9  
DI10  
DO9  
DO10  
22  
23  
24  
25  
26  
27  
28  
29  
30  
MI+2  
MI-2  
MI+3  
MI-3  
MI+4  
MI-4  
DO6  
DO7  
DO8  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
MI+1  
MI-1  
AO1  
SC  
AO2  
AO3  
SC  
2
output  
1
Manipulated  
output  
3
Voltage  
input  
Voltage  
output  
Manipulated  
output  
4
AO4  
FLT  
9
10  
11  
12  
13  
14  
15  
16  
31 DIO-COM  
32  
33  
DO1  
DO2  
DO3  
DO4  
DO5  
DI1  
PCD  
VPD  
(+)  
(-)  
DI6  
DI7  
24 V external  
supply  
34 DIO-COM  
RS-485  
35  
36  
37  
38  
39  
40  
41  
42  
DI8  
OPT+  
OPT-  
COM  
I+2  
Io2  
Rcj-2  
I-2  
communication  
(Opto22)  
downloading  
(+)  
(-)  
RS-485  
commun-  
ication  
58 DIO-COM  
59  
60  
(COM)  
(+)  
PCD  
17 MOD+  
18 MOD-  
19  
20  
21  
DI2  
DI3  
(Modbus)  
uploading  
(+)  
(-)  
(+)  
Process  
value  
Rcj  
(-)  
COM  
VPD  
PCD  
61 DIO-COM  
(COM)  
PCD  
input 2  
62  
63  
64  
65  
66  
67  
DI4  
DI5  
I+1  
Io1  
Rcj-1  
I-1  
VPD  
(+)  
24 V  
supply  
for  
(-)  
(+)  
Process  
Voltage Thermo- Resistance  
value  
input 1  
DIO  
Rcj  
(-)  
input  
couple  
input  
bulb  
input  
(-)  
Voltage Thermo-  
Resistance  
bulb  
input  
input  
couple  
input  
G
N/- L/+  
Instrument power supply 100 to 240VAC  
Grounding  
Instrument power supply 24VDC  
[Note] Windows is the registered trade mark of Microsoft corporation.  
[Note] Modbus is the registered trade mark of Gould Modicon.  
[Note] Compact Flash is the registered trade mark of Sandisk corporation.  
[Note] OPTO22 interface and SNAP I/O is the registered trade mark of OPTO22(USA).  
[Note] Adobe and Acrobat are trademarks of Adobe Systems Incorporated.  
Caution on Safety  
*Before using this product, be sure to read its instruction manual in advance.  
Head Office  
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan  
http://www.fesys.co.jp/eng  
Sales Div.  
International Sales Dept.  
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan  
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187  
http: //www.fic-net.jp/eng  
Printed in Japan  
Information in this catalog is subject to change without notice.  

相关型号:

EDSX11-133

Z SERIES FUZZY CONTROLLER X (48)48mm)
FUJI

EDSX11-134

Z SERIES FUZZY CONTROLLER X (48)96, 96)96mm)
FUJI

EDSX11-135B

FC SERIES MANUAL LOADER(CONTINUOUS OUTPUT TYPE)
FUJI

EDSX11-136B

FC SERIES SETTER(CONTINUOUS OUTPUT TYPE)
FUJI

EDSX11-137B

FC SERIES RATIO SETTER
FUJI

EDSX11-138B

FC SERIES ELECTRONIC INDICATOR
FUJI

EDSX11-140A

Digital Controller COMPACT CONTROLLER M [CC-M] (PROGRAMMABLE STEP OUTPUT TYPE)
FUJI

EDSX3-113C

IN-SITU ZIRCONIA OXYGEN ANALYZER ">
FUJI

EDSX3-119B

IN-SITU ZIRCONIA OXYGEN ANALYZER < ZIRCOMAT-C >
FUJI

EDSX3-137D

IN-SITU ZIRCONIA OXYGEN ANALYZER
FUJI

EDSX5-71

FCX – AX SERIES ABSOLUTE PRESSURE TRANSMITTER
FUJI

EDSX5-72

FFCCXX – –AAX SSEERRIIEESS REMOTE SEAL TYPE PRESSURE TRANSMITTER
FUJI