EDSX11-135B [FUJI]
FC SERIES MANUAL LOADER(CONTINUOUS OUTPUT TYPE); FC系列手动加载程序(连续输出型)型号: | EDSX11-135B |
厂家: | FUJI ELECTRIC |
描述: | FC SERIES MANUAL LOADER(CONTINUOUS OUTPUT TYPE) |
文件: | 总12页 (文件大小:109K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
FC SERIES MANUAL LOADER
(CONTINUOUS OUTPUT TYPE)
DATA SHEET
PDB3
The FC series Manual Loader carries out remote control in
combination with a controller.
This product is a manual loader to be used in a process and
it excels in the effect of monitoring due to adoption of a
color LCD.
Besides standard signals of 1 to 5 V DC, input signals from
thermocouples and resistance bulbs can be handled at op-
tion.
FEATURES
1. High visibility ensured with color graphic display
A color LCD is adopted for graphic display of bar graph
and trend screens,etc.
2. Communication function (option)
RS-485 (Modbus protocol) are available.
3. Back-up (option)
If the loader becomes faulty, influence over the system
can be evaded by changing the built-in backup operation
unit.
4. Memory card (option)
Memory card can save any data, for example process in-
put, manipulation output, WAFER output, etc.
Communication
®
RS-485 (Modbus
Transmission terminal
)
PV indicator
MV indicator
Signal name/terminal No.
Signal name/terminal name
Manual mode output/DO8
Linearize
square root
Filter
(KPV)
Process variable input/PV1
(Analog input)
PV compensation signal
(KPV)/AO3
MH
ML
External AMV input/PV2
(Analog input)
Manipulation output (voltage)
(MV)/AO1
MV
M
Manipulation output (current)
/Mi+1, Mi-1
Forced opening constants
MV
HMV
(Option)
Forced opening command
(EXS)/Di9
Upper alarm output (H)/DO9
Lower alarm output (L)/DO10
Fault output (FLT-Do)/FLT
KPV
Alarm
Manual mode command
(SMV)/Di10
Fault
FLT lamp
EDSX11-135b
Date Dec. 24, 2003
PDB3
•Allowable signal source resistance:
100 Ω or less (Zener barrier connection
unallowable)
SPECIFICATIONS
1. Input Signals
Performance under reference condition(23± 2˚C,
55±10%RH, Power voltage and frequency variation ±1%,
free from the effect of external noise) unless otherwise
specified.
•Influence by signal source resistance:
About 0.25 µV/Ω
•Influence by ambient temperature:
±0.2% FS/10°C ±1°C or less.
•Influence by power supply fluctuation:
±0.2% FS ±1˚C or less
1-1 Analog input signal
• Number of inputs
8 inputs
•Burnout detection: Provided
•Isolation: Isolated from internal circuit.
(3) Resistance bulb (option)
•Types and measurable ranges:
* See Table 2.
•Input accuracy: ±0.2% FS ±1 digit
•Input accuracy guarantee range:
-5% to 105% of input range
• Inpute signal types
: DC voltage, thermocouple (option), resistance bulb (op-
tion)
Two thermocouple inputs or two resistance bulb inputs
are selectable.
•Allowable wiring resistance: 10Ω or
less per wire, provided wiring resis-
tance must be equal among 3 wires (Ze-
ner barrier connection unallowable)
•Influence by ambient tempera-
ture: ±0.2% FS/10˚C or less.
•Influence by power supply fluctuation:
±0.2% FS or less
•Burnout detection: Provided
(1) DC voltage • Input range: Selectable among 0 to 5 V
DC, 1 to 5 V DC and 0 to 10 V DC
Initial set before delivery : 1 to 5 V DC
•Input accuracy: ±0.1% of input span±1
digit
•Scaling (Industrial data conversion) :
Settable within a range from -32767 to
32767
4, 3, 2, 1 or 0 digit below decimal point
is selectable.
Initial set before delivery : 0.00% to
100.00%
•Industrial unit: Settable in up to 8 char-
acters
•Isolation: Isolated from internal circuit.
[Note] FS: full span.
• Sampling period
: 100 ms
Usable characters: Alphabets numerals,
1-2 Digital input signal
• Number of inputs
: 10 inputs
• Electrical specifications
: No-voltage contact or transistor contact
symbols such as +, – , ,etc.
*
•Input accuracy guarantee range: –5% to
105% of input range.
•Maximum continuous permissible volt-
age: ±35 V
•Input resistance: 1 MΩ or more
•Influence by ambient temperature:
±0.1% FS/10°C or less.
•Influence by power supply fluctuation:
±0.1% FS or less.
•Isolation : Non-isolated from internal cir-
cuit.
ON/0 V, OFF/24 V, ON current/about 8
mA
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Contact rating : 30 V DC, 10 mA or more
• Signal judgment
: No-voltage contact
•In case of current input:
Shunt resistor need to be connected to
the analog input terminal.
Contact resistance;
200 Ω or less at ON,
100 kΩ or more at OFF
: Transistor contact
1V max at ON.,
leakage current 100µA max. at OFF
(250 Ω shunt resistor is optional item)
(2) Thermocouple (option)
•Types and measurable ranges:
* See Table 2.
2. Output Signals
•Input accuracy: ±0.2% FS ±1 digit
[Note]B type: ±5% between 0 to 400˚C
S and R type: ±1%between 0 to 500˚C
All type of TC: ±5% under–100˚C
•Reference junction compensation error:
±1.0°C (provided measurable range is
–50°C and higher)
[Note]Reference junction compensa-
tion resistor is connected at external
input terminal in case of thermo-
couple input is ordered.
Performance under reference condition(23± 2˚C,
55±10%RH, Power voltage and frequency variation ±1%,
free from the effect of external noise) unless otherwise
specified.
2-1 Analog output signal
(1) Control output
• Number of outputs
: 1 output
• Output signal : 4 to 20 mA DC
• Output accuracy
: ±0.2% FS
•Input accuracy guarantee range: –5%
to 105% of input range.
•Input resistance: 1 MΩ or more
• Load resistance
: 600 Ω or less
2
• Output accuracy guarantee range
: 2 to 22 mA DC
4.Setting and Operation
• Influence by ambient temperature
: ±0.2% FS/10˚C or less
• Influence by power supply fluctuation
: ±0.2% FS or less
(1) Control output operation method
• Operation key : Up key, down key and high-speed key
• Operation speed
: About 40 s/FS (usual),
• Isolation
: Non-isolated from internal circuit
about 8 s/FS (high speed)
(2) Auxiliary analog output
• Number of outputs:
(2) Operation mode
• Kinds of operation mode
: 4 outputs
: A, M and HM
• Types of signal: Selectable among 0 to 5 V DC, 1 to 5 V
DC and 0 to 10 V DC
Initial set before delivery: 1 to 5 V DC
• Output accuracy
[Note] A : Auto mode (operation according to the
remote control signal (voltage input))
M: Manual mode (control output to be manu-
ally operated by operator)
: ±0.1% FS
HM: Hardware Manual mode (operated by
back-up loader)
• Load resistance
: 15 kΩ or more
• Changeover : Balanceless bumpless changeover
[Note] Balanceless bumpless changeover is a method
where each setting value is automatically bal-
anced by the manual loader at the time of
changeover.
• Output guarantee range
: 1 to 5 VDC : –12.5% to 112.5%
: 0 to 5 VDC : 0% to 112.5%
: 0 to 10VDC : 0% to 105%
• Influence by power supply fluctuation
: ±0.1% FS or less
(3) Security
• Method
• Password
: Setting of a password
: Settable in 4 numerals (within 0000 to
ffff)
•Isolation
: Non-isolated from internal circuit
2-2 Digital output signal
• Number of outputs
: 10 outputs
• Electrical specifications
: Transistor open collector
Initial set before delivery: 0000
• Contents of security
: Inhibition of parameter setting
(4) Other setting items
• Tag name
: Settable in up to 8 characters
1 V max. at ON, 10 µA max at OFF.
Isolated from the internal circuit by
photocoupler. Not isolated between
Usable characters; alphabes, numerals,
symboles such as +, – , ,etc.
*
each digital input and output.
5.Power Supply
• Output rating : 30 V DC, 100 mA max. (resistive load)
• Voltage rating : 100 V to 240 V AC/24 V DC
• Allowable range
2-3 Fault output signal (terminal symbol FLT)
• Number of outputs
: 1 output
• Electrical specifications
: 85 V to 264 V AC/20 V to 30 V DC
• Frequency
• Power consumption
: 60 VA or less (100 V to 240 V AC)
: 30 W or less (24 V DC)
•Power supply output voltage
(terminal symbol VP and PC)
: 20V to 30V DC, max. 40mA
: 47 to 63 Hz
: Transistor open collector
1 V max. at ON, 10 µA max at OFF.
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Output rating : 30 V DC, 100 mA max. (resistive load)
3. Display
• Display unit : 16 Colors graphic liquid crystal display,
with CFL back light and contrast adjust
function.
• Contents of display
: Menu
: Loop panel
Bar graph display, digital display, etc.
: Trend screen (max. 8 screens)
: Alarm and alarm historical screen
: Analog input/output and digital input/
output indication screen
: WAFER connection screen
: Parameter setting screen
3
PDB3
6. General performance and characteristics
• Insulation resistance
9. Self-Diagnosis
• Control and computation circuit failure
: 500 V DC, 50 MΩ or more.
• Dielectric strength
: Monitoring with watchdog timer
• Input signal failure
: Voltage/current input
: 2,000 V AC for 1 minute between
power terminal and ground terminal in
case of 100 V to 240 V AC power supply
: 500 V AC for 1 minute between power
terminal and ground terminal in case of
24 V DC power supply.
: 500 V AC for 1 minute between signal
communication terminals and ground
terminal
Monitoring of range over
: Thermocouple and resistance bulb
Monitoring of disconection
• Control output signal failure
: Monitoring of disconnection by read
back check
• Behavior at failure
: FLT is indicated, FLT lamp lights, FLT
output signal turns on, and manipulation
output is held.
• Rush current : 60 A or less. (100 V AC to 240 V AC
power supply)
• Clock
: Set and display year, month, day, hour,
minute, second
10. Structure
• Enclosure
• Finish color
• Flame resistance
: UL94V-0
• Protection
accuracy : ±100 ppm except for time lag
shorter than 1 s / power ON / OFF ac-
tion.
: Plastic (material: PC-ABS)
: Front frame and enclosure both gray
• Memory backup
: Protection by lithium battery.
: Front face; IP54 (display unit and opera-
tion key)
(expected battery life is about 2 years
under room temperature)
• External dimensions (W x H x D)
Parameter and program are stored non-
volatile memory.
: 72 x 144 x 280 mm
• Mass
• Mounting method
: Flush on indoor panel
: 1.9 kg or less
7. Operating and storage conditions
• Mounting place
: Indoor
Vertical mounting as standard
Tilted mounting allowed within back-
ward angle 0° to 45°.
• Operating temperature
: 0 to 50˚C
: 0 to 40°C in case of multiple mounting
( Temperature change rate : Max. 10˚C / h)
• Transport and storage temperature
: -20 to 70˚C
90° to 45°
( Temprature change rate : Max. 20˚C / h)
• Operating humidity
For panel cutout dimension, refer to
Panel Cutout Dimensions
: 5 to 90% RH, condensation unallowable
• Transport and storage humidity
: 5 to 95% RH, condensation unallowable
• Operating continuous vibration
: 4.9 m/s2 or less
• External terminal
: Compression terminal type
11. Backup Function (option)
• Method : With backup operation unit
• Transport and storage shock
: Fall of 60cm max. in packed status
• Number of control output
: 1 output
• Output signal : 4 to 20 mA DC
8. Power Failure and restart Function
• Permissible duration of momentary power failure
: 20 ms at 90V AC (100 V to 240 V AC
only)
• Indication
: Manipulation output indication (mA indi-
cation)
: 21-segment LED
• Indicator
• Operation key : Manipulation output up, manipulation
output down, loop selection
• Operation resolution
[Note] In case of 24 V DC, system power supply unit
(model: PXJ) is recommended to avoid power
failure problem.
: 5%
• Behavior at power failure detection
: Control stops at detection of power fail-
ure.
• Backup changeover
: Changeover has been made by the HM
(Hard Manual) switch. However,
changeover cannot be made when the
backup operation unit is faulty.
: In all loops, changeover to the HM
mode is blanceless and bumpless.
• Power recovery mode
: Selectable initial start and continuous
start
4
12. Communications (option)
12-1 RS485 interface-1
•Communication behavior
: Slave
14. Standards under Conformity
(1) General safety
: IEC 1010-1 (1990)
EN 61010-1 (1993)
• Communication protocol
(2) EMC
: Emission EN 50081-2 (1994)
Immunity EN 50082-2 (1995)
: Modbus® protocol
• Physical specification
: EIA RS-485
• Communication method
: Half-duplex, bit serial
: Start-stop synchronizing
• Connection form
: Multi-drop
• Communication speed
: 19.2 kbps
• Communication distance
: Max. 500 m in total
• Number of connectable units
: Max. 31 units
• Data length
• Parity
• Stop bit
: Fixed to 8 bits
: Odd / Even / None
: 1 or 2
• Isolation
• Terminator
: Isolated from internal circuit
: 100 Ω (optional item)
• Communication items
: Parameters and process value.
• RS232C / RS485 signal converter (optional item)
: Code symbol: PDZT0001
13. Memory Card Interface (option)
• Specification : Compact Flash® (Based on CFA)
• Compatible memory card
: 5 V flash memory card
Capacity 4, 20 and 32 MB
• Application
: Process data logging (32 points or less)
• Saving period : 1s to 2h
• Data storage capacity
Memory card
capacity
Data storge
4MB
about 180 thousand data
about 900 thousand data
about 1.35 million data
20MB
32MB
[Note] The data of max. 16 points (4 screens) can be
storaged at storage time as 1 s.
• Format method
: Dependent on this manual loader
• Data readout : Readout by PC using PCMCIA card slot
• Recommended memory card
: Made by Sandisk corporation
Sandisk CompactFlash memory card is
standardized and on the market.
5
PDB3
Table 1
List of WAFERS
WAFER name
Kinds
Outline
WAFER name
Kinds
Outline
Bit concatevate
8
Outputs digital data as word data to
an external expansion I/O.
Slices the digital data acquired as
word data from an external
expansion I/O into each bit.
Encodes an input signal into
a binary code.
Generates a sawtooth wave with
a slope entered for each
cycle time.
Converts BCD data into binary data
and binary data into BCD data.
Carries out AND,OR,NOT,XOR
and a combination of these logical
operations.
Carries out a combination of
addition,subtraction,multiplication
and division.
Carries out temperature and
pressure compensation through use
of differential pressure,compensated
pressure,proper temperature.
Carries out segmented-line
approximation with 15-segmented-
line function.
Pulse No.counter
1
Detects rise of pulse and counts the
number of pulses.
Integrates the input signal and
converts it to number of pulses
for output.
Bit slicing
1
Pulse No.output
1
Encoder
1
1
Decoder
1
2
1
Decodes 2-bit pure binary input and
outputs it to 4 terminals.
Sawtooth wave generator
Running average
Sample & hold
Calculates ranning average of input
data and outputs the result.
Holds the input value according to
sample signal(0/1)and continues
the output.
Usable for dead time compensation
control etc.Data sampling can be
done in 1 sec or 1 min units.
Outputs ON-OFF signal with
hysteresis.
BCD
5
6
Logical operation
Dead time
6
Arithmetic operation
8
1
ON-OFF
1
1
1
Alarm
Compares the input and set value
and outputs the judgment result.
Performs output processing in time
proportional PID control.
Temperature/pressure
compensation
Palse width modurator
A variety of applications are possible through combination of WAFERS.
Linearize
7
Flip-flop
Pulse width integration
1
1
RS flip-flop.
Adds the change of input at each
basic cycle to the previous
integration value.
Selector
1
Compares two input values,and
provides High output(Large one),
Low output(Small one),and result
of judgement on large/small.
Selects input or output via a switch
function.Analog hold circuit also
provided.
Outputs on-delay,off-delay timer
signal via start of input signal
according to timer setting.
Carries out absolute value processing
on input and outputs the result.Also
judges the sign(Positive,negative)of
input value and outputs the result.
Extracts square root of input value
and outputs the result.Low input
cutoff function equipped.
Carries out lead/lag operation on the
input and outputs the results.
Used as analog filter function and
for various compensations.
Limits the input within the range of
high/low limit settings,and outputs
the result.Also outputs high/low
limit alarm signal.
Outputs signal which changes...in
ramp from toward target value at
the set full scale time.There are two
of these wafers...in minute unit and
hour unit.
Changeover
Timer
1
1
1
Absolute value/sign
inversion
Square root extraction
Lead,lag
1
3
Limiter
1
2
Ramp function
Analog averaging
Analog integration
1
1
Carries out sequential integration on
input data,calculates the average
value at each averaging time,
and otuputs the result.
Integrates the value obtained by
multiplying the input data by
a proportional constant,and outputs
the result.
Pulse generation
Dead band
1
1
Outputs a pulse at the set time
interval.
Adds dead band compensation to
the input and outputs the result.
6
Table 2
SCOPE OF DELIVERY
List of Thermocouple and Resistance Bulb Measurable
range
Manual loader, panel mounting bracket, instruction
manual (depend on code symbols)
Input signal
Input type code Input range code Measurable range˚C
Thermocouple
J
01
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
00
01
02
03
04
05
06
07
0.0~400.0
0.0~800.0
0.0~400.0
0.0~800.0
0.0~1200.0
0.0~1600.0
0.0~1800.0
Optional Items
J
Available
Item
Type
Specificatio
unit
K
Terminator
PDZR2001
For compression terminal
1
K
for communication (100 Ω)
Shunt resistor (250 Ω)
K
PDZS2001
For compression terminal
1
1
1
1
1
R
Communication cable (Note1)
B
For compression terminal, PDZK4xx1
from PD* to PD*
With compression
T
-
200.0
~
200.0
400.0
terminal at both ends
With M3.5 solderless
terminal on PLC side
9-pin connector on PC side
T
-
150.0~
For compression terminal, PDZK5xx1
from PD* to PLC
E
0.0~800.0
200.0 800.0
E
-
~
For compression terminal, PDZK6xx1
from PD* to PC
S
0.0~1600.0
0.0~1300.0
N
Communication converter PDZT0001
RS232C / RS485
signal converter
Instruction manual in
book form
U
-200.0~400.0
WRe5-26
PL2
0.0~2300.0
0.0~1300.0
0.0~150.0
0.0~300.0
0.0~500.0
0.0~600.0
-50.0~100.0
Manual Loader
Instruction Manual
PDZX3B01
PDZQ2001
PDZA1001
1
Resistance bulb Pt100
00
in book form (in English)
Instruction Manual on
CD-ROM (in English)
Mounting bracket
Instruction manual on
CD-ROM
1
1
Improved mounting
bracket
-
100.0
200.0~600.0
200.0~850.0
~200.0
(Note 1) These cables are used for Modbus
Length needs to be specified.
.
-
-
Block diagram of electrical isolation
Solid line shows
isolation from the
other units or circuits.
Power
supply
Power supply
unit
DI1 to DI10
DI / DO
unit
Ground
PV1
DO1 to DO10
Ground
TC or RTD
input unit
AI1 to AI6
MI1
AI / AO
unit
TC or RTD
input unit
PV2
AO1 to AO4
RS485
(Modbus)
Communication unit
7
PDB3
CODE SYMBOLS
1 2 3 4 5 6 7 8
P D B 3 1 -
9 10111213 1415
- Y Y
Description
Number of control loops <5th digit code>
1 loop (1 control output)
1
External terminal <6th digit code>
Compression terminal
2
Input signal <7th digit code>
1 to 5 V DC
Thermocouple
A
C
D
Note 1
Note 2
Note 2
Resistance bulb Pt100
Power supply voltage <9th digit code>
A
B
100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz
24V DC (Usable range 20 to 30V DC)
Operation mode <10th digit code>
Auto-Manual changeable type
A
Backup operation unit <11th digit code>
Without
For 1 control output, 100 to 240 V AC
For 1 control output, 24 V DC
Y
A
D
Communicatioin / Memory card interface <12th digit code>
(Slave)
Without
Without
RS485
RS485
(Master)
Without
Without
Without
Without
(memory card interface) Note 3 Note 4
Without
With
Y
M
C
Without
With
Note 5
Note 5
U
Instruction manual <13th digit code>
Without
Y
D
With Instruction manual on CD-ROM (in Japanese and English)
Note 1) For current input, a shunt resistor is used for conversion into voltage.
Shunt resistor is optional item.
Note 2) Thermocouple and resistance bulb input are opitons.
Allowable up to 2 points.
Note 3) Communication cable and terminator are optional items.
Note 4) Recommended maker: Sandisk corporation.
Note 5) Slave interface is Modbus protocol.
Note 6) Input signal and measurable range initial set before delibvery is as follows.
For specification of voltage input, scale is 0.00 to 100.00%
For specification of thermocouple, K, 0.0 to 400.0˚C.
For specification of resistance bulb is 0.0 to 150.0˚C.
8
OUTLINE DIAGRAM (Unit : mm)
Terminal cover
Panel thickness 8mm or less
Mounting bracket
Panel
72
21.6
280
Mounting bracket
Note) The distance between other instruments and low end of PDB shall be more than 100mm.
MOUNTING BRACKET
50
205
PANEL CUTOUT DIMENSIONS
For mounting
one unit
For mounting
multiple "n" units
Number of
units n
2
+1
0
68 +0.7
(72.2n-4)
0
9
PDB3
EXTERNAL CONNECTION DIAGRAM
1
2
3
4
5
6
7
8
AI1
SC
AI2
AI3
SC
AI4
AI5
SC
AI6
SC
VP
PC
DI9
DI10
DO9
DO10
22
23
24
25
26
27
28
29
30
MI+2
MI-2
MI+3
MI-3
MI+4
MI-4
DO6
DO7
DO8
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
MI+1
MI-1
AO1
SC
AO2
AO3
SC
Manipulation
output
Voltage
input
VPD
AO4
FLT
9
10
11
12
13
14
15
16
31 DIO-COM
32
33
DO1
DO2
DO3
DO4
DO5
DI1
VPD
PCD
(+)
(–)
DI6
DI7
24 V external
Power supply
34 DIO-COM
35
36
37
38
39
40
41
42
DI8
OPT+
OPT-
COM
I+2
Io2
Rcj2
I-2
58 DIO-COM
59
60
PCD
(+)
17 MOD+
18 MOD-
19
20
21
DI2
DI3
PCD
(+)
RS-485
(Modbus
(–)
(COM)
b
)
Rcj
Process
variable
input 2
COM
VPD
PCD
61 DIO-COM
A
62
63
64
65
66
67
DI4
DI5
I+1
Io1
Rcj1
I-1
24 V
(–)
Power
supply
for DIO
B
(+)
Resistance
Voltage Thermo-
b
Rcj
bulb
input
input
couple
input
Process
variable
input 1
A
(–)
B
Resistance
Voltage Thermo-
bulb
input
couple
input
input
G
N/– L/+
Power source 100 to 240V AC
Power source 24V DC
~
–
+
INPUT/OUTPUT TERMINAL FUNCTION (when preset WAFER)
Input signal name
PV input
Input terminal
I+1,I-1
I+2,I-2
AI1
Output signal name
Output terminal
AO1
Manipulation output / Voltage (MV)
Universal analog output
PV compensation signal (KPV)
Universal analog output
External AMV input
AO2
Universal analog input
Universal analog input
Universal analog input
Universal analog input
Universal analog input
Universal analog input
Universal digital input
Universal digital input
Universal digital input
Universal digital input
Universal digital input
Universal digital input
Universal digital input
Universal digital input
Forced opening command
Manual mode command
AO3
AI2
AO4
Analog
AI3
Manipulation output / Current (MI) MI+1,MI-1
AI4
Don't use
MI+2,MI-2
MI+3,MI-3
MI+4,MI-4
DO1
AI5
Don't use
AI6
Don't use
DI1
Universal digital output
Universal digital output
Universal digital output
Universal digital output
Universal digital output
Universal digital output
Universal digital output
Manual mode output (M)
Upper alarm output (H)
Lower alame output (L)
Fault output (FLT-DO)
Don't use
DI2
DO2
DI3
DO3
DI4
DO4
DI5
DO5
DI6
DO6
Digital
DI7
DO7
DI8
DO8
DI9
DO9
DI10
DO10
FLT
OPT+
OPT-
Don't use
10
11
PDB3
[Note] Windows is the registered trade mark of Microsoft corporation.
[Note] Modbus is the registered trade mark of Gould Modicon.
[Note] Compact Flash is the registered trade mark of Sandisk corporation.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Printed in Japan
Information in this catalog is subject to change without notice.
相关型号:
©2020 ICPDF网 联系我们和版权申明